PEMELIHARAAN CUBICLE OUTGOING PT PLN (PERSERO) APD SEMARANG PENYEBAB TRIPNYA INC 04 GI KEBASEN RABU, 06 OKTOBER 2010 . PUKUL 22:13 WIB PMT 20 KV INCOMING TRAFO 4 (60 MVA) GI KEBASEN “TRIP” DENGAN INDIKASI RELE OCR GFR RST N INST BERSAMAAN DENGAN GANGGUAN YANG TERJADI DI PENYULANG KSN 10 (BREAKDOWN ARRESTER PADA RISE POLE PHASA T KSN 10). INDIKASI RELE PADA KSN 10 ADALAH OCR GFR RST N INST, NAMUN PMT KSN 10 “TIDAK TRIP” SEHINGGA ARUS GANGGUAN MENYEBABKAN PMT INCOMING “TRIP”. PUKUL 23:00 WIB PMT KSN 10, KSN 11 DAN KSN 12 “DILEPAS” MELALUI ROPO. UNTUK BEBAN DILIMPAHKAN KSN 10 KE KSN 03 DAN BBS 04, KSN 11 KE KSN 02 SEDANGKAN KSN 12 KE KSN 05. PENANGANAN GANGGUAN UJI CLEARANCE TIME DAN INDIVIDU RELE KSN 10 EVENT AMP INDIVIDUAL RELE TIME CLEARENCE TIME OPENING TIME KETERANGAN I> 10 A 1.006 s 1.201 s 0.195 s LAMBAT 0.145 s I>> 40 A 0.040 s 0.157 s 0.117 s LAMBAT 0.067 s Io> 4 A 2.003 s 2.160 s 0.157 s LAMBAT 0.107 s Io>> 30 A 0.036 s 0.231 s 0.195 s LAMBAT 0.145 s RATA-RATA OPENING TIME PADA PMT MERK ALSTOM TIPE VB 6 ADALAH 0.040 s SAMPAI DENGAN 0.050 s. DARI DATA DI ATAS DAPAT DIAMBIL KESIMPULAN BAHWA PMT KSN 10 MENGALAMI “KETERLAMBATAN WAKTU MEMBUKA”, UNTUK ITU DIPERLUKAN PENGUJIAN BREAKER ANALYZER. UJI BREAKER ANALYZER KSN 10 EVENT PENGUJIAN PERTAMA PENGUJIAN KEDUA PENGUJIAN KSN 12 KETERANGAN OPEN R 206.10 ms 256.85 ms 42.00 ms TERLAMBAT S 205.80 ms 256.75 ms 41.50 ms TERLAMBAT T 205.80 ms 256.95 ms 41.50 ms TERLAMBAT CLOSE R 39.70 ms 40.00 ms 38.50 ms NORMAL S 39.65 ms 39.90 ms 38.50 ms NORMAL T 39.50 ms 39.85 ms 38.50 ms NORMAL HASIL PENGUJIAN KECEPATAN EKSPANSI TERUTAMA “OPENING TIME” PADA PMT KSN 10 DIDAPATKAN BAHWA PMT KSN 10 TERLAMBAT ± 150 ms THOMAS AMBONO 8406022K

Upload: hoangque

Post on 06-Feb-2018

234 views

Category:

Documents


1 download

TRANSCRIPT

PEMELIHARAAN CUBICLE OUTGOINGPT PLN (PERSERO) APD SEMARANG

PENYEBAB TRIPNYA INC 04 GI KEBASEN

RABU, 06 OKTOBER 2010.• PUKUL 22:13 WIB PMT 20 KV INCOMING TRAFO 4 (60 MVA) GI KEBASEN

“TRIP” DENGAN INDIKASI RELE OCR GFR RST N INST BERSAMAAN DENGAN GANGGUAN YANG TERJADI DI PENYULANG KSN 10 (BREAKDOWN ARRESTER PADA RISE POLE PHASA T KSN 10).

• INDIKASI RELE PADA KSN 10 ADALAH OCR GFR RST N INST, NAMUN PMT KSN 10 “TIDAK TRIP” SEHINGGA ARUS GANGGUAN MENYEBABKAN PMT INCOMING “TRIP”.

• PUKUL 23:00 WIB PMT KSN 10, KSN 11 DAN KSN 12 “DILEPAS” MELALUI ROPO. UNTUK BEBAN DILIMPAHKAN KSN 10 KE KSN 03 DAN BBS 04, KSN 11 KE KSN 02 SEDANGKAN KSN 12 KE KSN 05.

PENANGANAN GANGGUAN

• UJI CLEARANCE TIME DAN INDIVIDU RELE KSN 10

EVENT AMPINDIVIDUAL RELE TIME

CLEARENCETIME

OPENING TIME

KETERANGAN

I> 10 A 1.006 s 1.201 s 0.195 s LAMBAT 0.145 sI>> 40 A 0.040 s 0.157 s 0.117 s LAMBAT 0.067 sIo> 4 A 2.003 s 2.160 s 0.157 s LAMBAT 0.107 sIo>> 30 A 0.036 s 0.231 s 0.195 s LAMBAT 0.145 s

RATA-RATA OPENING TIME PADA PMT MERK ALSTOM TIPE VB 6 ADALAH 0.040 s SAMPAI DENGAN 0.050 s. DARI DATA DI ATAS DAPAT DIAMBIL KESIMPULAN BAHWA PMT KSN 10 MENGALAMI “KETERLAMBATAN WAKTU MEMBUKA”, UNTUK ITU DIPERLUKAN PENGUJIAN BREAKER ANALYZER.

