sb writeup
TRANSCRIPT
-
8/18/2019 Sb Writeup
1/2
SOOT BLOWER LOGIC – WRITEUP
ITC SPECIALITY DIVISION & PAPER MILLS LTD -400 TDS/D RECOVERY BOILERDOC NO.: 0913-40-90-29-3668; REV.0 SEET NO.: P!"# 3 $% 2
Introduction
Twenty three (23) soot blowers are being provided for the recovery boiler. These soot blowers are provided with
a single motor for both rotary and traverse motions. These soot blowers can be controlled from the following
locations: Soot Blower (Operation from !S)
"ocal #$shb$tton Stations ("#BS)
Control from DCS
#rovision shall be made for %ndivid$al &an$al Operation as well as '$tomatic Se$ence !ontrol ('S!) with
provision for bypassing any blower. ("ocal*emote selection shall be in !S). "ocation of Blowers+ indications
controls and interloc,s will be shown in the &%&%!S for soot blower operation in !S.
Control from Local Pushbutton Stations (LPBS)
#rovision shall be made for %ndivid$al &an$al Operation
Operation from DCS
Pre-start Permissive:
or Soot Blo!ers:
-o Trip !ondition /ist for 0orward Operation (from &!! overload relay)
-o Trip !ondition /ist for *everse Operation (from &!! overload relay)
*emote Operation Selected (from !S)
or Soot Blo!in" Steam Isolation Control #alve ($#-%&'-)
-o Trip !ondition /ist (from &!! overload relay)
*emote Operation Selected (from !S)
Blo!ers in $ome Position:
'll blowers m$st be in 1ome #osition for carrying o$t the se$ence operation.
anual Operation:
'll blowers m$st be in 1ome #osition for carrying o$t the man$al operation.
Before starting $p the blowing operation the Steam %solation alve (42515467&) sho$ld be closed.
!lose the steam %solation alve (42515467&) and then open acc$m Brea,er alve (42515
482). 'fter 9 min$te time interval+ open the rain !ontrol alve (42515469&) for Sootblowers 5
9 to 92 (Boiler Ban, conomiser 'reas) (4251548&) for Sootblowers 5 93 to 23 (s$perheater
'reas) and close the acc$m Brea,er alve (42515482).
425#%!5489 controller shall be set to a$to mode and the set point shall be assigned to 4;,gcm 2.%f the
press$re e/ceeds 49,gcm2 and persist for seconds (tentative) then the press$re controller o$tp$t will
be set to
-
8/18/2019 Sb Writeup
2/2
SOOT BLOWER LOGIC – WRITEUP
ITC SPECIALITY DIVISION & PAPER MILLS LTD -400 TDS/D RECOVERY BOILERDOC NO.: 0913-40-90-29-3668; REV.0 SEET NO.: P!"# 4 $% 2
Then if steam press$re (425#S"5484) is not low+ start the seal air fan and operate the soot blowers
individ$ally.
'fter the completion of blowing operation+ open the rain !ontrol alve (42515469&) (425
1548&) the ac$$m Brea,er alve (42515482) for draining.
Se*uence Operation:
Se$ence of Operation incl$des
Predefined Se*uence:
%n predefined se$ence opening of condensate drain control valve+ closing of condensate drain control
valve after ens$ring ade$ate condensate drain temperat$re and insertion and retrieval of all the soot
blowers that are selected for se$ence operation shall be carried o$t in a se$ential manner. %n
predefined se$ence all the soot blowers will operate one by one.
Soot blowers can be retracted to home position a$tomatically once getting an signal from the
corresponding nd position limit switch or the forced retract timer contact (from &!!).
+ser defined Se*uence:
%n $ser defined se$ence operation opening of condensate drain control valve+ closing of condensate
drain control valve and after ens$ring ade$ate condensate drain temperat$re and insertion and
retrieval of soot blowers that are selected for se$ence operation shall be carried o$t in a se$ential
manner. By selecting the soot blowers in the $ser defined se$ence (from !S)+ the operator can
decide which blowers to be incl$ded in se$ence and which are to be bypassed .Operator can also
select the sootblowers based on the areas as
Sootblowers 9 to 92 in Boiler Ban, conomiser 'rea.
Sootblowers 93 to 23 in S$perheater 'rea.
Soot blowers can be retracted to home position a$tomatically once getting an signal from the
corresponding nd position "imit switch or Timer contact (from &!!).
ault onitorin":
The opening and closing operation of steam isolation valve+ opening and closing of condensate drain
control valve+ forward and retract operations of all the blowers shall be monitored and appropriate
indicationalarms shall be generated to notify the operator the s$ccess or fail$re of each operation.
%f there is a fa$lt d$ring retract operation of any of the blowers+ provision shall be made to
a$tomatically force retract the blower to home position.
The se$ence operation shall be stopped after the affected blower is bro$ght to home position. The
operator can then proceed the se$ence f$rther by pressing reset #B (from !S).
0ail$re of a$to retract operation shall also be ann$nciated so that the operator can ta,e appropriate
action to man$ally bring the blower to home position.