vlt® hvac drive fc 102 1.1-90 kw oper. ifiles.danfoss.com/download/drives/mg11ai9b.pdf · 2.4.5.3...

96
MAKING MODERN LIVING POSSIBLE Petunjuk Pengoperasian VLT ® Drive HVAC FC 102, 1.1-90 kW

Upload: duongnhan

Post on 29-Apr-2019

255 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

MAKING MODERN LIVING POSSIBLE

Petunjuk PengoperasianVLT® Drive HVAC FC 102, 1.1-90 kW

Page 2: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1
Page 3: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Keselamatan

PERINGATANTEGANGAN TINGGI!Konverter frekuensi berisi tegangan tinggi pada saattersambung ke daya input sumber listrik AC. Instalasi,permulaan dan pemeliharaan dapat dilakukan oleh pekerjayang memenuhi standar yang berlaku. Tidak mengikutiprosedur instalasi, memulai dan memelihara denganpersonel yang berkualifikasi dapat menyebabkan kematianatau cedera serius.

Tegangan TinggiKonverter frekuensi tersambung ke tegangan hantaranlistrik yang berbahaya. Perhatian secara khusus harusdilakukan guna melindungi dari kejutan. Hanya denganpersonal yang telah mendapatkan pelatihan denganperalatan elektronik dapat melakukan instalasi, memulai,atau menjaga peralatan ini.

PERINGATANSTART YANG TIDAK DISENGAJA!Pada saat konverter frekuensi tersambung ke hantaranlistrik AC, motor dapat memulai kapan saja. Konverterfrekuensi, motor dan peralatan apa saja yang dijalankanharus diperiksa kesiapan pengoperasiannya. Tidakmengikuti prosedur kesiapan pengoperasional pada saatkonverter frekuensi tersambung ke sumber listrik AC dapatmenyebabkan kematian, cedera serius, kerusakanperalatan, atau properti.

Pengaktifan Tiba-tibaPada saat konverter frekuensi tersambung ke hantaranlistrik AC, motor dapat dimulai dengan saklar eksternal,perintah bus serial, sinyal reference input, atau kondisimasalah yang telah selesai. Gunakan perhatian yang sesuaiuntuk mencegah pengaktifan tiba-tiba.

PERINGATANPEMBERHENTIAN WAKTU!Konverter frekuensi berisi kapasitor hub-DC yang dapattetap dibebankan bahkan ketika converter frekuensi tidakbertenaga. Untuk menghindari bahaya listrik, lepaskanlistrik AC, setiap jenis motor magnet permanen, danpasokan daya hub DC jauh, termasuk backup baterai, UPSdan koneksi hub DC ke konverter frekuensi lain. Tunggukapasitor untuk sepenuhnya sebelum melakukan layananatau perbaikan. Jumlah waktu tunggu yang tercantumdalam tabel Waktu Discharge. Tidak menunggu waktu yangditentukan setelah daya dilepas sebelum melakukanlayanan atau perbaikan pada unit, dapat mengakibatkankematian atau cedera yang serius.

Tegangan[V]

Waktu tunggu minimum (Menit)

4 7 15

200-240 1,1-3,7 kW 5.5-45 kW

380-480 1,1-7,5 kW 11-90 kW

525-600 1,1-7,5 kW 11-90 kW

525-690 1,1-7,5 kW 11-90 kW

Tegangan tinggi masih aktif sekalipun lampu indikatorperingatan LED tidak aktif.

Pemberhentian Waktu

SimbolSimbol berikut digunakan di dalam manual ini.

PERINGATANMenunjukkan potensial situasi berbahaya, apabila tidakdihindari, dapat menyebabkan kematian atau cedera yangserius.

KEWASPADAANMenujukkan potensial situasi berbahaya apabila tidakdihindari, dapat menyebakan cedera ringan dan sedang.Hal ini juga dapat digunakan untuk memberikan sinyalterhadap pelatihan yang tidak aman.

KEWASPADAANMenujukkan situasi yang dapat menyebabkan kejadianpada peralatan atau hanya-kerusakan-properti.

CATATAN!Menunjukkan informasi penting yang seharusnyadiperhatikan untuk menghindari kesalahan atau mengope-rasikan peralatan yang kurang dari kinerja optimal.

Pengesahan

CATATAN!Pembatasan beban pada frekuensi output(karena regulasi kontrol ekspor):Dari versi perangkat lunak 3.92 frekuensi output darikonverter frekuensi ini dibatasi ke 590 Hz.

Keselamatan VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss

Page 4: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Keselamatan VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss

Page 5: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Daftar Isi

1 Pendahuluan 4

1.1 Tujuan Manual 6

1.2 Sumber Tambahan 6

1.3 Gambaran Produk 6

1.4 Fungsi Kontroler Konverter Frekuensi Internal 6

1.5 Ukuran Bingkai dan Pengukuran Daya 7

2 Instalasi 8

2.1 Daftar Pemeriksaan Bagian Instalasi 8

2.2 Konverter Frekuensi dan Daftar Pemeriksaan Sebelum instalasi Motor 8

2.3 Instalasi Mekanis 8

2.3.1 Pendinginan 8

2.3.2 Pengangkat 9

2.3.3 Pemasangan 9

2.3.4 Torsi Pengetatan 9

2.4 Instalasi Listrik 10

2.4.1 Permintaan 12

2.4.2 Persyaratan Pembumian (Arde) 12

2.4.2.1 Arus Kebocoran (>3.5 mA) 13

2.4.2.2 Kabel Pelindung Penggunaan Arde 13

2.4.3 Hubungan Motor 13

2.4.3.1 Sambungan Motor untuk A2 dan A3 15

2.4.3.2 Sambungan Motor untuk A4/A5 15

2.4.3.3 Sambungan Motor untuk B1 dan B2 16

2.4.3.4 Hubungan Motor untuk C1 dan C2 16

2.4.4 Sambungan Hantaran listrik AC 16

2.4.5 Wiring Kontrol 17

2.4.5.1 Akses 17

2.4.5.2 Jenis Terminal Kontrol 17

2.4.5.3 Wiring untuk Kontrol Terminal 18

2.4.5.4 Gunakan Kabel Kontrol Layar 19

2.4.5.5 Fungsi Terminal Kontrol 20

2.4.5.6 Terminal Jumper 12 dan 27 20

2.4.5.7 Saklar terminal 53 dan 54 20

2.4.6 Komunikasi Serial 20

2.5 Hentian Aman 21

2.5.1 Terminal 37 Fungsi Stop Aman 22

2.5.2 Uji Komisi Stop Aman 24

3 Permulaan dan Pengujian Fungisonal 26

Daftar Isi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 1

Page 6: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

3.1 Sebelum mulai 26

3.1.1 Pemeriksaan Keselamatan 26

3.2 Tetapkan Daya 28

3.3 Program Operasional Dasar 28

3.4 Pengaturan Motor Asinkron 29

3.5 Pengaturan Motor Lanjutan 29

3.6 Penyesuaian Motor Otomatis 30

3.7 Periksa Rotasi Motor 31

3.8 Pengujian Kontrol-lokal 31

3.9 Permulaan Sistem 32

3.10 Desis Akustik atau Getaran 32

4 Penghubung pengguna 33

4.1 Panel Kontrol Lokal (LCP) 33

4.1.1 Susunan LCP 33

4.1.2 Pengaturan Angka tampilan LCP 34

4.1.3 Tampilan Tombol Menu 34

4.1.4 Tombol Navigasi 35

4.1.5 Tombol operasi 35

4.2 Cadangan dan Menyalin Pengaturan Parameter 35

4.2.1 Upload Data ke LCP 36

4.2.2 Download Data dari LCP 36

4.3 Mengembalikan Pengaturan Standar 36

4.3.1 Inisialisasi Yang Disarankan 36

4.3.2 Inisialisasi Manual 36

5 Tentang Program Konverter Frekuensi 37

5.1 Pendahuluan 37

5.2 Contoh Program 37

5.3 Contoh Program Terminal Kontrol 39

5.4 Pengaturan Parameter Standar Internasional/Amerika Utara 39

5.5 Struktur Menu Parameter 40

5.5.1 Struktur Menu Cepat 41

5.5.2 Struktur Menu Utama 43

5.6 Program jauh dengan MCT 10 Set-up Perangkat Lunak 47

6 Contoh Pengaturan Aplikasi 48

6.1 Pendahuluan 48

6.2 Contoh Aplikasi 48

7 Status Pesan 52

7.1 Status Layar 52

Daftar Isi VLT® Petunjuk Operasional Drive HVAC

2 MG11AI9B - VLT® merek dagang terdaftar Danfoss

Page 7: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

7.2 Definisi Pesan Status 52

8 Peringatan dan Alarm 55

8.1 Sistem Monitoring 55

8.2 Jenis Peringatan dan Alarm 55

8.3 Tampilan Peringatan dan Alarm 55

8.4 Definisi Peringatan dan Alarm 56

9 Dasar Pemecahan masalah 65

9.1 Memulai dan Operasi 65

10 Spesifikasi 68

10.1 Bergantung-daya Spesifikasi 68

10.1.1 Pasokan/masukan Hantaran listrik 3 x 525-690 V AC 76

10.2 Data Teknis Umum 79

10.3 Tabel sekering 84

10.3.1 Sekering Proteksi Sirkuit Bercabang 84

10.3.2 UL dan Proteksi Sirkuit Bercabang Sekering 86

10.3.3 Sekering Pengganti untuk 240 V 88

10.4 Sambungan Torsi Pengencangan 88

Indeks 89

Daftar Isi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 3

Page 8: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

1 Pendahuluan

1

23

4

5

6

7

8

9

10

11

1213

14

8

15

16

17

18

130B

B492

.10

Ilustrasi 1.1 Dikeluarkan Tampilan Ukuran A

1 LCP 10 Terminal output motor 96 (U), 97 (V), 98 (W)

2 Konektor bus serial RS-485 (+68), -69) 11 Relai 2 (01, 02, 03)

3 Konektor I/O analog 12 Relai 1 (04, 05, 06)

4 Plug input LCP 13 Rem (-81, +82) dan terminal (-88, +89) pemakaian bersama

5 Switch analog (A53), (A54) 14 Terminal input sumber listrik 91 (L1), 92 (L2), 93 (L3)

6 Pelepasan kabel renggang/arde PE 15 Konektor USB

7 Pelat pelepasan gandengan 16 Saklar terminal bus serial

8 Penjepit arde (PE) 17 Pasokan daya digital I/O dan 24 V

9 Penjepit arde kabel pelindung dan pelepasan renggang 18 Kontrol pelat penutup kabel

Tabel 1.1 Legenda ke Ilustrasi 1.1

Pendahuluan VLT® Petunjuk Operasional Drive HVAC

4 MG11AI9B - VLT® merek dagang terdaftar Danfoss

11

Page 9: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

1

2

3

4

5

6

7

8

9

10

11

12 13

1617

1819

1415

FAN MOUNTING

QDF-30

DC- DC+

Remove jumper to activate Safe StopMax. 24 Volt !

12 13 18 19 27 29 32 33 20

61 6839 42 50 53 54

0605

0403

0201

130B

B493

.10

Ilustrasi 1.2 Dikeluarkan Tampilan Ukuran B dan C

1 LCP 11 Relai 2 (04, 05, 06)

2 Penutup 12 Ring pengangkat

3 Konektor bus serial RS-485 13 Pemasangan slot

4 Pasokan daya digital I/O dan 24 V 14 Penjepit arde (PE)

5 Konektor I/O analog 15 Pelepasan kabel renggang / arde PE

6 Pelepasan kabel renggang/arde PE 16 Terminal rem (-81, +82)

7 Konektor USB 17 Terminal bersama beban (Bus DC) (-88, +89)

8 Saklar terminal bus serial 18 Terminal output motor 96 (U), 97 (V), 98 (W)

9 Switch analog (A53), (A54) 19 Terminal input sumber listrik 91 (L1), 92 (L2), 93 (L3)

10 Relai 1 (01, 02, 03)

Tabel 1.2 Legenda ke Ilustrasi 1.2

Pendahuluan VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 5

1 1

Page 10: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

1.1 Tujuan Manual

Manual ini bertujuan untuk menyediakan informasi detaiuntuk intalasi dan permulaan konverter frekuensi. 2 Instalasi menyediakan persyaratan untuk mekanik daninstalasi elektrik termasuk input, motor, kontrol dan kabelkomunikasi serial dan fungsi terminal kontrol. 3 Permulaandan Pengujian Fungisonal menyediakan prosedur detailuntuk permulaan, program operasional dasar, danpengujian fungsional. Chapter lainnya menyediakantambahan informasi selengkapnya. Detail ini meliputipenghubung pengguna, detail program, contoh apliasi,memulai pemecahan masalah, dan spesifikasi.

1.2 Sumber Tambahan

Sumber lain tersedia untuk mengerti fungsi konverterfrekuensi lanjutan dan program.

• Panduan Pemrograman VLT®, menyediakaninformasi lengkap untuk bekerja denganparameter dan banyak contoh aplikasi.

• Panduan Rancangan VLT® bermaksud untukmenyediakan kemampuan dan fungsional untukmerancang sistem kontrol motor

• Penambahan publikasi dan manual tersedia dariDanfoss.Lihat www.danfoss.com/BusinessAreas/DrivesSo-lutions/Documentations/VLT+Technical+Documentation.htm untuk listing.

• Peralatan opsional tersedia dapat mengubahbeberapa prosedur yang telah dijelaskan.Referensi petunjuk yang telah diberikan denganbeberapa pilihan untuk permintaan khusus.Hubungi lokal Danfoss pemasok atau kunjungisitus Danfoss: www.danfoss.com/BusinessAreas/DrivesSolutions/Documentations/VLT+Technical+Documentation.htm, untuk download atauinformasi tambahan.

1.3 Gambaran Produk

Konverter frekuensi merupakan pengontrol motorelektronik yang mengubah masukan hantaran listrik AC keoutput bentuk gelombang AC variabel. Frekuensi danoutput tegangan diatur untuk mengontrol kecepatanmotor atau torsi. Konverter frekuensi dapat mengubahkecepatan motor terhadap sistem umpan balik, sepertiperubahan suhu atau tekanan yang bertujuan untukmengontrol kipas, motor kompresor, atau pompa.Konverter frekuensi juga dapat mengatur motor denganmerespond perintah jauh dari pengontrol eksternal.

Dan, konverter frekuensi dapat memonitor sistem danstatus motor, menunjukkan peringatan atau alarm untuk

kondisi yang salah, memulai dan memberhentikan motor,mengoptimalkan efisiensi energi, menyediakan perlin-dungan harmonis barisan, dan menawarkan beberapakontrol, memonitor dan fungsi yang efisiensi. Fungsioperasi dan monitor tersedia sebagai status indikasi untuksistem kontrol di luar atau jaringan komunikasi serial.

1.4 Fungsi Kontroler Konverter FrekuensiInternal

Ilustrasi 1.3 menunjukkan diagram blok dari komponeninternal konverter frekuensi. Lihat Tabel 1.3 untukfungsinya.

Ilustrasi 1.3 Konverter Frekuensi Diagram Blok

Luas Judul Fungsi1 Input sumber listrik • Tiga-fasa hantaran listrik AC

pasokan daya ke konverterfrekuensi

2 Penyearah • Jembatan penyearahmengubah input AC ke arusDC untuk memasok dayainverter

3 Bus DC • Sirkuit DC-bus lanjutankonverter frekuensimenangani arus DC

4 Reaktor DC • Menyaring tegangan sirkuitDC lanjutan

• Jaminan proteksi salurantransien

• Pengurangan arus RMS

• Peningkatan faktor daya yangmemantulkan kembali kesaluran

• Pengurangan harmoni padainput AC

5 Bank kapasitor • Menyimpan daya DC

• Menyediakan pengendaramelalui perlindungan untukkehilangan daya pendek

Pendahuluan VLT® Petunjuk Operasional Drive HVAC

6 MG11AI9B - VLT® merek dagang terdaftar Danfoss

11

Page 11: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Luas Judul Fungsi6 Inverter • Mengubah DC ke PWM yang

dikontrol bentuk gelombangAC untuk output variabelyang kontrol ke motor

7 Output ke motor • Pengaturan daya output tigafasa ke motor

Luas Judul Fungsi8 Sirkuit kontrol • Daya input, proses internal,

output, dan arus motordimonitor untuk menyediakanoperasi dan kontrol yangefisien

• Penghubung pengguna danperintah eksternal dimonitordan dilakukan

• Keluaran status dan kontroldapat disediakan

Tabel 1.3 Tulisan ke Ilustrasi 1.3

1.5 Ukuran Bingkai dan Pengukuran Daya

Referensi ke ukuran bingkai digunakan di manual ini ditentukan di Tabel 1.4.

