    SOOT BLOWER LOGIC – WRITEUP

    ITC SPECIALITY DIVISION & PAPER MILLS LTD -400 TDS/D RECOVERY BOILERDOC NO.: 0913-40-90-29-3668; REV.0 SEET NO.: P!"# 3 $% 2

    Introduction

    Twenty three (23) soot blowers are being provided for the recovery boiler. These soot blowers are provided with

    a single motor for both rotary and traverse motions. These soot blowers can be controlled from the following

    locations: Soot Blower (Operation from !S)

    "ocal #$shb$tton Stations ("#BS)

    Control from DCS

    #rovision shall be made for %ndivid$al &an$al Operation as well as '$tomatic Se$ence !ontrol ('S!) with

     provision for bypassing any blower. ("ocal*emote selection shall be in !S). "ocation of Blowers+ indications

    controls and interloc,s will be shown in the &%&%!S for soot blower operation in !S.

    Control from Local Pushbutton Stations (LPBS)

    #rovision shall be made for %ndivid$al &an$al Operation

    Operation from DCS

    Pre-start Permissive:

    or Soot Blo!ers:

     

     -o Trip !ondition /ist for 0orward Operation (from &!! overload relay)

     

     -o Trip !ondition /ist for *everse Operation (from &!! overload relay)

     

    *emote Operation Selected (from !S)

     

    or Soot Blo!in" Steam Isolation Control #alve ($#-%&'-)

     

     -o Trip !ondition /ist (from &!! overload relay)

     

    *emote Operation Selected (from !S)

    Blo!ers in $ome Position:

    'll blowers m$st be in 1ome #osition for carrying o$t the se$ence operation.

    anual Operation:

     

    'll blowers m$st be in 1ome #osition for carrying o$t the man$al operation.

    Before starting $p the blowing operation the Steam %solation alve (42515467&) sho$ld be closed.

     

    !lose the steam %solation alve (42515467&) and then open acc$m Brea,er alve (42515

    482). 'fter 9 min$te time interval+ open the rain !ontrol alve (42515469&) for Sootblowers 5

    9 to 92 (Boiler Ban, conomiser 'reas) (4251548&) for Sootblowers 5 93 to 23 (s$perheater 

    'reas) and close the acc$m Brea,er alve (42515482).

     

    425#%!5489 controller shall be set to a$to mode and the set point shall be assigned to 4;,gcm 2.%f the

     press$re e/ceeds 49,gcm2 and persist for   seconds (tentative) then the press$re controller o$tp$t will

     be set to

  • 8/18/2019 Sb Writeup

    2/2

    SOOT BLOWER LOGIC – WRITEUP

    ITC SPECIALITY DIVISION & PAPER MILLS LTD -400 TDS/D RECOVERY BOILERDOC NO.: 0913-40-90-29-3668; REV.0 SEET NO.: P!"# 4 $% 2

    Then if steam press$re (425#S"5484) is not low+ start the seal air fan and operate the soot blowers

    individ$ally.

    'fter the completion of blowing operation+ open the rain !ontrol alve (42515469&) (425

    1548&) the ac$$m Brea,er alve (42515482) for draining. 

    Se*uence Operation:

    Se$ence of Operation incl$des

    Predefined Se*uence:

     

    %n predefined se$ence opening of condensate drain control valve+ closing of condensate drain control

    valve after ens$ring ade$ate condensate drain temperat$re and insertion and retrieval of all the soot

     blowers that are selected for se$ence operation shall be carried o$t in a se$ential manner. %n

     predefined se$ence all the soot blowers will operate one by one.

    Soot blowers can be retracted to home position a$tomatically once getting an signal from the

    corresponding nd position limit switch or the forced retract timer contact (from &!!).

    +ser defined Se*uence:

     %n $ser defined se$ence operation opening of condensate drain control valve+ closing of condensate

    drain control valve and after ens$ring ade$ate condensate drain temperat$re and insertion and

    retrieval of soot blowers that are selected for se$ence operation shall be carried o$t in a se$ential

    manner. By selecting the soot blowers in the $ser defined se$ence (from !S)+ the operator can

    decide which blowers to be incl$ded in se$ence and which are to be bypassed .Operator can also

    select the sootblowers based on the areas as

    Sootblowers 9 to 92 in Boiler Ban, conomiser 'rea.

    Sootblowers 93 to 23 in S$perheater 'rea.

    Soot blowers can be retracted to home position a$tomatically once getting an signal from the

    corresponding nd position "imit switch or Timer contact (from &!!).

    ault onitorin":

     

    The opening and closing operation of steam isolation valve+ opening and closing of condensate drain

    control valve+ forward and retract operations of all the blowers shall be monitored and appropriate

    indicationalarms shall be generated to notify the operator the s$ccess or fail$re of each operation.

    %f there is a fa$lt d$ring retract operation of any of the blowers+ provision shall be made to

    a$tomatically force retract the blower to home position.

     

    The se$ence operation shall be stopped after the affected blower is bro$ght to home position. The

    operator can then proceed the se$ence f$rther by pressing reset #B (from !S).

     

    0ail$re of a$to retract operation shall also be ann$nciated so that the operator can ta,e appropriate

    action to man$ally bring the blower to home position.