TUGAS SISTEM CERDAS DALAM SISTEM TENAGA LISTRIK Dikerjakan Oleh : Nama : Alam Afif Makarim NIM : 21060112140078 Kelas : A UNIVE!I"A! DI#ONE$OO !EMAAN$ 201% 1. Cari standar (SPLN) Sistem Otomasi Gard Ind! (SOGI) " &a'a( : #Standar Sistem Otomasi Gard Ind! a) IE* 618%0 () IE* 611+1,+ #Standar Lin$!n$an !em-a .erala/an .r /eksi n/r l 3an MI men5a - s/an3ar (erik-/ ini : T%&e Test Name T%&e Test Standard Ins-la/i n esis/an e : IE* 602%%,% IE* 602%%, 27 IE* 60870,2,1 Diele /ri i/hs/an3 : IE* 602%%,% IEEE *+7) 0 IE* 602%%, 27 i5h V l/a5e Im.-lse "es/ : IE* 602%%,% IE* 602%%, 27 Vi(ra/i n "es/ : IE* 602%%,21,1 !h k an3 9-m. /es/ : IE* 602%%,21,2

Upload: dedybrianericsonnainggolan

Post on 04-Nov-2015

231 views

Category:

Documents


0 download

DESCRIPTION

aam

TRANSCRIPT

TUGAS SISTEM CERDAS DALAM SISTEM TENAGA LISTRIK

Dikerjakan Oleh :Nama : Alam Afif MakarimNIM : 21060112140078Kelas : A

UNIVERSITAS DIPONEGOROSEMARANG20151. Cari standar (SPLN) Sistem Otomasi Gardu Induk (SOGI) !Jawab :

*Standar Sistem Otomasi Gardu Induk

a. IEC 61850 b. IEC 61131-3

*Standar Lingkungan

Semua peralatan proteksi, control, dan HMI mengacu standar berikut ini :

Type Test Name Type Test Standard

Insulation Resistance : IEC 60255-5 / IEC 60255-27 / IEC 60870-2-1

Dielectric Withstand : IEC 60255-5 / IEEE C37.90 / IEC 60255- 27

High Voltage Impulse Test : IEC 60255-5 / IEC 60255-27

Vibration Test : IEC 60255-21-1

Shock and Bump test : IEC 60255-21-2

Damp Heat Test : IEC 60068-2-3 / IEC 60068-2-30

Cold Test : IEC 60068-2-1 / IEC 60255-6

Dry Heat : IEC 60068-2-2 / IEC 60068-2-1

Enclosure Protection : IEC 60529 / IP 30

Supply variation : IEC 60255-6

Overvoltage (peak withstand) : IEC 60255-6

Supply interruption : IEC 60255-11 / Max. 50ms

Ripple (frequency fluctuations) : IEC 60255-11 / Max. 12%

Supply variations : IEC 60255-6 / 20%

High Frequency Disturbance : IEC 60255-22-1 / IEC 61000-4-12 / IEEE C37.90.1

Electrostatic discharge : IEC 60255-22-2 / IEC 61000-4-2

Radiated Immunity : IEC 60255-22-3 / ANSI C37.90.2 / IEC 61000-4-3

Fast Transient Burst : IEC 60255-22-4 / IEC 61000-4-4 / IEEE C37.90.1 /(ANSI C37.90.1)

Surge immunity : IEC 61000-4-5

High frequency conducted immunity : IEC 61000-4-6

Harmonics Immunity : IEC 61000-4-7

Power Frequency Magnetic Field Immunity : IEC 61000-4-8

Power Frequency : IEC 61000-4-16

Conducted emission : EN 55022

Radiated emission : EN 55022

Radio Interference Withstand : IEC60255-22-3:1992 / ANSI C37.90.2

*Standar KomunikasiGateway ke Control Center :

a. IEC 60870-5-101 (Redundant) b. IEC 60870-5-104 (option)

IED protocol:

a. IEC 61850 IED BCU IED MPU 1 IED MPU 2 BPU IED I/O IED AVR b. DNP3 (optional untuk peralatan pendukung) c. Modbus (optional untuk peralatan pendukung) d. IEC 60870-5-104 (optional) e. IEC 60870-5-103 (optional)

2. Apakah sistem jaringan antara server, workstation, dan control proteksi / bay control unit menggunakan double ring apa jenis yang lain ?

Jawab:

Konfigurasi umum dari Sistem Otomasi Gardu Induk (SOGI) yang menggambarkan tentang pembagian bay level dan station level. Server, workstation, dan control proteksi / bay control unit.

3. Carilah single line diagram termasuk bay lengkap (DS, ES, CB) ! Jawab :

4. Apa yang dimaksud dengan LCP (Local Control Panel) Jawab :

Local Control Panel (LCP) adalah panel luar yang melekat pada transformator tenaga (Power Transformator). Panel ini digunakan terutama sebagai titik lokal untuk mengontrol kipas transformator (dan kadang-kadang pompa) dan untuk menunjukkan suhu lilitan (HV dan LV) dan minyak.