Ukuran Bingkai [kW]

[V] A2 A3 A4 A5 B1 B2 B3 B4 C1 C2 C3 C4

200-240 1.1-2.2 3.0-3.7 1.1-2.2 1.1-3.7 5.5-11 15 5.5-11 15-18.5 18.5-30 37-45 22-30 37-45

380-480 1.1-4.0 5.5-7.5 1.1-4.0 1.1-7.5 11-18.5 22-30 11-18.5 22-37 37-55 75-90 45-55 75-90

525-600 n/a 1.1-7.5 n/a 1.1-7.5 11-18.5 22-30 11-18.5 22-37 37-55 75-90 45-55 75-90

525-690 n/a 1.1-7.5 n/a n/a n/a 11-30 n/a 11-37 n/a 37-90 45-55 n/a

Tabel 1.4 Ukuran Bingkai dan Pengukuran Daya

Pendahuluan VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 7

1 1

Page 12: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2 Instalasi

2.1 Daftar Pemeriksaan Bagian Instalasi

• Konverter frekuensi tergantung pada udarasekitar untuk pendinginan. Pengamatan bataspada suhu udara sekitarnya untuk pendinginanoperasi

• Pastikan lokasi instalasi mempunyai dukungankekuatan yang cukup untuk memasang konverterfrekuensi

• Manual, gambar, dan diagram tetap dapat diaksesuntuk instalasi detail dan instruksi operasi.Sangatlah penting bahwa manual tersedia untukperalatan operator.

• Menempatkan peralatan sedekat mungkindengan motor. Tetap menempatkan kabel motorsedekat mungkin. Periksa karakteristik motoruntuk toleransi yang aktual. Tidak boleh melebihi

• 300m (1000 ft) kaki tanpa penutupmotor pelindung

• 150 m (500 kaki) untuk kabel pelindung.

• Pastikan bahwa ingress perlindungan ratinguntuk konverter frekuensi sesuai untuk instalasilingkungan. IP55 (NEMA 12) atau IP66 (NEMA 4)mungkin diperlukan.

KEWASPADAANPerlindungan IngressIP54, IP55 dan IP66 pengukuran hanya dapat guaranteedapabila unit dengan benar tertutup.

• Pastikan bahwa semua kabel glands dan lubangyang tidak digunakan untuk glands secara benardisegel.

• Pastikan unit secara benar tertutup penutup

KEWASPADAANPerangkat kerusakan melalui kontaminasiJangan tinggalkan konverter frekuensi terbuka.

2.2 Konverter Frekuensi dan DaftarPemeriksaan Sebelum instalasi Motor

• Perbandingan jumlah unit model pada pelatnamadengan unit yang telah dipesan bertujuan untukmemastikan peralatan yang sesuai

• Pastikan bahwa masing-masing berikut ini telahdiukur untuk tegangan yang sama:

Hantaran listrik (daya)

Konverter frekuensi

Motor

• Pastikan bahwa output konverter frekuensipengukuran arus sama atau lebih besar dari arusbeban penuh motor untuk perfoma puncakmotor

Ukuran Motor dan daya konverterfrekuensi harus sesuai untuk kelebihanbeban yang sesuai.

Apabila pengukuran konverter frekuensikurang dari motor, output motor penuhtidak dapat tercapai

2.3 Instalasi Mekanis

2.3.1 Pendinginan

• Pemasangan unit ke permukaan datar solid ataupelat belakang optional (lihat 2.3.3 Pemasangan)

• Pembersih udara bagian atas dan bawah untukpendingin udara harus disediakan. Secara umum,100-225mm (4-10in) diperlukan. Lihat Ilustrasi 2.1untuk persyaratan jarak ruang

• Pemasangan yang tidak sesuai dapatmenyebabkan pemanasan dan penurunan kinerja

• Penurunan untuk suhu dimulai antara 40 °C (104°F) dan 50 °C (122 °F) dan elevasi 1000 m (3300kaki) diatas permukaan laut harus dipertim-bangkan. Lihat Panduan Rancangan peralatanuntuk informasi selengkapnya.

Instalasi VLT® Petunjuk Operasional Drive HVAC

8 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 13: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

a

b

130B

A41

9.10

Ilustrasi 2.1 Jarak ruang Pendingin Atas dan Bawah

Penutup A2-A5 B1-B4 C1, C3 C2, C4

a/b [mm] 100 200 200 225

Tabel 2.1 Persyaratan Jarak Ruang Minimum Aliran Udara

2.3.2 Pengangkat

• Periksa berat unit untuk menentukan metodepengangkat

• Pastikan perangkat pengangkat sesuai untuktugas tersebut

• Apabila diperlukan, rencana untuk pengungkit,crane, atau forklift dengan pengukuran yangsesuai untuk memindahkan unit tersebut

• Untuk pengangkat, gunakan ring pengungkitpada unit, apabila disediakan

2.3.3 Pemasangan

• Pasang unit secara vertikal

• Konverter frekuensi memungkinkan instalasi

• Pastikan bahwa kekuatan dari lokasi pemasanganakan mendukung pemasangan berat

• Pemasangan unit ke permukaan datar solid ataupilihan pelat belakang untuk memberikan aliranudara pendingin (lihat Ilustrasi 2.2 danIlustrasi 2.3)

• Pemasangan yang tidak sesuai dapatmenyebabkan pemanasan dan penurunan kinerja

• Gunakan lubang pemasang slot pada unit untukpemasangan dinding, pada saat disediakan

130B

A21

9.10

A

Ilustrasi 2.2 Pasang yang Sesuai dengan Pelat belakang

Item A adalah Pelat belakang diinstal secara benar untukudara masuk yang bertujuan untuk melakukanpendinginan unit.

130B

A22

8.10

A

Ilustrasi 2.3 Pemasangan unit yang Sesuai dengan memberikanPembatas

CATATAN!Pelat belakang diperlukan pada saat memasang dipembatas.

2.3.4 Torsi Pengetatan

Lihat 10.4 Sambungan Torsi Pengencangan untuk spesifikasipengencangan yang sesuai.

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 9

2 2

Page 14: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2.4 Instalasi Listrik

Bagian ini berisi instruksi detail untuk konverter frekuensiwiring. Tugas berikut dideskripsikan.

• Sambung motor ke terminal output konverterfrekuensi.

• Sambung kabel sumber listrik AC ke terminalinput konverter frekuensi .

• Sambung kabel kontrol dan komunikasi serial

• Setelah daya ditetapkan, periksa input dan dayamotor; terminal kontrol program untuk fungsiyang dimaksud

Ilustrasi 2.4 memperlihatkan sambungan elektrik dasar.

Ilustrasi 2.4 Gambar Skematis Kabel Dasar.

* Terminal 37 merupakan pilihan

Instalasi VLT® Petunjuk Operasional Drive HVAC

10 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 15: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

1

2

3

4

5

6

7

8

PE

UVW

9

L1L2L3PE

130B

B607

.10

10

Ilustrasi 2.5 Sambungan Elektrikal Tipikal

1 PLC 6 Min. 200mm (7.9 in) antara kabel kontrol, motor dan hantaranlistrik

2 Konverter frekuensi 7 Motor, 3 fasa dan PE

3 Kontaktor output (Secara umum tidak disarankan) 8 Hantaran listrik, 3 fasa dan penguatan PE

4 Tanah (pembumian) batas (PE) 9 Wiring kontrol

5 Insulasi kabel (strip) 10 Equalising min. 16 mm2 (0.025 in)

Tabel 2.2 Legenda ke Ilustrasi 2.5

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 11

2 2

Page 16: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2.4.1 Permintaan

PERINGATANPERALATAN BAHAYA!Perputaran poros dan perlengkapan elektrik dapatberbahaya. Semua pekerjaan elektrik harus dikonfirmasi kekode nasional dan lokal elektrikal. Sangat direkomen-dasikan bahwa instalasi, permulaan, dan perawatan hanyadapat dilakukan oleh pekerja yang telah dilatih danberkualifikasi. Gagal mengikuti petunjuk ini dapatmenyebabkan kematian atau kecelakaan yang serius.

KEWASPADAANISOLASI KABEL!Menjalankan daya input, wiring motor dan wiring kontroldi tiga saluran metalik yang terpisah atau menggunakankabel pelindung yang terpisah untuk isolasi kebisinganfrekuensi tinggi. Gagal untuk mengisolasi daya, motor dankabel kontrol dapat menyebabkan konverter frekuensi dankinerja peralatan yang berhubungan tidak optimum.

Untuk keselamatan Anda, patuhi semua persyaratanberikut.

• Peralatan kontrol elektronik tersambung ketegangan sumber listrik yang berbahaya.Perhatian khusus harus dilakukan gunamelindungi dari kejutan elektrik apabilamelakukan daya ke unit.

• Jalankan kabel motor dari konverter frekuensimultipel secara terpisah. Penambahan tegangandari kabel motor output berjalan bersamaandapat mengisi peralatan kapasitor meskipunperalatan telah dinonaktifkan dan keluar.

Kelebihan beban dan Perlindungan Peralatan

• Fungsi yang diaktifkan secara elektrik di antarakonverter frekuensi menyediakan perlindungankelebihan beban untuk motor. Kelebihan bebanmenghitung ke tingkat penambahan waktu aktifuntuk fungsi (stop output kontroler) trip. Semakinbesar tingkat arus yang dihasilkan, semakin cepattanggapan dari trip tersebut. Kelebihan bebanmenyediakan perlindungan Kelas 20 perlindunganmotor. Lihat 8 Peringatan dan Alarm untuk detaildi fungsi trip.

• Semua konverter frekuensi harus disediakandengan sirkuit pendek dan perlindungan arusyang berlebih. Sekering input diperlukan untukmenyediakan proteksi ini, lihat Ilustrasi 2.6.Apabila pabrik tidak dapat mendukungprosesnya, sekering harus dapat disediakan olehpenginstal sebagai bagian dari instalasiinstalasi..Lihat pengukuran sekering maksimum di10.3 Tabel sekering.

L1

L1

L2

L2

L3

L3

GND

91 92 93Fuses

130B

B460

.10

Ilustrasi 2.6 Sekering konverter frekuensi

Jenis kabel dan Pengukuran

• Semua kabel harus mematuhi peraturan lokal dannasional berkenaan dengan persyaratanpenampang dan suhu sekitarnya.

• Danfoss menyarankan sambungan daya dibuatdengan minimum 75° C kabel tembaga terukur.

• Lihat 10.1 Bergantung-daya Spesifikasi untukukuran kabel yang disarankan.

2.4.2 Persyaratan Pembumian (Arde)

PERINGATANBAHAYA ARDE!Untuk keselamatan operator, sangatlah penting untukmenempatkan konverter frekuensi arde secara benarmenurut kode elektrik nasional dan lokal serta instruksiyang berisi dokumen ini. Arus arde lebih tinggi dari 3.5mA. Tidak mengikuti konverter frekuensi arde dapatmenyebabkan kematian atau cedera yang serius.

CATATAN!Tanggung jawab pengguna atau penginstal elektrik yangdisertifikasi untuk memastikan peralatan arde (pembumian)yang benar menurut kode elektrik nasional, lokal danstandar yang berlaku.

• Mengikuti semua kode elektrik lokal dan nasionaluntuk menempatkan peralatan elektrik ardesecara benar

• Perlindungan arde secara benar untuk peralatandengan arus arde lebih tinggi dari 3.5 mA harusdilakukan, lihat 2.4.2.1 Arus Kebocoran (>3.5 mA)

• Kabel arde diperlukan untuk daya input, dayamotor dan kabel kontrol.

• Gunakan penjepit yang disediakan denganperalatan untuk hubungan arde

Instalasi VLT® Petunjuk Operasional Drive HVAC

12 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 17: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

• Tidak menempatkan arde pada satu konverterfrekuensi dengan lainnya pada cara "rantai daisy"

• Tetap menempatkan sambungan kabel ardesedekat mungkin

• Penggunaan kabel high-strand untuk mengurangikebisingan elektrik disarankan

• Ikuti persyaratan wiring pabrik motor

2.4.2.1 Arus Kebocoran (>3.5 mA)

Kode lokal dan nasional berikut mengenai proteksiperalatan pembumian dengan arus kebocoran > 3.5 mA.Teknologi konverter frekuensi menyatakan saklar frekuensitinggi pada daya tinggi. Hal ini akan menghasilkan arusbocor di sambungan pembumian. Arus yang bermasalah dikonverter frekuensi pada terminal daya output berisikomponen DC di mana dapat mengenai kapasitor filterdan menyebabkan arus bumi transien. Arus bocorpembumian tergantung pada konfigurasi sistem yangberbeda termasuk filter RFI, kabel motor yang di screen,dan daya konverter frekuensi.

EN/IEC61800-5-1 (Standar Produk Sistem Drive Daya)memerlukan penanganan khusus apabila arus bocormelebihi 3.5mA. Arde pembumian harus diperkuat di salahsatu berikut:

• Kabel arde pembumian minimal 10 mm2

• Kedua kabel arde pembumian menyetujuiperaturan dimensi

Lihat EN 60364-5-54 § 543.7 untuk informasi lebih lanjut.

Menggunakan RCDPerangkat arus residual (RCD), dikenal sebagai rem sirkuitbocor pembumian(ELCB) yang digunakan, memenuhisebagai berikut:

Gunakan RCD hanya dari jenis B yang mampumendeteksi arus AC dan DC

Gunakan RCD dengan penundaan inrush untukmencegah masalah karena arus pembumiantransien

RCD dimensi menurut konfigurasi sistem danpertimbangan lingkungan

2.4.2.2 Kabel Pelindung Penggunaan Arde

Penjepit pembumian (arde) disediakan untuk kabel motor(lihat Ilustrasi 2.7).

130B

A26

6.10

+DC BR- B

MA

IN

S

L1 L2 L391 92 93

REL

AY

1

REL

AY

2

99

- LC -

U V W

MOTOR

Ilustrasi 2.7 Arde dengan Kabel Pelindung

2.4.3 Hubungan Motor

PERINGATANTEGANGAN BERTAMBAH!Jalankan kabelmotor output dari konverter frekuensimultipel secara terpisah. Penambahan tegangan dari kabelmotor output berjalan bersamaan dapat mengisi peralatankapasitor meskipun peralatan telah dinonaktifkan dankeluar. Gagal menjalankan kabel output dapatmenyebabkan kematian atau cedera yang serius.

• Untuk ukuran kabel maksimum, lihat10.1 Bergantung-daya Spesifikasi

• Mematuhi kode elektrik lokal dan nasional untukukuran kabel

• Pemutusan kabel motor atau akses paneldisediakan pada IP21 dan lebih tinggi (NEMA1/12)unit

• Tidak instal kapasitor koreksi faktor daya antarakonverter frekuensi dan motor

• Tidak melakukan sambungan perangkat atauperubahan-pole antara konverter frekuensi danmotor

• Sambung kabel motor 3 fasa ke terminal 96 (U),97 (V), dan 98 (W)

• Menempatkan kabel menurut instruksi arde yangdisediakan

• Terminal torsi menurut informasi yang disediakandi 10.4 Sambungan Torsi Pengencangan

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 13

2 2

Page 18: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

• Ikuti persyaratan wiring pabrik motor

Ilustrasi 2.8, Ilustrasi 2.9 dan Ilustrasi 2.10 mewakili inputsumber listrik, motor, dan penempatanarde untukkonverter frekuensi dasar. Konfigurasi aktual berubahdengan jenis unit dan peralatan optional.

