  • IBA DOC

  • SAKLAR SEKSI OTOMATIS ( SSO )AUTOMATIC CIRCUIT SECTIONALISERSAKLAR YANG DILENGKAPI DENGAN KONTROL ELEKTRONIK ,YANG DIGUNAKAN SEBAGAI PENGAMAN SEKSI, DAN BEKERJANYA BERKAITAN DENGAN PENGAMAN DISISI SUMBER ( SEPERTI RELAI RECLOSER ATAU PBO ) .

    MENGISOLIR SEKSI SUTM YANG TERGANGGU SECARA OTOMATIS .

    BILA TIDAK ADA RELAI RECLOSER ATAU PBO DISISI SUMBER MAKA SSO TIDAK BERFUNGSI OTOMATIS ( SEBAGAI SAKLAR BIASA ).

    IBA DOC

  • IBA DOCKLASIFKASI SSO MENURUT PENGINDRAAN : 1. PENGINDRA TEGANGAN ( AUTOMATIC VACCUM CIRUIT ) 2, PENGINDRA ARUS ( AUTOMATIC CIRCUIT RECLOSER )

    MEDIA PEMUTUS : 1. MINYAK 2. VACCUM 3. GAS SF6

    KONTROL : 1. HIDRAULIK 2. ELEKTRONIK

    FASA : 1. FASA TUNGGAL 2. FASA TIGA .

  • IBA DOCAPLIKASISISTEM DISTRIBUSI TM POLA 1 (PENTANAHAN NETRAL R TINGGI) .SSO 1SSO 2TTPCTPCTPOWERCONTROLTRANSFORMERKOTAK PENGATURCONTROL DEVICEPMTAVS 1AVS 2SEKSI 1SEKSI 2SEKSI 3FOCRDGFRRECLOSERR># SEBAGAI ALAT PEMUTUS OTOMATIS UNTUK MEMISAHKAN SALURAN UTAMA DALAM BEBERAPA SEKSI AGAR DAERAH YANG TERGANGGU SEKECIL MUNGKIN .# MAMPU MENUTUP PADA SAAT GANGGUAN DAN MEMBUKA / MENUTUP DALAM KEADAAN BERBEBAN .# BEKERJA BERDASARKAN PENGIDRA TEGANGAN .

  • IBA DOCPRINSIP OPERASI AVS SETTING WAKTU :

    t1 = selang waktu sso bertegangan sampai menutup kontak ( close ) t2 = selang waktu SSO merasakan tegangan sampai trip (< t2 akan lockout ) t3 = selang waktu SSO tidak bertegangan sampai membuka kontak ( trip )

  • IBA DOCPRINSIP OPERASI AVSGANGGUAN DI SEKSI 3 :

    1. Relai kerja , PMT trip , tegangan sistem hilang maka setelah t3 SSO akan trip . 2. setelah waktu interval reclose , recloser di hulu akan memerintahkan PMT reclose pertama . 3. Seksi 1 akan bertegangan , setelah t1 SSO1 close seksi 2 bertegangan , setelah t1 SSO2 masuk . 4. Bila gangguan hilang sistem akan normal . 5. Bila gangguan masih , relai kerja , PMT trip, setelah t3 kedua SSO trip. 6. SSO2 merasakan tegangan < t2 maka SSO2 lockout . 7. Setelah waktu interval reclose ,recloser memerintahkan masuk ( reclose ke 2 ) . 8. Seksi 1 bertegangan ,setelah t1 SSO1 close . 9. Seksi 2 bertegangan, dan 10. Seksi 3 diisolir oleh SSO2 .

  • IBA DOC POLA 2

    SISTEM PENTANAHAN SOLID GROUNDEDSSOSSOPMTOCRGFRPBOPLPL# MELOKALISIR GANGGUAN DALAM SEKSI SEKSI YANG LEBIH KECIL# BEKERJA BERDASARKAN PENGINDRA ARUS ( ARUS HUBUNG SINGKAT )# MEMBUKA DAN LOCKOUT PADA SAAT RANGKAIAN TIDAK BERTEGANGAN . # MEMPUNYAI HITUNGAN UNTUK MEMBUKA( COUNT TO OPEN ) TERGANTUNG DARI PBO DI SISI SUMBER .

  • IBA DOCSENSINGBCTsMATCHINGTRANSFOCOUNTINGRELAYCOUNTINGCIRCUIT MEMORYCIRCUITFIRINGCIRCUITTRIPCOILTRIPSTORAGECAPASITORCOUNTINGCAPASITORINRUSHLOGICTIME DELAYRAISEDLEVELNETWORKVOLTAGERESTRAINTSOURCEVOLTAGERECTIFIERNETWORK806405101520304590BLOCK2 4 6 8PRINSIP KERJA SSO KONTROL ELEKTRONIM PENGINDRA ARUS