• UJI BREAKER ANALYZER KSN 10

EVENTPENGUJIAN PERTAMA

PENGUJIAN KEDUA

PENGUJIAN KSN 12

KETERANGAN

OPENR 206.10 ms 256.85 ms 42.00 ms TERLAMBATS 205.80 ms 256.75 ms 41.50 ms TERLAMBATT 205.80 ms 256.95 ms 41.50 ms TERLAMBAT

CLOSER 39.70 ms 40.00 ms 38.50 ms NORMALS 39.65 ms 39.90 ms 38.50 ms NORMALT 39.50 ms 39.85 ms 38.50 ms NORMAL

HASIL PENGUJIAN KECEPATAN EKSPANSI TERUTAMA “OPENING TIME” PADA PMT KSN 10 DIDAPATKAN BAHWA PMT KSN 10 TERLAMBAT ± 150 ms

THOMAS AMBONO8406022K

PEMELIHARAAN CUBICLE OUTGOINGPT PLN (PERSERO) APD SEMARANG

ATAU 0.150 s. BEGITU JUGA SAAT DILAKUKAN PENGUJIAN KEDUA PADA KUBIKEL LAIN. HASILNYA PMT KSN 10 TERLAMBAT MEMBUKA ± 200 ms ATAU 0.200 s. HASIL PENGUJIAN PERTAMA DAN KEDUA PMT KSN 10 SANGAT BERBEDA BILA DIBANDINGKAN DENGAN PENGUJIAN KSN 12.

THOMAS AMBONO8406022K

OPENING TIME PMT TERLAMBAT ± 0.150 s

OPENINGTIME PMT

TERLAMBAT ± 0.200 s

PEMELIHARAAN CUBICLE OUTGOINGPT PLN (PERSERO) APD SEMARANG

GAMBAR 1 HASIL PENGUJIAN PERTAMA DAN KEDUA KECEPATAN OPENING TIME PMT KSN 10

• PEMERIKSAAN TRIPPING COIL KSN 10

TAHANAN TRIPPING COIL = 93.5 ΩTAHANAN MELALUI TERMINAL 5 – 6 = 93.6 Ω

KESIMPULAN :TRIPPING COIL TIDAK BERMASALAH KARENA TAHANANNYA SESUAI STANDAR (MENANDAKAN KUMPARANNYA TIDAK PUTUS). SETELAH DIPERIKSA TERNYATA “PLUNGER TRIPPING COIL” YANG BERFUNGSI UNTUK MENARIK “MEKANIK TRIPPING SYSTEM PMT” MENGALAMI KEMACETAN YANG DISEBABKAN OLEH VASELINE YANG MENGERING. SEHINGGA SAAT “TRIPPING COIL” MENDAPAT TEGANGAN DARI RELE UNTUK BEKERJA, “PLUNGER TRIPPING COIL” TIDAK MAMPU MENGGERAKKAN “MEKANIK TRIPPING PMT”. HAL INILAH YANG MENGAKIBATKAN PMT KSN 10 “TIDAK TRIP” SAAT MENGALAMI GANGGUAN DAN MENGAKIBATKAN TRIPNYA PMT INCOMING.

THOMAS AMBONO8406022K

Y01

5

6RANGKAIAN

TRIPPING COIL KSN 10

TRIPPING COIL DAN MEKANIK TRIPPING SYSTEM PMT KSN 10

TRIPPING COIL DAN PLUNGER

PMT KSN 10

TRIPPING COIL

PLUNGER

ADJUSTING NUT

KE MEKANIK TRIPPING

PMT

PEMELIHARAAN CUBICLE OUTGOINGPT PLN (PERSERO) APD SEMARANG

GAMBAR 2 TRIPPING COIL DAN MEKANIK TRIPPING PMT KSN 10

• TINDAK LANJUT

MENGGANTI TRIPPING COIL KSN 10 DENGAN TRIPPING COIL PMT CADANGAN. LALU DILAKUKAN PENGUJIAN ULANG BAIK BREAKER ANALYZER MAUPUN CLEARENCE TIME.

EVENT AMP INDIVIDUAL RELE TIME

CLEARENCETIME

OPENING TIME

KETERANGAN

I> 10 A 1.006 s 1.053 s 0.047 s NORMALI>> 40 A 0.040 s 0.087 s 0.047 s NORMALIo> 4 A 2.003 s 2.050 s 0.047 s NORMALIo>> 30 A 0.036 s 0.083 s 0.047 s NORMAL

GAMBAR 3 HASIL UJI BREAKER ANALYZER SETELAH TRIPPING COIL KSN 10 DIGANTI

THOMAS AMBONO8406022K

OPENING TIME PMT SESUAI STANDAR0.040 – 0.050 s