130B

A26

6.10

+DC BR- B

MA

IN

S

L1 L2 L391 92 93

REL

AY

1

REL

AY

2

99

- LC -

U V W

MOTOR

Ilustrasi 2.8 Motor, Sumber Listrik dan Kabel Arde untuk UkuranBingkai A

91L1

92L2

93L3

96U

97V

98W

88DC-

89DC+

81R-

8R+

130B

A39

0.11

9995

Ilustrasi 2.9 Motor, Sumber Listrik dan Kabel Arde untukPenggunaan Kabel Pelindung Ukuran Bingkai B, C dan D

130B

B477

.10

91L1

92L2

93L3

96U

97V

99W

88DC+

89DC-

91R-

9R+

95 99

Ilustrasi 2.10 Motor, Sumber listrik dan Kabel Arde untuk UkuranBingkai B, C dan D

Instalasi VLT® Petunjuk Operasional Drive HVAC

14 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 19: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2.4.3.1 Sambungan Motor untuk A2 dan A3

Ikuti gambar ini selangkah-demi-selangkah untuk menghu-bungkan motor ke konverter frekuensi.

1. Pertama-tama, putus dahulu hubunganpembumian motor, kemudian pasang kabel U, V,dan W ke colokan dan kencangkan.

MA

IN

SL1 L2 L391 92 93

- LC

+

REL

AY

1

REL

AY

2

+DC BR- B+ D C B R - B R + U V W9 9

U V W

MOTOR

130B

A26

5.10

Ilustrasi 2.11 Sambungan Motor untuk A2 dan A3

2. Pasang penjepit kabel untuk membuatsambungan 360° antara sasis dan layar, dan ingatuntuk melepas insulasi luar dari kabel motor dibawah penjepit.

130B

A26

6.10

+DC BR- B

MA

IN

S

L1 L2 L391 92 93

REL

AY

1

REL

AY

2

99

- LC -

U V W

MOTOR

Ilustrasi 2.12 Pemasangan Penjepit Kabel

2.4.3.2 Sambungan Motor untuk A4/A5

Pertama-tama putus dahulu hubungan pembumian motor,kemudian pasang kabel U, V, dan W ke terminal dankencangkan. Pastikan bahwa isolasi luar kabel motor sudahdilepas dari penjepit EMC.

UV

W

9697

98

130B

T337

.10

Ilustrasi 2.13 Sambungan Motor untuk A4/A5

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 15

2 2

Page 20: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2.4.3.3 Sambungan Motor untuk B1 dan B2

Pertama-tama putus dahulu hubungan pembumian motor,kemudian pasang kabel U, V, dan W ke terminal dankencangkan. Pastikan bahwa isolasi luar kabel motor sudahdilepas dari penjepit EMC.

130B

T333

.10

Ilustrasi 2.14 Sambungan Motor untuk B1 dan B2

2.4.3.4 Hubungan Motor untuk C1 dan C2

91L1

92L2

93L3

96U

97V

98W

88DC-

89DC+

81R-

8R+

130B

A39

0.11

9995

Ilustrasi 2.15 Hubungan Motor untuk C1 dan C2

Pertama-tama putus dahulu hubungan pembumian motor,kemudian pasang kabel U, V, dan W pada terminal dan

kencangkan. Pastikan bahwa isolasi luar kabel motor sudahdilepas dari penjepit EMC.

2.4.4 Sambungan Hantaran listrik AC

• Ukuran kabel didasarkan arus input dari konverterfrekuensi Untuk ukuran kabel maksimum, lihat 10.1 Bergantung-daya Spesifikasi. .

• Selalu mematuhi kode lokal dan nasional elektrikuntuk ukuran kabel.

• Sambung 3-fasa kabel daya input ke terminal keterminal L1, L2 dan L3 (lihat Ilustrasi 2.16).

• Tergantung pada konfigurasi peralatan, dayainput akan tersambung ke sumber listrik terminalinput atau input terputus.

L 1 L 2 L 3

91 92 93

130B

T336

.10

Ilustrasi 2.16 Menyambung ke Sumber listrik AC

• Menempatkan kabel menurut instruksi arde yangdisediakan 2.4.2 Persyaratan Pembumian (Arde)

• Semua konverter frekuensi dapat digunakandengan sumber input yang terpisah dan salurandaya referensi arde. Pada saat dipasok darisumber listrik terpisah (sumber listrik IT atau deltamengambang) atau sumber listrik TT/TN-Sdengan kaki arde (delta arde), atur 14-50 Filter RFIke TIDAK AKTIF. Pada saat tidak aktif, kapasitorfilter RFI antara sasis dan sirkuit lanjutandipisahkan untuk mencegah kerusakan padasirkuit lanjutan dan mengurangi arus kapasitasarde menurut IEC 61800-3.

Instalasi VLT® Petunjuk Operasional Drive HVAC

16 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 21: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2.4.5 Wiring Kontrol

• Pisahkan wiring kontrol dari komponen dayatinggi di konverter frekuensi.

• Apabila konverter frekuensi tersambung ketermistor, untuk isolasi PELV, wiring kontroltermistor optional harus diperkuat/dilipat-gandakan perlindungannya. Tegangan pasokan24 V DC disarankan.

2.4.5.1 Akses

• Lepaskan akses pelat penutup dengan obeng.Lihat Ilustrasi 2.17.

• Atau lepaskan penutup depan dengan mengen-durkan skrup. Lihat Ilustrasi 2.18.

130B

T248

.10

Ilustrasi 2.17 Jalan Kabel Kontrol untuk Penutup A2, A3, B3, B4,C3 dan C4

130B

T334

.10

Ilustrasi 2.18 Jalan Kabel Kontrol untuk Penutup A4, A5, B1, B2,C1 dan C2

Lihat Tabel 2.3 sebelum mengetatkan penutup.

Bingkai IP20 IP21 IP55 IP66

A3/A4/A5 - - 2 2

B1/B2 - * 2.2 2.2

C1/C2/C3/C4 - * 2.2 2.2

* Tidak ada skrup untuk mengencangkan- Tidak ada

Tabel 2.3 Pengetatan Torsi untuk Penutup (Nm)

2.4.5.2 Jenis Terminal Kontrol

Ilustrasi 2.19 memperlihatkan konektor konverter frekuensiyang dapat dilepas. Fungsi terminal dan pengaturanstandar diringkas di Tabel 2.4.

1

4

2

3

130B

A01

2.12

6168

69

3942

5053

5455

1213

1819

2729

3233

2037

Ilustrasi 2.19 Lokasi Terminal Kontrol

• Konektor 1 menyediakan 4 terminal input digitalyang dapat diprogram, dua tambahan terminaldigital yang dapat diprogram sebagai input atauoutput, pasokan tegangan terminal 24V DC, dansecara umum untuk optional pelanggan dipasokdengan tegangan 24V DC

• Konektor 2 terminal (+) 68 dan (-)69 untuksambungan komunikasi serial RS-485

• Konektor 3 menyediakan dua input analog, satuoutput analog, tegangan pasokan 10VDC, dansecara umum untuk input dan output .

• Konektor 4 merupakan port USB yang tersediauntuk penggunaan dengan konverter frekuensi.

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 17

2 2

Page 22: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

• Persediaan juga meliputi dua output relai BentukC yang merupakan tempat lokasi dan tergantungpada konfigurasi konverter frekuensi dan ukuran

• Beberapa opsi tersedia untuk pemesanan denganunit yang dapat menyediakan terminal tambahan.Lihat manual yang disediakan dengan opsiperalatan.

Lihat 10.2 Data Teknis Umum untuk rincian selengkapnya.

Keterangan TerminalInput/Output Digital

Terminal ParameterDefaultP'aturan Keterangan

12, 13 - +24 V DC Tegangan pasokan 24V DC. Arus outputmaksimum adalah 200mA taotal untuksemua beban 24 V.Penggunaan untukinput digital dantransduser eksternal.

18 5-10 [8] Start

Input Digital.

19 5-11 [0] Tidak adaoperasi

32 5-14 [0] Tidak adaoperasi

33 5-15 [0] Tidak adaoperasi

27 5-12 [2] Coastterbalik

Dapat dipilih untukinput dan outputdigital. Pengaturanstandar adalah input.

29 5-13 [14] JOG

20 - Umum untuk inputdigital dan 0 Vpotensial untukpasokan 24 V.

37 - Torsi AmanTidak Aktif(STO)

(opsional) Input aman.Digunakan untuk STO

Input/Output Analog

39 -

Bersama untuk outputanalog

42 6-50 Kecepatan 0 -Batas Tinggi

Dapat diprogramoutput analog. Sinyalanalog adalah 0-20mAatau 4-20mA pada

maksimum 500Ω Ω.

50 - +10 V DC Tegangan pasokananalog 10 V DC. 15mA maksimum secaraumum digunakanuntuk potensiometeratau termistor.

Keterangan TerminalInput/Output Digital

Terminal ParameterDefaultP'aturan Keterangan

53 6-1 Referensi Input analog. Dapatdipilih untuktegangan atau arus.Saklar A53 dan A54pilih mA atau V.

54 6-2 Umpan Balik

55 -

Bersama untuk inputanalog

Komunikasi Serial

61 -

RC-Filter yangterintegrasi untuklayar kabel. HANYAuntuk menyambunglayar pada saat terjadimasalah EMC.

68 (+) 8-3 Interface RS-485.Saklar kartu kontroldisediakan untukresistensi pemutusan.

69 (-) 8-3

Relai

01, 02, 03 5-40 [0] [0] Alarm Output relai Bentuk C.Dapat digunakanuntuk tegangan ACatau DC dan bebanhambatan atauinduktif.

04, 05, 06 5-40 [1] [0] Berjalan

Tabel 2.4 Keterangan Terminal

2.4.5.3 Wiring untuk Kontrol Terminal

Konektor terminal kontrol tidak dapat dimasukkan darikonverter frekuensi untuk kemudahan instalasi, sepertiyang tertera di Ilustrasi 2.20.

130B

T306

.10

Ilustrasi 2.20 Tidak dimasukkan ke Terminal Kontrol

Instalasi VLT® Petunjuk Operasional Drive HVAC

18 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 23: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

1. Membuka kontak dengan memasukkan obengkecil ke slot di atas atau di bawah kontak sepertiyang terlihat di Ilustrasi 2.21.

2. Masukkan kabel kontrol yang diperlihatkan kekontak.

3. Lepaskan obeng untuk mengencangkan kabelkontrol ke kontak.

4. Pastikan kontak telah ada dan tidak hilang.Kendurkan kabel kontrol dapat menjadi sumbermasalah peralatan atau mengurangi ooperasiyang optimal.

Lihat 10.1 Bergantung-daya Spesifikasi untuk ukuran kabelterminal kontrol.

Lihat 6 Contoh Pengaturan Aplikasi untuk sambungan kabelkontrol tipikal.

2

1

10 m

m

130B

A31

0.10

12 13 18 19 27 29 32 33

Ilustrasi 2.21 Tersambung ke Kabel Kontrol

2.4.5.4 Gunakan Kabel Kontrol Layar

Screen yang benarPemilihan metode di beberapa masalah bertujuan untukmengontrol pengamanan dan kabel komunikasi serialdengan jepitan screen yang disediakan di kedua bagianakhir untuk memastikan kontak kabel frekuensi tinggi yangmemungkinkan.Apabila potensial arde antara konverter frekuensi dan PLCberbeda, kebisingan elektrik dapat terjadi di mana akanmengganggu sistem secara keseluruhan. Untuk menyele-saikan masalah ini dengan menyesuaikan kabel equalizingsetelah kabel kontrol. Bagian penampang kabel minimum:16 mm2.

12

PE

FC

PE

PLC

130B

B922

.12

PE PE<10 mm

Ilustrasi 2.22 Screen Yang Benar

1 Min. 16 mm2

2 Kabel Equalizing

Tabel 2.5 Legenda ke Ilustrasi 2.22

50/60 Hz putaran ardeDengan kabel kontrol yang sangat panjang, loop ardedapat terjadi. Untuk menghilangkan putaran arde,sambung ke layar bagian paling bawah ke arde dengankapasitor 100 nF (sedekat mungkin).

100nF

FC

PEPE

PLC

<10 mm 130B

B609

.12

Ilustrasi 2.23 50/60 Hz Putaran Arde

Menghindari kebisingan EMC pada komunikasi serialTerminal ini tersambung ke arde melalui hubungan RCinternal. Gunakan kabel pasangan-twisted untukmengurangi gangguan diantara konduktor. Metode yangdirekomendasikan berada pada Ilustrasi 2.24:

PE

FC

PE

FC

130B

B923

.12

PE PE

696861

696861

12

<10 mm

Ilustrasi 2.24 Kabel pasangan-Twisted

1 Min. 16 mm2

2 Kabel Equalizing

Tabel 2.6 Legenda ke Ilustrasi 2.24

Pilihannya, sambungan ke terminal 61 dapat dihilangkan:

PE

FC

PE

FC

130B

B924

.12

PE PE

69696868

12

<10 mm

Ilustrasi 2.25 Kabel pasangan-Twisted tanpa Terminal 61

1 Min. 16 mm2

2 Kabel Equalizing

Tabel 2.7 Legenda ke Ilustrasi 2.25

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 19

2 2

Page 24: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2.4.5.5 Fungsi Terminal Kontrol

Fungsi konverter frekuensi diperintah oleh penerimaansinyal input kontrol .

• Setiap terminal harus diprogram untuk fungsiyang akan mendukung parameter berhubungandengan terminal tersebut. Lihat Tabel 2.4 untukterminal dan parameter yang berhubungan.

• Sangatlah penting untuk mengkonfirmasi bahwaterminal kontrol diprogram untuk fungsi yangbenar. Lihat 4 Penghubung pengguna untuk detaildalam mengakses parameter dan 5 TentangProgram Konverter Frekuensi for details onprogram.

• Program terminal standar bermaksud untukmemulai fungsi konverter frekuensi di modusoperasional tipikal.

2.4.5.6 Terminal Jumper 12 dan 27

Kabel jumper diperlukan antara terminal 12 (atau13) danterminal 27 untuk konverter frekuensi untuk mengope-rasikan pada saat menggunakan angka program standarpabrik.

• Terminal input Digital 27 dirancang untukmenerima perintah interlock eksternal 24 V DC.Pada banyak aplikasi, pengguna menghubungkanperangkat interlock eksternal ke terminal 27

• Pada saat tidak ada perangkat interlockdigunakan, hubungkan jumper antara terminalkontrol 12 (disarankan) atau 13 ke terminal 27.Hal ini menyediakan di sinyal internal 24V padaterminal 27

• Ketidakadaan sinyal mencegah unit dari pengope-rasian

• Pada saat status line berada di bagian bawah LCPpembacaan PELUNCURAN JAUH TERBALIK atauInterlock Eksternal Alarm 60 ditampilkan, hal inimenunjukkan bahwa untuk telah siap untukberoperasi tetapi masih terjadi kekurangan padainput di terminal 27.

• Pada saat penginstalan peralatan opsional pabrikdisambung ke terminal 27, jangan lepaskan kabeltersebut.

2.4.5.7 Saklar terminal 53 dan 54

• Terminal input analog 53 dan 54 dapat memilihuntuk tegangan (0 sampai 10 V) atau sinyal inputarus (0/4-20 mA)

• Lepaskan daya ke konverter frekuensi sebelummengubah posisi saklar

• Atur saklar A53 dan A54 untuk pilih jenis sinyal. Umemilih tegangan, I memilih arus.

• Saklar dapat diakses pada saat LCP telah dilepas(lihat Ilustrasi 2.26). Catatan bahwa beberapakartu opsi tersedia untuk unit yang dapatmenutup saklar dan harus dilepas untukmengubah pengaturan saklar. Selalu lepaskandaya ke unit sebelum melepaskan kartu opsi.