  • IBA DOCPRINSIP KERJA SSO KONTROL ELEKTRONIK# Arus di jaringan di deteksi oleh cCT Bushing , kemudian melalui Matching Tranformer dan Rectifier disearahkan dan disimpan dalam Trip Storage Capasitor untuk Triping .# Apabila I > dari arus kerja ( 125% arus kerja ) , Counting relay akan mengisi Counting Capasitor .# Apabila PBO di hulu trip , atau I < 50% arus kerja , Counting Capasitor akan mengisi Counting Circuit ,terjadi penghitungan# Jika hitungan sudah mencapai setting hitunganuntuk membuka maka isyarat akan dikirim ke Firing Circuit .# Trip Storage Capasitor memberikan arus ke trip coil ( Bestable Actuator ) SSO akan open dan lockout .# Tegangan Restraint ( Restraint Voltage ) Bila tegangan tidak diputus , I > lewat SSO , I < 50% arus kerja, maka restraint Voltage akan mencegah Counting Circuit untuk melakukan hitungan .# Restraint Inrush juga mencegah SSO dari penghitungan untuk Trip .

  • IBA DOCOPERASI MEKANIK SSO# Kondisi kontak ditutup ( gambar 1.6a ) pegas Opening dipertahankan energis, untuk operasi trip .# Signal trip mengerjakan Tripping Coil ( Bestable actuator ) mengerjakan trip lever , untuk membebaskan Toglelatch menyebabkan kontak open ( gambar 1.6b)# Closing Full ring memutar rachet dan Crak searah jarum jam menegangkan kedua pegas ( spring Closing / Opening ) gambar 1.6c# Gerakan lengan Crank merentangkan tigle sampai terkunci dan menarik mekanis untuk menutup kontak .# Dapat juga menggunakan motor untuk menegangkan pegas ( motor operated ) .

  • IBA DOCSETTING SSO TIPE MC GRAW EDISONGN3VE1, ARUS KERJA MINIMUM ( Operating Minimum Current )

    HITUNGAN UNTUK MEMBUKA ( Count to Open )

    PENAHAN ARUS INRUSH ( Inrush Current Restraint )

    ARUS KERJA MINIMUM GANGGUANFASA / GROUND :

    HITUNGAN UNTUK MEMBUKA( COUNT TO OPEN ) : N 1 ( N ) = JUMLAH TRIP SAMPAI LOCKOUT .Count to open setting 1 ; 2 ; 3 .Ground Actuating current resistorPhase Actuating Current resistorSetting for phaseActuating Current multiplierSetting for durationOf ground current sensing blockSetting for durationOf raised phaseCurrent sensing

  • IBA DOCSETTING SSO TIPE MC GRAW EDISONGN3VE

    ARUS KERJA MINIMUM GANGGUANFASA / GROUND :

    HITUNGAN UNTUK MEMBUKA( COUNT TO OPEN ) : N 1 ( N ) = JUMLAH TRIP SAMPAI LOCKOUT .

    PENAHAN ARUS INRUSH :

    SIFAT PENAHAN ARUS INRUSH DALAH MENAIKAN LEVELKERJA FASA MINIMUM DARI SSO DENGAN PENGALI X ( 2 ; 4 ; 6 ; 8 KALI )

    ATAU MEMBLOK DETEKSI ARUS LEBIH UNTUK PERIODE : Y ( 5 ; 10 ; 15 ; 20 CYCLE ) BILA SIRKUIT LOGIK MENENTUKAN BAHWA ARUS LEBIH ADALAH ARUS INRUSH .

    DALAM WAKTU YANG SAMA DETEKSI ARUS LEBIH GANGGUAN TANAH DIBLOK SAMA SEKALI UNTUK PERIODE Z ( 0,3 ; 0,7 ; 1,5 ; 3 ; 5 DETIK )PEMILIHAN X , Y , DAN Z DENGAN MEMINDAHKAN KABEL JUMPER .

  • IBA DOCPENGUJIAN SSO PENGUJIAN INDIVIDUAL DARI SSO DAPAT DILAKUKAN DENGAN INJEKSI PRIMER / SEKUNDER .

    JENIS PENGUJIAN :

    1. ARUS KERJA MINIMUM : FASA / GROUND

    2. HITUNGAN UNTUK MEMBUKA ( COUNT TO OPEN )

    3. PENAHAN ARUS INRUSH ( INRUSH CURRENT RESTRAINT )

  • IBA DOCSVacCT 500/5ATANK AMPRANGKAIAN PENGUJIAN SSODENGAN INJEKSI PRIMERSSO MC GRAW EDISONGN3VEmA

  • IBA DOCPROSEDUR PENGUJIAN Arus Kerja Minimum gangguan Fasa. 1. Blok sirkuit perasa gangguan tanah ( lepas dan hubung singkat plug ground . 2. Setel SSO untuk satu hitungan untuk membuka dengan memasang kabel jumper pada terminal nomer 1 . 3. Masukan SSO dengan menekan handel warna kuning . 4. Naikan arus uji kira kira 80% dari arus kerja 5. matikan alat uji SSO tidak membuka 6. Hidupkan alat uji dan naikan arus uji110% dari arus kerja 7. SSO akan menghitung dan membuka . 8. Ulangi butir 3 s/d 7 untuk fasa B dan C 9. Lepas penghubung singkat dan pasang kembali plug ground

