No. 1150 /10-04/P/2004 TUGAS AKHIR TL — 40Z0 EVALUASI KUALITAS UDARA DAN SISTEM VENTILASI PADA RUANGAN PARKIR TERTUTUP (Studi Kasus : Plaza Bandung Indah) oleh : Nama : Erlangga Dwisaputro MM : 15300001 Pembimbing : Dr. Ir. Dwina Roosmini, MS. Dr. Ir. FX Nugroho Soelanii, MBEnv. DEPARTEMEN TEKNIK LINGKUNGAN FAKULTAS TEKNIK SIPIL DAN PERENCANAAN INSTITUT TEKNOLOGI BANDUNG 2004

Upload: zoebair

Post on 13-Apr-2016

212 views

Category:

Documents


0 download

DESCRIPTION

gg

TRANSCRIPT

Page 1: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1

No. 1150/10-04/P/2004

TUGAS AKHIR

TL — 40Z0

EVALUASI KUALITAS UDARA DAN SISTEM VENTILASI

PADA RUANGAN PARKIR TERTUTUP

(Studi Kasus : Plaza Bandung Indah)

oleh :

Nama : Erlangga Dwisaputro

MM : 15300001

Pembimbing : Dr. Ir. Dwina Roosmini, MS.

Dr. Ir. FX Nugroho Soelanii, MBEnv.

DEPARTEMEN TEKNIK LINGKUNGAN

FAKULTAS TEKNIK SIPIL DAN PERENCANAAN

INSTITUT TEKNOLOGI BANDUNG

2004

Page 2: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1
Page 3: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1

Abstrak

Kendaraan bermotor mengeluarkan emisi gas buang di sepanjang jalan yangdilewatinya, termasuk di dalam ruangan parkir tertutup. Zat pencemar tersebutdapat terakumulasi dalam ruangan parkir dan membaharyakan manusia yang adadi dalamnya.• Ventilasi alami dan mekanik dibutuhkan untuk mengeluarkan zatpencemar dan mencatu udara bersih masuk ke dalam ruangan.Bangunan parkir tertutup Plaza Bandung Indah terdiri dari tiga lantai bawahtanah yang sudah dilengkapi dengan sistem ventilasi mekanik. Untuk ,mengevaluasi kualitas udara dan sistem ventilasi yang ada, dilakukanpengukuran terhadap konsentrasi partikulat (PMIO), CO dan pertukaran udara diruangan parkir.Pada Basement Utama total sirkulasi udara mencapai 141490 m 3/jam dengankebutuhan udara bersih menurut standar SNI 03-6572-2001 sebesar 84516m3/jam, sedangkan pada Lower Ground total sirkulasi udara mencapai 314525m3/jam dengan kebutuhan udara bersih menurut standar SNI 03-6572-2001sebesar 31884 m3/jam. Untuk Basement 2 dan Basement 3 dengan volumeruangan yang .lama, sirkulasi udara total pada masing-masing ruangan adalah221971 m3/jam dan 54385 m 3/jam dengan kebutuhan udara bersih menurutstandar SNI 03-6572-2001 sebesar 75774 m3/jam.Pada swat kondisi puncak kepadatan kendaraan terjadi konsentrasi partikulat disemua ruangan masih di bawah nilai ambang batas SE 01/MEN/1997 sebesar 10mg/m3 sedangkan konsentrasi CO di semua ruangan sudah melewati nilaiambang batas SE 01/1viEN/1997 sebesar 25 ppm.Usaha yang dapat dilakukan untuk memperbaiki kondisi udara di ruangan parkiradalah dengan memasang fan di beberapa titik ruangan guna menggerakanudara dan menghindari akumulasi pencemar, mengganti fan pada sistem ventilasimekanik Basement 2 dan Basement 3 agar sirkulasi udara dalam ruangan lebihoptimum dan pertukaran wilayah tugas bagi para petugas setiap 4 jam untukmnenjaga derajat kesehatan mereka tetap baik.

Kata kunci: ventilasi, CO, partikulat, udara bersih

Page 4: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1

Abstract

Motor vehicle releases gas emission alongside the road and also inside ofenclosed park room. The gas emission could accumulate and endanger humanbeing. Therefore the natural and mechanic ventilation are required to put out theemission and supply fresh air into the room.Plaza Bandung Indah 's enclosed building park consists of three basements whichequiped by mechanical ventilation system. Evaluating air quality and ventilationsystem can be done by measuring the concentration of particulate (PMlo), CO andair circulation in each room.Total air circulation in Basement Utama is 141490 m 3/hour with the amount offresh air needed based on standard SNI 03-6572-2001 is equal to 84546 m 3/hour.while total air circulation at Lower Ground is 314525 m 3/hour with the amount offresh air needed based on standard SNI 03-6572-2001 is equal to 31884 m3/hour.For Basement 2 and Basement 3 with equal volume, total air circulation for eachroom is 221971 m3/hour and 54385 m3/hour with the needs of fresh air based onstandard SNI 03-6572-2001 is equal to75774 m3/hour.At the peak of traffic of vehicles happened, the concentration of particulate inevery room still below the tresshold limit value of SE 01/MEN/1997 which isequal tol0 mg/m3 while CO concentration in every room have passed thetresshold limit value of SE 01/MEN/1997 which is equal to 25 ppm.Efforts can be done for improving air condition in the park are with installing fanin several spot places in the room for air movement and avoiding the pollutantaccumulation, changing fans of mechanical ventilation system at Basement 2 andBasement 3 in order to air circulation more optimum and rotation of duty regionfor the worker every 4 hours to keep their kind health degree.

Key words: ventilation, CO, particulate, fresh air

Page 5: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1
Page 6: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1
Page 7: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1
Page 8: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1
Page 9: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1
Page 10: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1
Page 11: jbptitbtl-gdl-s1-2004-erlanggadw-153-2004_ta_-1