• Standar terminal 53 adalah referensi kecepatanpada loop terbuka di 16-61 Terminal 53 Pegaturanswitch

• Standar terminal 54 merupakan sinyal umpan-balik pada loop tertutup 16-63 Terminal 54pengaturan switch

130B

T310

.10

12 N

O

VLT

BUS TER.OFF-ON

A53 A54U- I U- I

Ilustrasi 2.26 Lokasi dari Saklar Terminal 53 dan 54

2.4.6 Komunikasi Serial

RS-485 merupakan interface bus dua-kabel yang cocokdengan topologi jaringan multi-drop, misalnya node dapatdisambung sebagai bus, atau via kabel drop dari garistrunk umum. Jumlah 32 node dapat disambung ke satujaringan segmen.Pengulangan membagi jaringan segmen. Perhatikan bahwafungsi pengulangan sebagai node di dalam segmen telahdiinstal. Setiap node yang tersambung di jaringan yangtelah disediakan harus mempunyai alamat node yang unik,menyilang ke seluruh segmen.

Instalasi VLT® Petunjuk Operasional Drive HVAC

20 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 25: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Mengakhiri setiap segmen pada keduanya, menggunakanterminasi saklar (S801) konverter frekuensi atau jaringanresistor terminasi yang menyimpang. Selalu menggunakankabel screened twisted pair (STP) untuk kabel bus, danselalu mengikuti praktis instalasi yang umum.Sambungan layar pembumian (arde) impedansi-rendahpada setiap node sangatlah penting, termasuk frekuensitinggi. Jadi, sambung permukaan layar besar kepembumian (arde), contoh dengan penjepit kabel ataugelembung kabel yang konduktif. Sangatlah penting untukmenerapkan kabel equalising-potensial untuk menjagakeseimbangan potensial pembumian (arde) yang samamelalui jaringan. Khususnya di instalasi dengan kabelpanjang.Untuk mencegah impedansi yang tidak sesuai, selalumenggunakan jenis kabel yang sama melalui jaringankeseluruhan. Pada saat menyambung motor ke konverterfrekuensi, selalu menggunakan layar kabel motor.

Kabel Screened twisted pair (STP)

Impedansi 120 ΩPanjang kabel Maks. 1200 m (termasuk garis drop)

Maks. 500 stasiun ke stasiun

Tabel 2.8 Informasi Kabel

2.5 Hentian Aman

Konverter frekuensi dapat menjalankan fungsi keselamatanTorsi Aman Tidak Aktif (STO, yang didefinisikan oleh EN IEC61800-5-21) dan Kategori Berhenti 0 (didefinisikan di EN60204-12).Danfoss menyebut fungsionalitas ini Berhenti Aman.Sebelum integrasi dan penggunaan Berhenti Aman di saatpemasangan, harus dilakukan analisa risiko untukmenentukan apakah fungsionalitas Berhenti Aman dantingkat keamanan telah benar dan telah memadai. BerhentiAman dirancang dan telah sesuai dengan persyaratan:

- Keamanan Kategori 3 menurut EN ISO 13849-1

- Tingkat perfoma "d" menurut EN ISO13849-1:2008

- SIL 2 Kapabilitas menurut IEC 61508 dan EN61800-5-2

- SILCL 2 menurut EN 62061

1) Merujuk ke EN IEC 61800-5-2 untuk rincian fungsi torsiAman tidak aktif (STO).2) Merujuk ke EN IEC 60204-1 untuk detail kategori stop 0dan 1.Aktivasi dan terminasi Berhenti AmanFungsi Berhenti aman (STO) diaktifkan dengan melepastegangan pada Terminal 37 dari Inverter Aman. Denganmenyambungkan Inverter Aman ke perangkat keselamataneksternal yang menyediakan, tunda aman, instalasi untukBerhenti aman Kategori 1 dapat diperoleh. Fungsi Stop

aman dapat digunakan untuk asinkron, sinkron, dan motormagnet permanen.

PERINGATANSetelah selesai instalasi dari berhenti aman (STO),pengujian komisi yang tertuju pada 2.5.2 Uji Komisi StopAman harus dijalankan. Pengujian komisi yang telahdiwajibkan setelah pemasangan pertama dan setelahsetiap mengubah derau keselamatan instalasi.

Data Teknis Berhenti AmanNilai berikut ini berhubungan dengan jenis yang berbedapada tingkat keamanan:

Reaksi waktu untuk T37- Waktu reaksi maksimum: 10 md

Waktu reaksi = tunda antara de-penyaluran input STO danmenonaktifkan jembatan output konverter frekuensi.

Data untuk EN ISO 13849-1- Tingkat Perfoma "d"

- MTTFd (Mean Time To Dangerous Failure): 14000tahun

- DC (diagnosa Coverage): 90%

- Kategori 3

- Waktu usia 20 tahun

Data untuk EN IEC 62061, EN IEC 61508, EN IEC 61800-5-2- SIL 2 Kapabilitas, SILCL 2

- PFH (Probability of Dangerous failure perHour)=1e-10FIT=7e-19/h-9/h>90%

- SFF (Safe Failure Fraction) >99%

- HFT (Hardware Fault Tolerance)=0 (1001arsitektur)

- Waktu usia 20 tahun

Data untuk EN IEC 61508 rendah kebutuhan- PFDavg untuk satu tahun uji bukti: 1E-10

- PFDavg untuk tiga tahun uji bukti: 1E-10

- PFDavg untuk lima tahun uji bukti: 1E-10

Tidak ada pemeliharaan dari fungsional STO diperlukan.

Pengukuran pengamanan harus diambil oleh pengguna,contohnya, instalasi kabinet tertutup yang hanya dapatdiakses oleh karyawan yang mempunyai ketrampilan padabidang tersebut.

Data SISTEMAFungsi keamanan data tersedia melalui perpustakaan datauntuk penggunaan dengan alat perhitungan SISTEMA dariIFA (Institusi untuk Keselamatan dan Kesehatan Pekerjaandari Asuransi Kecelakaan Sosial Jerman), dan data untukkalkulasi manual. Perpustakaan secara permanen telahdiselesaikan dan diperpanjang.

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 21

2 2

Page 26: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2.5.1 Terminal 37 Fungsi Stop Aman

Konverter frekuensi tersedia dengan stop aman opsionalsecara fungsional melalui terminal kontrol 37. Stop amanmenonaktifkan tegangan kontrol semikonduktor daya daritingkat output konverter frekuensi. Pada ini dapatmencegah membangkitkan tegangan yang diminta untukmemutar motor. Pada saat Stop Aman (T37) diaktifkan,konverter frekuensi mengeluarkan alarm, trip unit, danmeluncur motor untuk berhenti. Mulai manual kembalidiperlukan. Fungsi stop aman dapat digunakan sebagaistop darurat untuk konverter frekuensi. Pada modusoperasi normal pada saat berhenti aman tidak diperlukan,gunakan fungsi stop regular sebaliknya. Pada saat mulaiotomatis kembali digunakan, pastikan persyaratan ISO12100-2 paragraf 5.3.2.5 adalah fulfilled.

Kondisi Pertanggung-jawabanPeralatan merupakan tanggung jawab pengguna untukmemastikan bahwa personel yang berkualifikasi installsdan operasi fungsi stop aman:

• Baca dan mengerti peraturan tentangkeselamatan mengenai kesehatan danpencegahan keselamatan/kecelakaan

• Mengerti panduan generik dan keselamatan yangdiberikan di deskripsi ini dan perluasan deskripsidi Panduan Rancangan yang relavan

• Mempunyai pengetahuan standar generik dankeselamatan yang sesuai dengan aplikasi spesifik

Pengguna ditentukan sebagai: integrator, operator,layanan, pemeliharaan technician technician.

StandarPenggunaan stop aman di terminal 37 meminta penggunamenyakinkan semua provisi untuk keselamatan termasukhukum, peraturan dan panduan yang berlaku. Fungsi stopaman opsional mematuhi standar berikut.

• IEC 60204-1: 2005 kategori 0 – stop tidakdikontrol

• IEC 61508: 1998 SIL2

• IEC 61800-5-2: 2007 – fungsi torsi tidak aktif (STO)

• IEC 62061: 2005 SIL CL2

• ISO 13849-1: 2006 Kategori 3 PL d

• ISO 14118: 2000 (EN 1037) – mencegahpermulaan tiba-tiba

Informasi dan petunjuk dari manual petunjuk tidakmemadai untuk penggunaan fungsionalitas Berhenti Amanyang benar dan tidak membahayakan. Informasi daninstruksi yang berhubungan dari Panduan Rancangan harusdiikuti.

Proteksi Ukuran

• Karyawan berkualifikasi dan mempunyaiketrampilan diperlukan untuk instalasi dan komisidari sistem teknik keselamatan

• Unit harus diinstal di kabinet IP54 ataulingkungan sekitarnya. Pada aplikasi khusus yanglebih IP degree diperlukan

• Kabel antara terminal 37 dan perangkatkeselamatan eksternal harus menjadi proteksisirkuit pendek menurut ISO 13849-2 tabel D.4

• Ketika eksternal memaksa pengaruh poros motor(sebagai contoh, beban di suspend), tambahanukuran diperlukian (contoh, keselamatan remdapat) untuk menghindari bahaya yang potensial

Instalasi Stop Aman dan Pengaturan

PERINGATANFUNGSI STOP AMAN!Fungsi stop aman TIDAK memisahkan tegangan hantaranlistrik ke konverter frekuensi atau sirkuit pelengkap.Melakukan pekerjaan pada bagian elektrik hanya darikonverter frekuensi atau motor setelah memisahkanpasokan tegangan hantaran listrik dan menunggu durasiwaktu yang spesifik di Tabel 1.1. Gagal memisahkanpasokan tegangan hantaran listrik dari unit dan menunggudurasi waktu dapat menyebabkan kematian ataukecelakaan serius.

• Tidak direkomendasi untuk memberhentikankonverter frekuensi dengan menggunakan fungsiTorsi Aman Tidak aktif. Apabila pengoperasiankonverter frekuensi dihentikan denganmenggunakan fungsi, unit mengalami trip danstop oleh peluncuran. Apabila tidak diterima ataubahaya, gunakan modus berhenti yang lain untukmenghentikan konverter frekuensi dan mesin,sebelum menggunakan fungsi ini. Tergantungpada aplikasi, rem mekanis dapat diperlukan.

• Mengenai synchronous dan konverter frekuensimotor magnet permanen pada kegagalansemikonduktor daya IGBT multipel: Meskipunpengaktifan dari fungsi Torsi Aman Tidak Aktif,sistem dapat memproduksi torsi penjajaran dimana berputar rotates poros motor dengan180/p celsius. p merujuk pada pasangan kutubnomor.

• Fungsi ini sesuai untuk melakukan pekerjaanmekanik hanya pada sistem atau area mesin yanghanya. Hal ini tidak memberikan keselamatanelektrik. Tidak menggunakan fungsi ini sebagaikontrol untuk memulai dan/atau memberhentikankonverter frekuensi.

Instalasi VLT® Petunjuk Operasional Drive HVAC

22 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 27: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Ikuti langkah berikut ini untuk melakukan instalasi amandari konverter frekuensi:

1. Lepaskan kabel jumper antara terminal kontrol 37dan 12 atau 13. Memotong atau mematahkanjumper saja tidak cukup untuk menghindarisirkuit pendek. (Lihat jumper di Ilustrasi 2.27.)

2. Sambung relai monitor keselamatan eksternalmelalui TIDAK ADA fungsi keselamatan keterminal 37 (berhenti aman) dan terminal 12 atau13 (24 V DC). Ikuti instruksi untuk perangkatkeselamatan. Relai monitor keselamatan harusmematuhi dengan kategori 3 PL “d” (ISO 13849-1)atau SIL 2 (EN 62061).

12/13 37

130B

A87

4.10

Ilustrasi 2.27 Jumper antara Terminal 12/13 (24 V) dan 37

130B

C971

.10

12

2

4

1

5

3

37

Ilustrasi 2.28 Instalasi untuk Mencapai Kategori Penghentian 0(EN 60204-1) dengan Cat. /“3 PL “d” (ISO 13849-1 SIL 2) atau (EN62061).

1 Konverter frekuensi

2 Tombol [Reset]

3 Keselamatan relai (cat. 3 PL d, atau SIL2

4 Tombol stop darurat

5 Kabel proteksi sirkuit pendek (jika tidak, di dalam instalasikabinet IP54 )

Tabel 2.9 Legenda ke Ilustrasi 2.28

Uji Komisi Stop AmanSetelah melakukan instalasi dan sebelum melakukanoperasi yang pertama, lakukan pengujian komisi dariinstalasi yang menggunakan berhenti aman. Lebih lanjut,lakukan pengujian setelah setiap modifikasi instalasi.

PERINGATANAktivasi Berhenti Aman (artinya penghapusan pasokantegangan DC 24 V ke terminal 37) tidak memberikankeselamatan listrik. Fungsi Berhenti Aman oleh karena itusendiri tidak cukup untuk implementasi fungsi darurat-Tidak Aktif sebagaimana didefinisikan pada EN 60204-1.Darurat-Tidak Aktif memerlukan pengukuran isolasielektrikal, contohnya, menonaktifkan sumber listrik melaluikontaktor tambahan.

1. Mengaktifkan Fungsi Berhenti Aman denganmelepas pasokan tegangan DC 24 V ke terminal37.

2. Setelah aktivasi Berhenti Aman (artinya, setelahwaktu tanggapan), konverter frekuensi meluncur(menghentikan pembuatan rotasi pada motor).Waktu tanggapan secara khusus kurang dari 10md.

Konverter frekuensi dijamin tidak memulai pembuatankembali rotasi dengan kerusakan internal (menurut Cat. 3PL d acc. EN ISO 13849-1 SIL 2 dan acc. EN 62061). Setelahaktivasi Berhenti Aman, layar menampilkan teks ”BerhentiAman diaktifkan”. Perbantuan teks yang berhubungan,"Berhenti Aman telah diaktifkan”. Ini berarti bahwaBerhenti Aman telah diaktifkan, atau bahwa operasi normalbelum dilanjutkan yet setelah Aktivasi Berhenti Aman

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 23

2 2

Page 28: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

CATATAN!Persyaratan Cat. /“3 PL d” (ISO 13849-1) hanya telah diisipenuh pada saat pasokan 24 V DC ke terminal 37 dihapusatau rendah oleh perangkat keselamatan sendiri yangmemenuhi Cat. 3 PL d” “(ISO 13849-1). Apabila eksternalmemaksa bertindak pada motor, hal tersebut tidak harusberoperasi tanpa ukuran tambahan untuk kegagalanperlindungan. Pemaksaan ekternal dapat memberikan,sebagai contoh, pada kejadian sumbu vertikal (beban disuspend) dimana terjadi pemindahan yang tidak dinginkan,disebabkan oleh gravity, yang dapat menyebabkan bahaya.Ukuran kegagalann perlindungan dapat memberikan remmekanis tambahan.

Dengan standar fungsi Berhenti Aman ditetapkan kePencegahan Mulai tindakan Kembali Tidak Disengaja. Jadi,untuk melanjutkan operasi setelah aktivasi Berhenti Aman,

1. tetapkan tegangan 24 V DC kembali ke terminal37 (Berhenti Aman teks yang telah diaktif masihditampilkan)

2. menghasilkan sinyal reset (via bus, Digital I/O,atau tombol [Reset].

Fungsi Berhenti Aman dapat diatur ke tindakan MulaiOtomatis Kembali. Tetapkan nilai dari 5-19 Terminal 37Berhenti Aman nilai standar [1] ke nilai [3].Restart otomatis berarti bahwa Berhenti Aman diputuskan,dan operasi normal dilanjutkan, 24 V DC yang ditetapkanke Terminal 37 secepatnya. Tidak ada Reset sinyaldiperlukan.