  • IBA DOCPROSEDUR PENGUJIAN Arus kerja minimum gangguan fasa ke tanah 1. Pasang plug fasa dan tanah ( set fasa lebih besar dari tanah ) 2. Periksa bahwa SSO diset pada satu hitungan untuk membuka 3. Masukan SSO 4. Uji fasa A ,naikan arus uji kira kira 80% arus kerja minimum 5. Matikan alat uji ( arus menjadi nol ) SSO tidak bekerja 6. Hidupkan alat uji ,dan naikan arus 110% arus kerja 7. Matikan alat uji , SSO akan membuka . 8. Ulangi butir 3 s/d 7 untuk fasa B dan C . Menguji jumlah hitungan untuk membuka 1. Set hitungan untuki membuka dari SSO ( misal 2 atau 3 ). 2. Masukan SSO 3. Uji fasa A dengan arus kira kira 150% dari arus kerja minimum 4. Matikan / hidupkan alat uji dengan menutup / membuka salar S sebanyak setting hitungan untuk membuka . Maka SSO akan membuka dan lockout .

  • IBA DOCCONTROLLOGICSENSINGCIRCUITCHARGEPROTECTIONCRCUITCHARGING CTsTRIPCOILK2K3K3K21211CP1CP2CP3C20C21C40C41C60C61126510943871211C22C23C42C43C62C63C20C21C40C41C60C611S21S11S11S11S21S21S21S11S21S11S11S2S1S2S2S1S1S2C11C10C30C31C51C50C11C31C51C70CONTROL UNIT PCBSECTIONALISER CONTROL UNITPROTECTIONCTsSSO TIPE BRUSH

  • IBA DOCSW 7SW 8SW 9SW 3SW 2SW 1SW 5SW 6SW 4KONTROL ELEKTRONIKTEMPAT KABEL CTARUS KERJA MINIMUM FASADAPAT DISETEL KE TIGA FASANYA DENGAN RENTANGSETELAN 10 A S/D 630A DENGAN STEP 10A LIHATTABEL .SW1 & SW6 UNTUK FASA RSW2 & SW5 UNTUK FASA SSW3 & SW4 UNTUK FASA T

    SW9 UNTUK SETTING GROUND

    SW8 UNTUK SETTING COUNT TO OPEN DAN ENABLE/ DISABLE PROTEKSI GROUND

    SW7 UNTUK SETTING RESET TIMESETTING SSOTIPE BRUSH

  • IBA DOCPOSISI SW1 & SW6 UNTUK SETTING ARUS KERJA MINIMUM FASA R

  • IBA DOCPOSISI SW2 & SW5 UNTUK FASA S SERTA SW3 & SW4 UNTUK FASA T ADALAH SAMA DENGAN POSISI SW1 & SW6 .

  • IBA DOCPOSISI SW9 UNTUK SETTING ARUS KERJA MINIMUM GANGGUAN TANAH

  • IBA DOC

  • IBA DOC1. PROTEKSI GANGGUAN TANAH POSISIKAN SW8.4 SEBAGAI BERIKUT : SW8.4 ENABLE OFFDISABLE ON 2. JUMLAH GANGGUAN YANG MENYEBABKAN LOCKOUT JUMLAH GANGGUAN SW8.1 SW8.2 SW8.3 1 ON - - 2 - ON - 3 - - ONRECLAIM TIME SW7.1 SW7.2 SW7.3 SW7.4 ( DETIK ) 15 ON 30 ON 60 ON 120 ON

  • IBA DOCTRIPCOILCONTROLLOGICSENSINGCIRCUITCHARGEPROTECTIONCRCUITK3K21211CP1CP2CP3C20C21C40C41C60C61126510943871211C22C23C42C43C62C63C20C21C40C41C60C61C11C10C30C31C51C50C11C31C51C70CONTROL UNIT PCBSECTIONALISER CONTROL UNITARVARIACVac10A30VacPENGUJIAN INJEKSISEKUNDER DARI SSO

  • IBA DOCPROSEDUR PENGUJIAN INJEKSI SEKUNDERLepaskan hubungan ke blok terminal dalam panel kontrol .

    Hubungkan catu daya bolak balik 30 V ke salah satu dari pasangan C20 dan C21 ,C40 dan C41 atau C60 dan C61 seperti gambar .

    Hubungkan sumber arus bolak balik ( variac dan tahanan seri ) ke C71 dan ke salah satu C11 atau C31 , C51 seperti gambar karena rasio ct proteksi 64 : 1,maka arus injeksi sama dengan sama dengan arus gangguan ( sisi primer )

    Jika menguji proteksi fasa , proteksi tanah dimatikan ( disable ) Untuk menguji gangguan tanah maka proteksi tanah harus dalam posisi enable . Pastikan bahwa arus kerja fasa harus lebih besar dari setting gangguan tanah .

    Atur besarnya arus uji dan setelah itu matikan alat uji maka SSO akan trip dan lockout .(set count to open 1 )

  • IBA DOCBYPASS SWITCHDISCONNECT SWITCHDISCONNECT SWITCHSURGEARRESTERSURGEARRESTERSECTIONALISERPRINSIP PEMASANGAN

  • IBA DOC