PERINGATANTindakan Restart otomatis diizinkan di satu dari dua situasi:

1. Pencegahan Restart Tidak Disengaja diimplemen-tasikan dengan suku cadang lain dari InstalasiBerhenti Aman.

2. Kehadiran di zona bahaya secara fisik tidakmeliputi pada saat Berhenti Aman Tidakdiaktifkan. Secara khusus, paragraf 5.3.2.5 dari ISO12100-2 2003 harus diamati

2.5.2 Uji Komisi Stop Aman

Setelah melakukan instalasi dan sebelum melakukanoperasi yang pertama, lakukan pengujian komisi dariinstalasi yang menggunakan stop aman.Lakukan pengujian setelah setiap modifikasi lagi dariinstalasi atau aplikasi involving Berhenti Aman.

CATATAN!Pengujian komisi yang telah diwajibkan setelahpemasangan pertama dan setelah setiap mengubah deraukeselamatan instalasi.

Penyiapan uji (pilih satu dari masalah 1 atau 2 sebagaiperaturan):

Hal 1: Pencegahan restart untuk Berhenti Aman diperlukan(artinya hanya Berhenti Aman di mana 5-19 Terminal 37Berhenti Aman diatur ke nilai standar [1], atau BerhentiAman kombinasi dan MCB 112 di mana 5-19 Terminal 37Berhenti Aman diatur ke [6] PTC 1 & Relai A atau [9] PTC 1& Relai W/A):

1.1 Lepaskan pasokan tegangan DC 24 V keterminal 37 menggunakan perangkat pemutussewaktu konverter frekuensi drive motor (artinyapasokan hantaran listrik tidak diganggu). Ujilangkah telah terlewati ketika

• Motor bereaksi dengan peluncuran, dan

• rem mekanis diaktifkan (apakahtersambung)

• alarm “Berhenti Aman [A68]”ditampilkan pada LCP, jika dipasang

1.2 Kirim sinyal Reset (melalui Bus, I/O Digital,atau [tombol Reset]). Uji langkah telah terlewatiapabila motor akan tetap pada keadaan berhentiaman, dan rem mekanis (apabila tersambung) iniakan tetap diaktifkan.

1.3 Tetapkan kembali DC 24 V ke terminal 37. Ujilangkah telah terlewati apabila motor tetapberada di dalam keadaan meluncur, dan remmekanis (apakah tersambung) ini akan tetapdiaktifkan.

1.4 Kirim sinyal Reset (melalui Bus, I/O Digital,atau [tombol Reset]). Uji langkah telah terlewatiketika motor menjadi operasional lagi.

Pengujian komisi yang telah terlewati apabila semuaempat uji langkah 1.1, 1.2, 1.3 dan 1.4 akan terlewati.

Hal 2: Restart otomatis dari berhenti aman diperlukan dandiizinkan (artinya, berhenti aman hanya di mana5-19 Terminal 37 Berhenti Aman ditetapkan ke [3], ataudikombinasikan berhenti aman dan MCB 112 di mana5-19 Terminal 37 Berhenti Aman ditetapkan ke [7] PTC 1 &relai W atau [8] PTC 1 & relai A/W):

2.1 Lepaskan pasokan tegangan DC 24 V keterminal 37 oleh perangkat pemutus sewaktukonverter frekuensi drive motor (artinya pasokanhantaran listrik tidak diganggu). Uji langkah telahterlewati ketika

• Motor bereaksi dengan peluncuran, dan

• rem mekanis diaktifkan (apakahtersambung)

• alarm “Berhenti Aman [A68]”ditampilkan pada LCP, jika dipasang

2.2 Tetapkan kembali DC 24 V ke terminal 37.

Instalasi VLT® Petunjuk Operasional Drive HVAC

24 MG11AI9B - VLT® merek dagang terdaftar Danfoss

22

Page 29: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Uji langkah telah terlewati apabila motor menjadioperasional lagi. Pengujian komisi yang telah terlewatiapabila kedua uji langkah 2.1 dan 2.2 dapat terlewati.

CATATAN!Lihat peringatan pada restart perilaku pada 2.5.1 Terminal37 Fungsi Stop Aman

PERINGATANFungsi Stop aman dapat digunakan untuk asinkron,sinkron dan motor magnet permanen. Dua masalah dapatterjadi di semikonduktor daya dari konverter frekuensi.Saat menggunakan atau magnet permanen sinkron a sisarotasi motor dapat menyebabkan dari masalah. Rotasi yangdapat diperhitungkan ke sudut = 360/(jumlah kutub).Aplikasi menggunakan atau magnet permanen sinkronmotor harus diambil ini rotasi sisa ke consideration danpastikan bahwa hal tersebut tidak pose aman risiko. Situasiini tidak relavan untuk motor asinkron.

Instalasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 25

2 2

Page 30: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

3 Permulaan dan Pengujian Fungisonal

3.1 Sebelum mulai

3.1.1 Pemeriksaan Keselamatan

PERINGATANTEGANGAN TINGGI!Apabila sambungan input dan output telah tersambungtidak secara benar, hal tersebut menimbulkan potensitegangan tinggi pada terminal ini. Apabila penggunaandaya untuk motor multipel tidak berjalan pada saluranyang sama, hal tersebut akan terjadi arus kebocoran untukmengisi kapasitor diantara konverter frekuensi, pada saatdiputuskan dari input sumber listrik. Untuk permulaaanawal, tidak ada asumsi tentang komponen daya. Ikutiprosedur sebelum memulai. Tidak mengikuti prosedursebelum memulai dapat menyebabkan cedera personalatau kerusakan pada peralatan.

1. Daya input ke unit harus DINONAKTIFKAN dandikunci. Tidak tergantung pada saklar pemutusankonverter frekuensi untuk isolasi daya input.

2. Pengujian dengan tidak adanya tegangan padaterminal input L1 (91), L2 (92), dan L3 (93) fasa kefasa dan fasa ke arde,

3. Pengujian tidak adanya tegangan pada terminaloutput 96 (U) 97(V), dan 98 (W), fasa ke fasa danfasa ke arde.

4. Konfirmasi berkelanjutan dari motor denganmengukur angka ohm pada U-V (96-97), V-W(97-98), dan W-U (98-96).

5. Periksa untuk arde dari konverter frekuensi danmotor yang benar.

6. Periksa konverter frekuensi untuk putuskansambungan ke terminal.

7. Catat data pelat nama-motor berikut: daya,tegangan, frekuensi, arus beban penuh, dankecepatan nominal. Angka ini diperlukan untukprogram data pelat nama motor di kemudianhari.

8. Konfirmasi bahwa tegangan pasokan cocokdengan tegangan konverter dan motor.

Permulaan dan Pengujian Fun... VLT® Petunjuk Operasional Drive HVAC

26 MG11AI9B - VLT® merek dagang terdaftar Danfoss

33

Page 31: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

KEWASPADAANSebelum menerapkan daya ke unit, periksa seluruh instalasisecara detail di Tabel 3.1. Periksa tanda untuk item padasaat selesai.

Periksa untuk Keterangan Perlengkapan peralatan • Lihat untuk perlengkapan peralatan, saklar, pemutusan, atau sekering/breaker sirkuit yang bertempat

di daya input di bagian konverter frekuensi atau output motor. Pastikan bahwa semuanya telah siapuntuk operasi kecepatan penuh.

• Periksa fungsi dan instalasi sensor yang digunakan untuk umpan-balik ke konverter frekuensi.

• Lepas cap koreksi faktor daya pada motor, jika ada

Routing kabel • Pastikan bahwa daya input, kabel motor dan kabel kontrol terpisah atau pada tiga saluran metalikyang terpisah untuk isolasi kebisingan frekuensi tinggi

Wiring kontrol • Periksa untuk kegagalan atau kerusakan kabel dan kendurnya sambungan

• Periksa bahwa kabel kontrol diisolasikan dari kabel daya dan motor untuk immunitas kebisingan

• Periksa sumber tegangan sinyal, apabila diperlukan

• Penggunaan kabel pelindung atau pasangan twisted disarankan. Pastikan bahwa pelindungdiputuskan secara benar

Pengosonganpendinginan

• Ukur jarak ruang bagian atas dan bawah pengosongan yang cukup pada bagian atas dan bawahuntuk memastikan pendinginan aliran udara menurut ukuran unit.

Pertimbangan EMC • Periksa untuk intalasi yang benar dengan kecocokan elektromagnetik

Pertimbanganlingkungan

• Lihat label peralatan untuk batas suhu operasi lingkungan maksimum batas suhu

• Tingkat kelembaban harus 5-95% tidak padat

Sekering dan pemotongsirkuit

• Periksa untuk sekering atau pemotong sirkuit yang benar

• Periksa bahwa semua sekering dimasukkan secara benar dan dalam kondisi operasional dan semuapemotong sirkuit di posisi terbuka

Pembumian (Arde) • Unit memerlukan kabel pembumian (kabel arde) dari sasis ke arde bangunan (arde)

• Kriteria sambungan pembumian (sambungan arde) yang baik adalah rapat dan bebas dari oksidasi

• Pembumian (arde) ke saluran atau pemasangan panel belakang ke permukaan metal tidak dianggapsebagai arde yang sesuai (arde)

Kabel daya input danoutput

• Periksa untuk melepaskan sambungan

• Periksa bahwa motor dan sumber listrik merupakan saluran terpisah atau kabel di-screen yangterpisah

Interior panel • Periksa bahwa interior unit bebas dari debu, potongan metal, embun, dan korosi

Saklar • Pastikan bahwa semua sakalar dan pengaturan pemutusan pada di posisi yang benar

Getaran • Periksa unit yang dipasang secara solid atau pemasangan kejutan digunakan, apabila diperlukan

• Periksa untuk jumlah getaran unit yang tidak seperti biasanya

Tabel 3.1 Permulaan Pemeriksaan

Permulaan dan Pengujian Fun... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 27

3 3

Page 32: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

3.2 Tetapkan Daya

PERINGATANTEGANGAN TINGGI!Konverter frekuensi berisi tegangan tinggi pada saattersambung ke sumber listrik AC. Instalasi,, permulaan danpemeliharaan dapat dilakukan oleh pekerja yangmemenuhi standar yang berlaku. Tidak mematuhinyadapat menyebabkan kematian atau cedera yang serius.

PERINGATANSTART YANG TIDAK DISENGAJA!Pada saat konverter frekuensi tersambung ke hantaranlistrik AC, motor dapat memulai kapan saja. Konverterfrekuensi, motor dan peralatan apa saja yang dijalankanharus diperiksa kesiapan pengoperasiannya. Gagalmematuhinya dapat menyebabkan kematian, cedera serius,kerusakan peralatan, atau properti.

1. Konfirmasi bahwa tegangan input seimbangdiantara 3%. Jika tidak, koreksi tegangan inputmengalami ketidakseimbangan sebelummemproses lebih lanjut. Ulangi prosedur inisetelah koreksi tegangan.

2. Pastikan bahwa kabel peralatan optional, jika ada,mencocokkan aplikasi instalasi.

3. Pastikan bahwa semua perangkat operator diposisi TIDAK AKTIF. Pintu panel tertutup ataupenutup dipasang.

4. Terapkan daya ke unit. TIDAK memulai konverterfrekuensi pada saat ini. Untuk unit denganmemutus saklar, aktifkan ke posisi AKTIF untukmenerapkan daya ke konverter frekuensi.

CATATAN!Pada saat status line berada di bagian bawah daripembacaan LCP PELUNCURAN JAUH TERBALIK atauInterlock Eksternal Alarm 60 ditampilkan, hal inimenunjukkan bahwa unit telah siap untuk beroperasitetapi masih terjadi kekurangan pada input di terminal 27.Lihat Ilustrasi 2.27 untuk detail.

3.3 Program Operasional Dasar

3.3.1 Memerlukan Permulaan ProgramKonverter-frekuensi

CATATAN!Apabila wizard sedang berjalan, abaikan berikut.

Konverter frekuensi memerlukan program operasionaldasar sebelum menjalankan kinerja yang maksimal.Program operasional dasar memerlukan masukan datanama pelat motor untuk motor yang sedang dioperasikandan kecepatan minimum dan maksimum kecepatan motor.Masukkan data menurut prosedur berikut. Rekomendasipengaturan Parameter dimaksud untuk tujuan permulaandan pemeriksaan. Pengaturan Aplikasi dapat berubah. Lihat4 Penghubung pengguna untuk instruksi detail dalammemasukan data melalui LCP.

Masukkan data dengan daya AKTIF, tetapi sebelummengoperasikan konverter frekuensi.

1. Tekan [Menu Utama] dua kali pada LCP.

2. Penggunaan tombol navigasi untuk skrol grupparameter 0-** Operasi/Tampilan dan tekan [OK].

130B

P066

.10

1107 RPM

0 - ** Operasi/Tampilan

1 - ** Beban/Motor

2 - ** Rem

3 - ** Referensi / Ramp

3,84 A 1 (1)

Menu Utama

Ilustrasi 3.1 Menu Utama

3. Gunakan tombol navigasi untuk skrol grupparameter 0-0* Pengaturan dasar dan tekan [OK].

0-**Operation / Display0.0%

0-0* Basic Settings

0-1* Set-up Opperations

0-2* LCP Display

0-3* LCP Custom Readout

0.00A 1(1)

130B

P087

.10

Ilustrasi 3.2 Operasi/Tampilan

Permulaan dan Pengujian Fun... VLT® Petunjuk Operasional Drive HVAC

28 MG11AI9B - VLT® merek dagang terdaftar Danfoss

33

Page 33: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

4. Gunakan tombol navigasi untuk skrol ke0-03 Pengaturan Wilayah dan tekan [OK].

0-0*Basic Settings0.0%

0-03 Regional Settings

[0] International

0.00A 1(1)

130B

P088

.10

Ilustrasi 3.3 Pengaturan Dasar

5. Gunakan tombol navigasi untuk memilh [0]Internasional atau [1] Amerika Utara dan tekan[OK]. (Perubahan pengaturan standar untukjumlah parameter dasar. Lihat 5.4 PengaturanParameter Standar Internasional/Amerika Utarauntuk data yang lebih lengkap.)

6. Tekan [Menu Cepat] di LCP.

7. Gunakan tombol navigasi untuk skrol grupparameter Pengaturan cepat Q2 dan tekan [OK].

130B

B847

.10

Q1 My Personal Menu

Q2 Quick Setup

Q5 Changes Made

Q6 Loggings

13.7% 13.0A 1(1)

Quick Menus

Ilustrasi 3.4 Menu Cepat

8. Pilih bahasa dan tekan [OK].

9. Kabel jumper harus ditempatkan antara terminalkontrol 12 dan 27. Apabila masalahnya seperti ini,tinggalkan 5-12 Terminal 27 Input Digital padastandar pabrik. Jika tidak, pilih Tidak ada Operasi.Untuk konverter frekuensi dengan bypass Danfossoptional, tidak ada kabel jumper diperlukan.

10. 3-02 Referensi Minimum

11. 3-03 Referensi Maksimum

12. 3-41 Waktu tanjakan Ramp 1

13. 3-42 Waktu Turunan Ramp 1

14. 3-13 Situs Referensi. Terhubung ke Hand/Auto*Remote Lokal.

3.4 Pengaturan Motor Asinkron

Masukkan data motor di parameter 1-20/1-21 ke 1-25.Informasi dapat ditemukan di pelat nama motor.

1. 1-20 Daya Motor [kW] atau 1-21 Dayamotor [HP]

1-22 Tegangan Motor

1-23 Frekuensi Motor

1-24 Arus Motor

1-25 Kecepatan Nominal Motor

130B

T772

.10

Q2

0.0 Hz 0.00kW 1(1)

Motor Setup

1 - 21 Motor Power [kW]

4.0 kW

Ilustrasi 3.5 Pengaturan Motor

3.5 Pengaturan Motor Lanjutan

KEWASPADAANLakukan hanya menggunakan motor PM dengan kipas danpompa.

Permulaan Langkah-Langkah Program1. Operasi mengaktifkan motor PM 1-10 Konstruksi

Motor, pilih [1) PM, SPM tak mnyolok

2. Pastikan untuk mengatur 0-02 Unit KecepatanMotor ke [0] RPM

Program data motor.Setelah memilih motor PM pada 1-10 Konstruksi Motor,motor PM-parameter yang terkait di grup parameter 1-2*,1-3* dan 1-4* yang aktif.Informasi dapat ditemukan di pelat nama motor dan dilembar data motor.Parameter berikut ini juga harus diprogram di daftarpemesanan

1. 1-24 Arus Motor

2. 1-26 Torsi Terukur Kontrol Motor

3. 1-25 Kecepatan Nominal Motor

4. 1-39 Kutub Motor

5. 1-30 Resistansi Stator (Rs)Masukkan garis untuk angka resistansi anginstator (Rs). Apabila data hanya terdapat garisyang tersedia, bagi yang terdapat garis nilai

Permulaan dan Pengujian Fun... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 29

3 3

Page 34: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

dengan 2 untuk mencapai yang garis nilai secaraumum (starpoint).Juga dimungkinkan untuk mengukur nilai denganohmmeter, yang juga akan berlangsung resistensiresistor kabel ke account. Membagi nilai yangdiukur dengan 2 dan masukkan hasil.

6. 1-37 Induktansi sumbu-d (Ld)Masukkan garis secara umum induksi axislangsung dari motor PM.Apabila hanya saat data terdapat garis tersedia,membagi yang terdapat garis nilai dengan 2untuk mencapai nilai saluran-umum (starpoint).Juga dimungkinkan untuk mengukur nilai denganinductancemeter, yang juga akan berlangsungyang induktansi dari kabel ke account. Membaginilai yang diukur dengan 2 dan masukkan hasil.

7. 1-40 EMF Balik pada 1000 RPMMasukkan garis ke garis EMF balik dari Motor PMpada kecepatan mekanik 1000 RPM (nilai RMS).EMF Balik merupakan tegangan yang dihasilkanoleh motor PM pada saat tidak ada drive yangtersambung dan poros diputar secara eksternal.EMF balik ini biasanya ditentukan untukkecepatan motor nominal atau untuk1000 RPMyang terukur diantara dua baris. Apabila nilaitidak tersedia untuk kecepatan motor 1000 RPM,hitunglah nilai yang benar sebagai berikut:Apabila EMF balik merupakan contoh 320 V pada1800 RPM, yang dapat dihitung pada 1000 RPMsebagai berikut: EMF balik= (Tegangan /RPM)*1000 = (320/1800)*1000 = 178. Ini adalahnilai yang harus diprogram untuk 1-40 EMF Balikpada 1000 RPM

Pengujian Operasi Motor1. Memulai motor pada kecepatan rendah (100 ke

200 RPM). Apabila motor tidak berputar, periksainstalasi, program umum dan data motor.

2. Periksa apabila fungsi start pada 1-70 PM StartMode sesuai dengan aplikasi persyaratan.

Deteksi RotorFungsi ini merupakan pilihan yang disarankan untukaplikasi di mana motor memulai dari perhentian pompaatau konveyor. Pada beberapa motor, kondisi soundakustik terdengar pada saat basis impuls yang dikirimkeluar. Hal ini tidak membahayakan motor.

Waktu ParkirFungsi ini merupakan pilihan yang disarankan untukaplikasi di mana motor berputar pada kecepatan lambatcontoh kitiran pada aplikasi kipas. 2-06 Parking Current dan2-07 Parking Time dapat disesuaikan. Peningkatanpengaturan pabrik dari parameter ini untuk aplikasidengan inersia tinggi.

Mulai motor pada kecepatan nominal. Apabila aplikasitidak berjalan dengan baik, periksa pengaturan VVCplus PM.

Rekomendasi pada aplikasi yang berbeda dapat dilihat diTabel 3.2.

Aplikasi P'aturan

Aplikasi Inersia RendahIBeban/IMotor <5

1-17 Voltage filter time const. akandinaikkan sebanyak faktor 5 ke 101-14 Damping Gain harus dikurangi1-66 Arus min. pada KecepatanRendah harus dikurangi (<100%)

Aplikasi Inersia Rendah50>IBeban/IMotor >5

Menjaga nilai terhitung

Aplikasi Inersia TinggiIBeban/IMotor > 50

1-14 Damping Gain, 1-15 Low SpeedFilter Time Const. dan 1-16 HighSpeed Filter Time Const. harus diting-katkan

Beban tinggi padakecepatan rendah<30% (kecepatan terukur)

1-17 Voltage filter time const. harusditingkatkan1-66 Arus min. pada KecepatanRendah harus ditingkatkan (>100%untuk waktu lebih lama dapatterjadi kepanasan pada motor)

Tabel 3.2 Rekomendasi di Berbagai Aplikasi

Apabila motor berjalan pada kecepatan tertentu, naikkan1-14 Damping Gain. Naikkan nilai dengan langkah berikut.Tergantung pada motor, nilai yang baik untuk parameterini dapat 10% atau 100% lebih tinggi daripada nilaistandar.

Torsi awal dapat disesuaikan di 1-66 Arus min. padaKecepatan Rendah. 100% menyediakan torsi awal nominalsebagai torsi awal.

3.6 Penyesuaian Motor Otomatis

Penyesuaian motor otomatis (AMA) merupakan prosedurpengujian yang mengukur karakteristik elektrik motoruntuk mengoptimalkan kesesuaian antara konverterfrekuensi dan motor.

• Konverter frekuensi membangun model motorsecara matematika untuk peraturan arus motorkeluar. Prosedur juga menguji keseimbangan fasainput dari daya elektrik. Prosedur memban-dingkan karakteristik motor dengan daya yangdimasukkan di parameter 1-20 ke 1-25.

• Hal tersebut tidak menyebabkan motor untukberjalan atau membahayakan motor

• Beberapa motor tidak dapat dijalankan untukmenyelesaikan versi pengujian. Pada masalah itu,pilih [2] Aktifkan pengurangan AMA

• Apabila filter output tersambung ke motor, pilihAktifkan pengurangan AMA

Permulaan dan Pengujian Fun... VLT® Petunjuk Operasional Drive HVAC

30 MG11AI9B - VLT® merek dagang terdaftar Danfoss

33

Page 35: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

• Apabila peringatan atau alarm terjadi, lihat8 Peringatan dan Alarm

• Jalankan prosedur ini pada pendingin motoruntuk hasil yang baik

CATATAN!Algoritma AMA tidak bekerja pada saat menggunakanmotor PM.

Untuk menjalankan AMA1. Tekan [Menu Utama] untuk mengakses

parameter.

2. Skrol ke grup parameter 1-** Beban dan Motor.

3. Tekan [OK].

4. Skrol ke grup parameter 1-2* Data Motor.

5. Tekan [OK].

6. Skrol ke 1-29 Penyesuaian Motor Otomatis (AMA).

7. Tekan [OK].

8. Pilih [1] Aktifkan AMA lengkap.

9. Tekan [OK].

10. Ikuti instruksi pada layar.

11. Pengujian akan berjalan secara otomatis danmemberikan indikasi pada saat telah selesai.

3.7 Periksa Rotasi Motor

Sebelum menjalankan konverter frekuensi, periksa motorrotation. Motor akan berjalan secara singkat pada 5 Hzatau frekuensi minimum yang diatur pada 4-12 BatasanRendah Kecepatan Motor [Hz]..

1. Tekan [Menu cepat].

2. Skrol ke Pengaturan Cepat Q2.

3. Tekan [OK].

4. Skrol ke 1-28 Periksa Rotasi Motor.

5. Tekan [OK].

6. Skrol untuk [1] Aktif.

Teks berikut akan muncul: Catatan! Motor dapat berjalandgn arah keliru.

7. Tekan [OK].

8. Ikuti instruksi pada layar.

Untuk mengubah arah rotasi, lepaskan daya ke konverterfrekuensi dan tunggu daya untuk berhenti. Membalikkansambungan dua dari tiga kabel motor pada motor ataubagian motor atau konverter frekuensi dari koneksi.

3.8 Pengujian Kontrol-lokal

KEWASPADAANMOTOR MULAI!Pastikan bahwa motor, sistem, dan peralatanyang terlampirtelah siap untuk memulai. Peralatan merupakan tanggungjawab pengguna untuk memastikan pengoperasian yangaman di bawah kondisi apa pun. Tidak mengikuti prosedurmotor, sistem, dan peralatan yang terlampir untuk siapdimulai dapat menyebabkan cedera personal ataukerusakan peralatan.

CATATAN!Tombol [Kanan Aktif] menyediakan perintah mulai lokal kekonverter frekuensi. Tombol [Off] menyediakan fungsi stop.Pada saat mengoperasikan di modus lokal, [] dan []menambah dan mengurangi output kecepatan darikonverter frekuensi. [] dan [] memindahkan kursortampilan pada tampilan numerik.

1. Tekan [Hand On].

2. Menambah konverter frekuensi dengan menekan[] untuk kecepatan penuh. Memindahkan kursorke kiri dari poin desimal menyediakan perubahaninput yang lebih cepat.

3. Catatan masalah akselerasi.

4. Tekan [Tidak Aktif].

5. Catatan masalah penurunan.

Apabila masalah penambahan ditemukan

• Apabila peringatan atau alarm terjadi, lihat 8 Peringatan dan Alarm

• Periksa bahwa data motor dimasukkan secarabenar

• Penambahan waktu ramp-atas percepatan waktudi 3-41 Waktu tanjakan Ramp 1

• Tambahkan batas arus di 4-18 Batas Arus

• Tambahkan batas torsi di 4-16 Mode MotorBatasan Torsi

Apabila masalah penurunan ditemukan

• Apabila peringatan atau alarm terjadi, lihat 8 Peringatan dan Alarm.

• Periksa bahwa data motor dimasukkan secarabenar.

• Tambahkan waktu ramp-bawah penurunan waktudi 3-42 Waktu Turunan Ramp 1.

• Aktifkan kontrol tegangan berlebih di2-17 Pengontrol tegangan berlebih.

Permulaan dan Pengujian Fun... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 31

3 3

Page 36: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Lihat 4.1.1 Panel Kontrol Lokal (LCP) untuk mengatur ulangkonverter frekuensi setelah trip.

CATATAN!3.1 Sebelum mulai to 3.8 Pengujian Kontrol-lokal menyim-pulkan prosedur untuk menetapkan daya ke konverterfrekuensi, program dasar, pengaturan dan pengujianfungisonal.

3.9 Permulaan Sistem

Prosedur di bagian ini memerlukan kabel-pengguna danprogram aplikasi untuk diselesaikan. 6 Contoh PengaturanAplikasi dimaksud untuk membantu tugas ini. Bantuan lainuntuk pengaturan aplikasi didaftar di 1.2 SumberTambahan. Prosedur berikut disarankan setelah pengaturanaplikasi oleh pengguna terpenuhi.

KEWASPADAANMOTOR MULAI!Pastikan bahwa motor, sistem dan peralatanyang terlampirtelah siap untuk memulai. Peralatan merupakan tanggungjawab pengguna untuk memastikan pengoperasian yangaman di bawah kondisi apa pun. Tidak mengikuti dapatmenyebabkan cedera personal atau kerusakan peralatan.

1. Tekan [Otomatis Aktif].

2. Pastikan bahwa fungsi kontrol eksternal telahdisambung secara benar ke konverter frekuensidan semua program telah terpenuhi.

3. Terapkan perintah jalankan eksternal.

4. Sesuaikan referensi kecepatan melalui jarakkecepatan.

5. Lepaskan perintah jalankan eksternal.

6. Catatan masalah apa saja.

Apabila peringatan atau alarm terjadi, lihat 8 Peringatandan Alarm.

3.10 Desis Akustik atau Getaran

Jika motor atau peralatan dijalankan oleh motor - misalnyapisau kipas - membuat suara atau getaran pada frekuensitertentu, coba berikut:

• Kecepatan Bypass, grup parameter 4-6*

• Modulasi-lebih, 14-03 Kelebihan modulasi diatur ketidak aktif

• Pattern switching dan frekuensi switching grupparameter 14-0*

• Peredaman Resonansi, 1-64 Peredaman Resonansi

Permulaan dan Pengujian Fun... VLT® Petunjuk Operasional Drive HVAC

32 MG11AI9B - VLT® merek dagang terdaftar Danfoss

33

Page 37: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

4 Penghubung pengguna

4.1 Panel Kontrol Lokal (LCP)

Panel kontrol lokal (LCP) merupakan tampilan yangdikombinasikan dan keypad pada unit bagian depan. LCPmerupakan interface pengguna ke konverter frekuensi.

LCP mempunyai beberapa fungsi pengguna.

• Mulai, stop, dan kecepatan kontrol pada saat dikontrol lokal

• Tampilkan data operasional, status, peringatandan perhatian

• Program fungsi konverter frekuensi

• Reset konverter frekuensi secara manual setelahkesalahan pada saat reset otomatis dinonaktifkan

Numerik optional LCP (NLCP) juga tersedia. NLCPmengoperasikan pada tata cara yang hampir sama denganLCP. Lihat Panduan Pemrograman selengkapnya padapengggunaan NLCP.

CATATAN!Tampilan kontras dapat disesuaikan dengan menekan[STATUS] dan tombol []/[]

4.1.1 Susunan LCP

LCP dibagi dalam empat grup fungsional (lihat Ilustrasi 4.1).

Autoon ResetHand

onO

StatusQuickMenu

MainMenu

AlarmLog

Cancel

Info

Status 1(1)1234rpm

Back

OK

43,5Hz

Run OK

43,5Hz

On

Alarm

Warn.

130B

C362

.10

a

b

c

d

1.0 A

Ilustrasi 4.1 LCP

a. Tampilan area.

b. Tombol menu tampilan untuk mengubahtampilan guna memperlihatkan pilihan status,program, atau riwayat pesan salah.

c. Tombol navigasi untuk fungsi program,memindahkan kursor tampilan, dan kontrolkecepatan pada operasi lokal. Termasuk jugalampu indikator status.

d. Tombol modus operasional dan reset.

Penghubung pengguna VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 33

4 4

Page 38: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

4.1.2 Pengaturan Angka tampilan LCP

Tampilan area diaktifkan pada saat konverter frekuensimenerima daya dari tegangan hantaran listrik, terminal busDC, atau pasokan eksternal 24 V DC pasokan.

Tampilan informasi pada LCP dapat disesuakan untukaplikasi pengguna.

• Pada masing-masing pembacaan tampilanmempunyai parameter yang berhubungan

• Opsi terpilih di menu cepat Q3-13 PengaturanTampilan

• Tampilan 2 mempunyai opsi tampilan alternatifyang lebih besar

• Status konverter frekuensi pada bagian bawahdari tampilan secara otomatis dihasilkan dan tidakdapat dipilih

1.1

2

3 1.3

1.2

130B

T831

.10

0.0%

Off Remote Stop

1 (1)0.00 kw0.00 A

0.0Hz

2605kWh

Status

Ilustrasi 4.2 Pembacaan Tampilan

Tampilan Nomor parameter Pengaturan standar

1.1 0-20 Referensi %

1.2 0-21 Arus motor

1.3 0-22 Daya [kW]

2 0-23 Frekuensi

3 0-24 penghitung kWh

Tabel 4.1 Legenda ke Ilustrasi 4.2

4.1.3 Tampilan Tombol Menu

Tombol menu digunakan untuk akses menu pengaturanparameter, toggle melalui modus tampilan status selamaoperasi normal, dan memperlihatkan data log masalah.

130B

P045

.10

Status QuickMenu

MainMenu

AlarmLog

Ilustrasi 4.3 Tombol Menu

Tombol FungsiStatus Memperlihatkan informasi operasional.

• Pada Modus otomatis, tekan untuk toggleantara tampilan pembacaan status

• Tekan berulang kali untuk skrol melaluipada masing-masing tampilan status

• Tekan [Status] plus [] atau [] untuk

menyesuaikan tampilan terang

• Simbol bagian tampilan pojok atas memper-lihatkan arah dari putaran motor danpengaturan menjadi aktif. Ini tidak dapatdiprogram.

Menu Cepat Memungkinkan akses untuk parameter programuntuk permulaan instruksi pengaturan danbeberapa instruksi aplikasi detail.

• Tekan untuk mengakses Pengaturan CepatQ2 untuk instruksi yang berurutan gunamemprogram pengaturan pengontrolfrekuensi

• Mengikuti urutan parameter sebagaiperkenalan untuk pengaturan fungsi

Menu Utama Memungkinkan akses untuk semua parameterprogram.

• Tekan dua kali untuk mengakses indekstingkat atas

• Tekan sekali untuk kembali ke lokasi yangdiakses terakhir kalinya

• Tekan untuk masuk ke nomor parameteruntuk akses langsung ke parameter tersebut

Log alarm Menampilkan daftar arus peringatan, 10 alarmyang terakhir, dan log pemeliharaan.

• Untuk informasi selengkapnya tentangkonverter frekuensi sebelum memasukkanmodus alarm, pilih nomor alarm denganmenggunakan tombol navigasi dan tekan[OK].

Tabel 4.2 Fungsi Keterangan Tombol Menu

Penghubung pengguna VLT® Petunjuk Operasional Drive HVAC

34 MG11AI9B - VLT® merek dagang terdaftar Danfoss

44

Page 39: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

4.1.4 Tombol Navigasi

Tombol navigasi digunakan untuk fungsi program danmemindahkan kursor tampilan. Tombol navigasi jugamenyediakan kontrol kecepatan pada operasi (tangan)lokal. Tiga status lampu indikator status konverter frekuensijuga ditempatkan di area ini.

130B

T117

.10

OK

Back

InfoWarm

Alarm

On

Cancel

Ilustrasi 4.4 Tombol Navigasi

Tombol Fungsi

Kembali Kembali pada langkah atau daftar sebelumnya distruktur menu.

Batal Batalkan perubahan atau perintah yang terakhirselama modus tampilan tidak berubah.

Info Tekan untuk definisi fungsi yang telah ditampilkan.

TombolNavigasi

Gunakan empat tanda panah navigasi untukmemindahkan antar aitem di menu.

OK Gunakan untuk mengakses grup parameter ataumengaktifkan pilihan.

Tabel 4.3 Fungsi Tombol Navigasi

Lampu Indikator Fungsi

Hijau NYALA LAMPU NYALA pada saat konverterfrekuensi menerima daya daritegangan sumber listrik, terminalbus DC, atau dari catu eksternal 24V.

Kuning PERINGATAN Pada saat kondisi peringatanditampilkan, Lampu PERINGATANkuning nyala dan teksmenampilkan tampilan area yangmengidentifikasikan masalah.

Merah ALARM Kondisi bermasalah dapatmengakibatkan ampu alarm merahberkedit dan teks alarmditampilkan.

Tabel 4.4 Fungsi Lampu Indikator

4.1.5 Tombol operasi

Tombol operasi dapat dicari di bagian bawah LCP.

130B

P046

.10

Handon O Auto

on Reset

Ilustrasi 4.5 Tombol operasi

Tombol Fungsi

Hand On Memulai konverter frekuensi di kontrol lokal.

• Gunakan tombol navigasi untuk mengontrolkecepatan konverter frekuensi

• Eksternal memberhentikan sinyal denganmengontrol komunikasi input ataukomunikasi serial mengesampingkan hand onlokal

Mati Memberhentikan motor tetapi tidak melepasdaya ke konverter frekuensi.

Otomatis On Tempatkan sistem di modus operasional jauh.

• Menjawab perintah mulai eksternal dengankontrol terminal atau komunikasi serial

• Referensi kecepatan dari sumber eksternal

Reset Reset konverter frekuensi secara manual setelahmasalah telah terdeteksi.

Tabel 4.5 Fungsi Tombol Operasi

4.2 Cadangan dan Menyalin PengaturanParameter

Data program disimpan secara interal di konverterfrekuensi.

• Data dapat dimuat di memori LCP sebagaicadangan penyimpanan

• Pada saat disimpan di LCP, data dapat disimpansecara internal di konverter frekuensi.

• Data juga dapat didownload ke konverterfrekuensi yang lain dengan menyambungkan kedalam unit tersebut dan mendownloadpengaturan yang disimpan. (Hal ini merupakancara cepat untuk memprogram multipel unitdengan pengaturan yang sama).

• Inisialisasi konverter frekuensi untuk mengem-balikan pengaturan standar pabrik tidakmengubah data yang disimpan di memori LCP

Penghubung pengguna VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 35

4 4

Page 40: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

PERINGATANSTART YANG TIDAK DISENGAJA!Pada saat konverter frekuensi tersambung ke hantaranlistrik AC, motor dapat memulai kapan saja. Konverterfrekuensi, motor dan peralatan apa saja yang dijalankanharus diperiksa kesiapan pengoperasiannya. Tidakmengikuti prosedur kesiapan pengoperasional pada saatkonverter frekuensi tersambung ke sumber listrik AC dapatmenyebabkan kematian, cedera serius, atau kerusakanperalatan, atau properti.

4.2.1 Upload Data ke LCP

1. Tekan [Tidak aktif] untuk hentikan motor sebelummemuat atau mendownload data.

2. Ke 0-50 Copy LCP.

3. Tekan [OK].

4. Pilih “Semua ke LCP”

5. Tekan [OK]. Progress bar memperlihatkan prosesmuat.

6. Tekan [Hand Aktif] atau [Otomatis Aktif] untukkembali ke operasi normal.

4.2.2 Download Data dari LCP

1. Tekan [Tidak aktif] untuk hentikan motor sebelummemuat atau mendownload data.

2. Ke 0-50 Copy LCP.

3. Tekan [OK].

4. Pilih “Semua dari LCP”

5. Tekan [OK]. Progress bar memperlihatkan prosesdownload.

6. Tekan [Hand Aktif] atau [Otomatis Aktif] untukkembali ke operasi normal.

4.3 Mengembalikan Pengaturan Standar

KEWASPADAANInisialisasi mengembalikan unit ke pengaturan standarpabrik. Catatanprogram, data motor, lokalisasi, dan monitorakan hilang. Pemuatan data ke LCP menyediakancadangan sebelum inisialisasi.

Mengembalikan pengaturan parameter konverter frekuensiyang kembali ke angka standar dilakukan dengan inisia-lisasi dari konverter frekuensi. Inisialisasi dapat melalui14-22 Modus Operasi atau secara manual.

• Inisialisasi menggunakan 14-22 Modus Operasitidak mengubah data konverter frekuensi sepertijam operasi, pilihan komunikasi serial, pengaturan

menu personal, log masalah, log alarm, danfungsi monitor lainnya

• Penggunaan 14-22 Modus Operasi secara umumdisarankan

• Inisialisasi manual menghapus semua motor,program, lokalisasi, dan memonitor data danmengembalikan pengaturan standar pabrik

4.3.1 Inisialisasi Yang Disarankan

1. Tekan [Menu Utama] du kali untuk mengaksesparameter.

2. Skrol ke 14-22 Modus Operasi.

3. Tekan [OK].

4. Skrol ke Inisialisasi.

5. Tekan [OK].

6. Putuskan daya ke unit dan tunggu sampai layarmati.

7. Terapkan daya ke unit.

Pengaturan parameter standar disimpan selamapermulaan. Ini lebih lama dari normalnya.

8. Alarm 80 ditampilkan.

9. Tekan [Reset] untuk kembali ke modus operasi.

4.3.2 Inisialisasi Manual

1. Putuskan daya ke unit dan tunggu sampai layarmati.

2. Tekan dan tahan [Status], [Menu Utama], dan [OK]pada waktu bersamaan dan terapkan daya keunit.

Pengaturan parameter standard pabrik dikembalikanselama permulaan. Ini lebih lama dari normalnya.

Inisialisasi manual tidak melakukan reset untuk mengikutiinformasi konverter frekuensi

• 15-00 Jam Pengoperasian

• 15-03 Penyalaan

• 15-04 Kelebihan Suhu

• 15-05 Keleb. Tegangan

Penghubung pengguna VLT® Petunjuk Operasional Drive HVAC

36 MG11AI9B - VLT® merek dagang terdaftar Danfoss

44

Page 41: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

5 Tentang Program Konverter Frekuensi

5.1 Pendahuluan

Konverter frekuensi diprogram untuk fungsi aplikasidengan menggunakan parameter. Parameter diaksesdengan menekan [Menu Cepat] atau [Menu Utama] padaLCP. (Lihat 4 Penghubung pengguna untuk detail denganmenggunakan tombol fungsi LCP.) Parameter juga dapatdiakses melalui PC dengan menggunakan MCT 10 Set-upPerangkat Lunak (lihat 5.6 Program jauh dengan MCT 10Set-up Perangkat Lunak).

Menu cepat bermaksud untuk inisial permulaan (Q2-**Pengaturan Cepat) dan instruksi detail untuk aplikasikonverter frekuensi (Q3-** Pengaturan Fungsi). Instruksisetahap demi setahap disediakan. Instruksi ini mengak-tifkan pengguna untuk menjalankan parameter yangdigunakan untuk memprogram aplikasi di urutan yangbenar. Data yang dimasukkan di parameter dapatmengubah opsi yang tersedia di masukan parameterberikut. Menu cepat menampilkan petunjuk yang mudahdi mengerti yang bertujuan untuk menjalankan sistemdengan baik.

Menu utama mengakses semua parameter dan memung-kinkan aplikasi konverter frekuensi lanjutan.

5.2 Contoh Program

Ini adalah contoh untuk program konverter frekuensi untukaplikasi umum di lloop terbuka dengan menggunakanmenu cepat.

• Prosedur ini memprogram konverter frekuensiuntuk menerima sinyal kontrol analog 0-10 V DCdi input terminal 53

• Konverter frekuensi akan menjawab denganmemberikan output 6-60 Hz untuk proposionalmotor ke sinyal input (0-10V DC =6-60 Hz)

Pilih parameter berikut dengan menggunakan tombolnavigasiuntuk skrol judul dan tekan [OK] setelah masing-masing tindakan.

1. 3-15 Sumber Referensi 1

5-1*

130B

B848

.10

3-15 Reference Resource

[1]] Analog input 53

14.7% 0.00A 1(1)

References

Ilustrasi 5.1 Referensi 3-15 Sumber Referensi 1

2. 3-02 Referensi Minimum. Atur referensi konverterfrekuensi internal minimum ke 0 Hz. (Inimengatur kecepatan konverter frekuensiminimum pada 0 Hz.)

Q3-21

130B

T762

.10

3-02 Minimum Reference

0.000 Hz

14.7% 0.00A 1(1)

Analog Reference

Ilustrasi 5.2 Referensi Analog 3-02 Referensi Minimum

3. 3-03 Referensi Maksimum. Atur konverter frekuensiinternal maksimum ke 60 Hz. (Ini mengaturkecepatan konverter frekuensi maksimum pada60 Hz. Catatan bahwa 50/60 Hz adalah variasiregional.)

Q3-21

130B

T763

.11

3-03 Maximum Reference

50.000 Hz

14.7% 0.00A 1(1)

Analog Reference

Ilustrasi 5.3 Referensi Analog 3-03 Referensi Maksimum

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 37

5 5

Page 42: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

4. 6-10 Terminal 53 Tegangan Rendah. Tetapkanreferensi tegangan eksternal minimum padaTerminal 53 di 0 V. (Hal ini mengatur sinyal inputminimum 0 V.)

Q3-21

130B

T764

.10

6-10 Terminal 53 Low

Voltage

0.00 V

14.7% 0.00A 1(1)

Analog Reference

Ilustrasi 5.4 Referensi Analog 6-10 Terminal 53 Tegangan Rendah

5. 6-11 Terminal 53 Tegangan Tinggi. Atur referensitegangan eksternal maksimum pada Terminal 53di 10V. (Hal ini mengatur sinyal input maksimumdi 10V.)

Q3-21

130B

T765

.10

6-11 Terminal 53 High

Voltage

10.00 V

14.7% 0.00A 1(1)

Analog Reference

Ilustrasi 5.5 Referensi Analog 6-11 Terminal 53 Tegangan Tinggi

6. 6-14 Terminal 53 Ref Rdh/Nilai Ump-Balik. Aturreferensikecepatan minimum pada Terminal 53 di6 Hz. (Ini memberitahukan konverter frekuensibahwa tegangan minimum diterima di Terminal53 (0 V) sama dengan output 6 Hz.)

130B

T773

.11

Q3-21

14.7 % 0.00 A 1(1)

Analog Reference

6 - 14 Terminal 53 Low Ref./Feedb. Value

000020.000

Ilustrasi 5.6 Referensi Analog 6-14 Terminal 53 Ref Rdh/Nilai Ump-Balik

7. 6-15 Terminal 53 Ref Tinggi/Nilai Ump-Balik. Aturreferensi kecepatan maksimum pada Terminal 53di 60 Hz. (Ini memberitahukan konverter frekuensibahwa tegangan maksimum yang diterima padaTerminal 53 (10 V) sama dengan output 60 Hz.)

130B

T774

.11

Q3-21

14.7 % 0.00 A 1(1)

Analog Reference

6 - 15 Terminal 53 High Ref./Feedb. Value

50.000

Ilustrasi 5.7 Referensi Analog 6-15 Terminal 53 Ref Tinggi/NilaiUmp-Balik

Dengan perangkat eksternal yang disediakan, sinyal kontrol0-10V sinyal kontrol tersambung ke terminal 53 konverterfrekuensi, sistem sekarang telah siap untuk beroperasi.Catatan bahwa skrol bar pada bagian kanan di ilustrasiterakhir dari layar berada di bagian bawah, yangmenunjukkan prosedur telah selesai.

Ilustrasi 5.8 memperlihatkan sambungan kabel yangdigunakan untuk mengaktifkan pengaturan ini.

53

55

6-1* +

A53

U - I

130B

B482

.10

0-10V

Ilustrasi 5.8 Contoh Kabel untuk Sinyal Kontrol 0-10 VPenyediaan Perangkat Eksternal (Konverter Frekuensi Bagian Kiri,Perangkat Eksternal Bagian Kanan)

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

38 MG11AI9B - VLT® merek dagang terdaftar Danfoss

55

Page 43: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

5.3 Contoh Program Terminal Kontrol

Terminal kontrol dapat diprogram.

• Setiap terminal mempunyai fungsi yang khususyang mampu melakukan pengoperasian

• Parameter yang berhubungan dengan terminalmengaktifkan fungsi

Lihat Tabel 2.4 untuk nomor parameter terminal kontrolkontrol dan pengaturan standar. (Pengaturan standardapat berubah berdasarkan pilihan di 0-03 PengaturanWilayah.)

Contoh berikut memperlihatkan akses Terminal 18 untukmelihat pengaturan standar.

1. Tekan [Menu Utama] dua kali, skrol ke 5-** DigitalMasuk/Keluar dan tekan [OK].

130B

T768

.10

2-** Brakes

3-** Reference / Ramps

4-** Limits / Warnings

5-** Digital In/Out

14.6% 0.00A 1(1)

Main Menu

Ilustrasi 5.9 6-15 Terminal 53 Ref Tinggi/Nilai Ump-Balik

2. Skrol ke grup parameter 5-1* Input Digital dantekan [OK].

130B

T769

.10

5-0* Digital I/O mode

5-1* Digital Inputs

5-4* Relays

5-5* Pulse Input

14.7% 0.00A 1(1)

Digital In/Out 5-**

Ilustrasi 5.10 Digital In/Out

3. Skrol ke 5-10 Terminal 18 Input Digital. Tekan [OK]untuk mengakses pilihan fungsi. Pengaturanstandar Mulai terlihat.

5-1*

130B

T770

.10

5-10 Terminal 18 Digital

Input

[8]] Start

14.7% 0.00A 1(1)

Digital Inputs

Ilustrasi 5.11 Masukan digital

5.4 Pengaturan Parameter StandarInternasional/Amerika Utara

Pengaturan 0-03 Pengaturan Wilayah ke [0] Internasionalatau [1] Amerika Utara mengubah pengaturan standaruntuk beberapa parameter. Tabel 5.1 mendaftar parameteryang berhubungan.

Parameter Angka ParameterStandar Interna-

sional

Angka ParameterStandar Amerika

Utara0-03 PengaturanWilayah

Internasional Amerika Utara

1-20 Daya Motor[kW]

Lihat Catatan 1 Lihat Catatan 1

1-21 Daya motor[HP]

Lihat Catatan 2 Lihat Catatan 2

1-22 TeganganMotor

230 V/400 V/575 V 208 V/460 V/575 V

1-23 FrekuensiMotor

50 Hz 60 Hz

3-03 ReferensiMaksimum

50 Hz 60 Hz

3-04 FungsiReferensi

Jumlah Eksternal/Preset

4-13 Batasan TinggiKecepatan Motor[RPM]Lihat Catatan 3 dan5

1500 PM 1800 RPM

4-14 Batasan TinggiKecepatan Motor[Hz]Lihat Catatan 4

50 Hz 60 Hz

4-19 FrekuensiOutput Maks.

100 Hz 120 Hz

4-53 KecepatanPeringatan Tinggi

1500 RPM 1800 RPM

5-12 Terminal 27Input Digital

Coast terbalik Interlock eksternal

5-40 Relai Fungsi Alarm Tiada alarm

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 39

5 5

Page 44: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Parameter Angka ParameterStandar Interna-

sional

Angka ParameterStandar Amerika

Utara6-15 Terminal 53Ref Tinggi/NilaiUmp-Balik

50 60

6-50 Terminal 42Output

Kecepatan 0-Batas Ti Kecepatan 4-20 mA

14-20 Mode Reset Reset manual Reset auto Tak T'bts

Tabel 5.1 Pengaturan Parameter Standar Internasional/Amerika Utara

Catatan 1: 1-20 Daya Motor [kW] hanya terlihat pada saat0-03 Pengaturan Wilayah diatur ke Internasional [0].Catatan 2: 1-21 Daya motor [HP] , hanya terlihat pada saat0-03 Pengaturan Wilayah diatur ke Amerika Utara [1].Catatan 3: Parameter ini hanya terlihat pada saat 0-02 UnitKecepatan Motor diatur ke RPM [0].Catatan 4: Parameter ini hanya terlihat pada saat 0-02 UnitKecepatan Motor diatur ke Hz [1].Catatan 5: Nilai standar tergantung pada jumlah kutub motor. Untuk4 kutub motor, nilai standar internasional adalah 1500 RPM danuntuk 2 kutub motor adalah 3000 RPM. Nilai untuk Amerika Utaraadalah masing-masing 1800 dan 3600 RPM.

Perubahan yang dibuat ke pengaturan standar disimpandan tersedia untuk melihat menu cepat dengan programyang dimasukkan ke dalam parameter.

1. Tekan [Menu cepat].

2. Skrol ke Q5 Merubah Yang Dibuat dan tekan[OK].

3. Pilih Q5-2 Sejak Pengaturan Pabrik untuk melihatsemua perubahan program atau Q5-1 10Perubahan Terakhir untuk baru-baru ini.

Q5

130B

B850

.10

Q5-1 Last 10 Changes

Q5-2 Since Factory Setti...

25.9% 0.00A 1(1)

Changes Made

Ilustrasi 5.12 Perubahan yg Dibuat

5.4.1 Periksa Data Parameter

1. Tekan [Menu cepat].

2. Skrol ke Q5 Merubah Yang Dibuat dan tekan [OK].

130B

P089

.10

Q1 My Personal Menu

Q2 Quick Setup

Q3 Function Setups

Q5 Changes Made

25.9% 0.00A 1(1)

Quick Menus

Ilustrasi 5.13 Q5 Perubahan yang Dibuat

3. Pilih Q5-2 Sejak Pengaturan Pabrik untuk melihatsemua perubahan program atau Q5-1 10Perubahan Terakhir untuk baru-baru ini.

5.5 Struktur Menu Parameter

Penetapan programyang benar untuk aplikasi seringmemerlukan fungsi pengaturan di beberapa parameteryang berhubungan. Pengaturan parameter inimenyediakan konverter frekuensi dengan sistem detail,guna mengoperasikannya secara benar. Sistem yang detailtermasuk jenis sinyal input dan output, terminal program,jangkauan sinyal maksimum dan minimum, tampilancustom, memulai otomatis kembali, dan fitur lainnya.

• Lihat layar LCP untuk menampilkan programparameter yang detail dan opsi pengaturan

• Tekan [Info] lokasi menu untuk menampilkandetail tambahan untuk fungsi tersebut

• Tekan dan tahan [Menu Utama] untuk masukkannomor parameter untuk akses langsung keparameter tersebut

• Detail untuk pengaturan aplikasi umum tersediadi 6 Contoh Pengaturan Aplikasi.

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

40 MG11AI9B - VLT® merek dagang terdaftar Danfoss

55

Page 45: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

5.5.1 Struktur Menu Cepat

Q3-

1 Pe

ngat

uran

Um

um0-

24 T

ampi

lan

Bar

is 3

Bes

ar1-

00 M

ode

Konf

igur

asi

Q3-

31 Z

ona

Tung

gal E

kst.

Set

Poin

t20

-70

Jeni

s Lo

op T

ertu

tup

Q3-

10 L

anju

tan

Pen

gatu

ran

Mot

or0-

37 T

eks

Tam

pila

n 1

20-1

2 Re

fere

nsi/U

nit

Um

pan

Bal

ik1-

00 M

ode

Konf

igur

asi

20-7

1 Pe

rfor

ma

PID

1-90

Pro

teks

i pd

ter

mal

mot

or0-

38 T

eks

Tam

pila

n 2

20-1

3 Re

fere

nsi/U

mpa

n b

alik

Min

imum

20-1

2 Re

fere

nsi/U

nit

Um

pan

Bal

ik20

-72

Peru

b. O

utpu

t PI

D

1-93

Sum

ber

Ther

mis

tor

0-39

Tek

s Ta

mpi

lan

320

-14

Refe

rens

i/Um

pan

Bal

ikM

aksi

mum

20-1

3 Re

fere

nsi/U

mpa

n b

alik

Min

imum

20-7

3 Le

vel U

mpa

n B

alik

Min

.

1-29

Pen

yesu

aian

Mot

or O

tom

atis

(AM

A)

Q3-

2 Pe

ngat

uran

Loo

p Te

rbuk

a6-

22 T

erm

inal

54

Aru

s Re

ndah

20-1

4 Re

fere

nsi/U

mpa

n B

alik

Mak

sim

um20

-74

Leve

l Um

pan

Bal

ik M

aks.

14-0

1 Fr

ekue

nsi s

witc

hing

Q3-

20 R

efer

ensi

Dig

ital

6-24

Ter

min

al 5

4 Re

f Rd

h/N

ilai

Um

p-Ba

lik6-

10 T

erm

inal

53

Tega

ngan

Ren

dah

20-7

9 Tu

ning

Oto

mat

is P

ID

4-53

Kec

epat

an P

erin

gata

n T

ingg

i3-

02 R

efer

ensi

Min

imum

6-25

Ter

min

al 5

4 Re

f Ti

nggi

/Nila

iU

mp-

Balik

6-11

Ter

min

al 5

3 Te

gang

an T

ingg

iQ

3-32

Mul

tizon

a /

Lanj

ut

Q3-

11 K

elua

ran

Ana

log

3-03

Ref

eren

si M

aksi

mum

6-26

Ter

min

al 5

4 Te

tapa

n W

aktu

Filte

r6-

12 T

erm

inal

53

Aru

s Re

ndah

1-00

Mod

e Ko

nfig

uras

i

6-50

Ter

min

al 4

2 O

utpu

t3-

10 R

efer

ensi

pre

set

6-27

Liv

e Ze

ro T

erm

inal

54

6-13

Ter

min

al 5

4 A

rus

Ting

gi3-

15 S

umbe

r 1

Refe

rens

i

6-51

Ter

min

al 4

2 Sk

ala

Out

put

Min

.5-

13 T

erm

inal

29

Inpu

t D

igita

l6-

00 W

aktu

Istir

ahat

Aru

s/Te

g. t

'lalu

rdh

6-14

Ter

min

al 5

3 Re

f Rd

h/N

ilai U

mp-

Balik

3-16

Sum

ber

2 Re

fere

nsi

6-52

Ter

min

al 4

2 Sk

ala

Out

put

Mak

s.5-

14 T

erm

inal

32

Inpu

t D

igita

l6-

01 F

ungs

i Ist

iraha

t ar

us/t

eg. t

'lalu

rdh

6-15

Ter

min

al 5

3 Re

f Ti

nggi

/Nila

i Um

p-Ba

lik20

-00

Sum

ber

Um

pan

Bal

ik 1

Q3-

12 P

enga

tura

n J

am5-

15 T

erm

inal

33

Inpu

t D

igita

l20

-21

Setp

oint

16-

22 T

erm

inal

54

Aru

s Re

ndah

20-0

1 Ko

nver

si U

mpa

n B

alik

1

0-70

Tan

ggal

dan

Wak

tuQ

3-21

Ref

eren

si A

nalo

g20

-81

Kont

rol N

orm

al/T

erba

lik P

ID6-

24 T

erm

inal

54

Ref

Rdh/

Nila

i Um

p-Ba

lik20

-02

Uni

t Su

mbe

r U

mp.

Bal

ik 1

0-71

For

mat

Tgl

.3-

02 R

efer

ensi

Min

imum

20-8

2 Ke

cep.

Sta

rt P

ID [R

PM]

6-25

Ter

min

al 5

4 Re

f Ti

nggi

/Nila

i Um

p-Ba

lik20

-03

Sum

ber

Um

pan

Bal

ik 2

0-72

For

mat

Wak

tu3-

03 R

efer

ensi

Mak

sim

um20

-83

Kece

p. S

tart

PID

[Hz]

6-26

Ter

min

al 5

4 Te

tapa

n W

aktu

Filt

er20

-04

Konv

ersi

Um

pan

Bal

ik 2

0-74

DST

/Sum

mer

time

6-10

Ter

min

al 5

3 Te

gang

an R

enda

h20

-93

Pero

leha

n P

ropo

rsi.

PID

6-27

Liv

e Ze

ro T

erm

inal

54

20-0

5 U

nit

Sum

ber

Um

p. B

alik

2

0-76

DST

/Sta

rt S

umm

ertim

e6-

11 T

erm

inal

53

Tega

ngan

Tin

ggi

20-9

4 W

aktu

Inte

gral

PID

6-00

Wak

tu Is

tirah

at A

rus/

Teg.

t'la

lurd

h20

-06

Sum

ber

Um

pan

Bal

ik 3

0-77

DST

/Akh

ir S

umm

ertim

e6-

12 T

erm

inal

53

Aru

s Re

ndah

20-7

0 Je

nis

Loop

Ter

tutu

p6-

01 F

ungs

i Ist

iraha

t ar

us/t

eg. t

'lalu

rdh

20-0

7 Ko

nver

si U

mpa

n B

alik

3

Q3-

13 P

enga

tura

n T

ampi

lan

6-13

Ter

min

al 5

4 A

rus

Ting

gi20

-71

Perf

orm

a PI

D20

-81

Kont

rol N

orm

al/T

erba

lik P

ID20

-08

Uni

t Su

mbe

r U

mp.

Bal

ik 3

0-20

Tam

pila

n B

aris

1,1

Kec

il6-

14 T

erm

inal

53

Ref

Rdh/

Nila

iU

mp-

Balik

20-7

2 Pe

rub.

Out

put

PID

20-8

2 Ke

cep.

Sta

rt P

ID [R

PM]

20-1

2 Re

fere

nsi/U

nit

Um

pan

Bal

ik

0-21

Tam

pila

n B

aris

1,2

Kec

il6-

15 T

erm

inal

53

Ref

Ting

gi/N

ilai

Um

p-Ba

lik20

-73

Leve

l Um

pan

Bal

ik M

in.

20-8

3 Ke

cep.

Sta

rt P

ID [H

z]20

-13

Refe

rens

i/Um

pan

bal

ik M

inim

um

0-22

Tam

pila

n B

aris

1,3

Kec

ilQ

3-3

Peng

atur

an L

oop

Tert

utup

20-7

4 Le

vel U

mpa

n B

alik

Mak

s.20

-93

Pero

leha

n P

ropo

rsi.

PID

20-1

4 Re

fere

nsi/U

mpa

n B

alik

Mak

sim

um

0-23

Tam

pila

n B

aris

2 B

esar

Q3-

30 Z

ona

Tung

gal I

nt. S

et P

oint

20-7

9 Tu

ning

Oto

mat

is P

ID20

-94

Wak

tu In

tegr

al P

ID6-

10 T

erm

inal

53

Tega

ngan

Ren

dah

Tabe

l 5.2

Str

uktu

r M

enu

Cep

at

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 41

5 5

Page 46: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

6-11

Ter

min

al 5

3 Te

gang

an T

ingg

i20

-21

Setp

oint

122

-22

Det

eksi

Kec

ep. R

enda

h22

-21

Det

eksi

Day

a Re

ndah

22-8

7 Te

k. p

d K

ecep

. Tia

da A

liran

6-12

Ter

min

al 5

3 A

rus

Rend

ah20

-22

Setp

oint

222

-23

Fung

si T

iada

Alir

an22

-22

Det

eksi

Kec

ep. R

enda

h22

-88

Teka

nan

pd

Kec

ep. T

eruk

ur

6-13

Ter

min

al 5

4 A

rus

Ting

gi20

-81

Kont

rol N

orm

al/T

erba

lik P

ID22

-24

Tund

a Ti

ada

Alira

n22

-23

Fung

si T

iada

Alir

an22

-89

Alir

an p

d T

itik

Ranc

anga

n

6-14

Ter

min

al 5

3 Re

f Rd

h/N

ilai U

mp-

Balik

20-8

2 Ke

cep.

Sta

rt P

ID [R

PM]

22-4

0 Ru

n T

ime

Min

imum

22-2

4 Tu

nda

Tiad

a A

liran

22-9

0 A

liran

pd

Kec

ep. T

eruk

ur

6-15

Ter

min

al 5

3 Re

f Ti

nggi

/Nila

iU

mp-

Balik

20-8

3 Ke

cep.

Sta

rt P

ID [H

z]22

-41

Wak

tu T

idur

Min

imum

22-4

0 Ru

n T

ime

Min

imum

1-03

Kar

akte

ristik

Tor

si

6-16

Tet

apan

Wak

tu F

ilter

Ter

min

al 5

320

-93

Pero

leha

n P

ropo

rsi.

PID

22-4

2 Ke

cep.

Wak

e-U

p [R

PM]

22-4

1 W

aktu

Tid

ur M

inim

um1-

73 S

tart

Mel

ayan

g

6-17

Liv

e Ze

ro T

erm

inal

53

20-9

4 W

aktu

Inte

gral

PID

22-4

3 Ke

cep.

Wak

e-U

p [H

z]22

-42

Kece

p. W

ake-

Up

[RPM

]Q

3-42

Fun

gsi K

ompr

esor

6-20

Ter

min

al 5

4 Te

gang

an R

enda

h20

-70

Jeni

s Lo

op T

ertu

tup

22-4

4 Se

lisih

Ref

./FB

Wak

e-U

p22

-43

Kece

p. W

ake-

Up

[Hz]

1-03

Kar

akte

ristik

Tor

si

6-21

Ter

min

al 5

4 Te

gang

an T

ingg

i20

-71

Perf

orm

a PI

D22

-45

Boos

t Se

tpoi

nt22

-44

Selis

ih R

ef./F

B W

ake-

Up

1-71

Pen

unda

an s

tart

6-22

Ter

min

al 5

4 A

rus

Rend

ah20

-72

Peru

b. O

utpu

t PI

D22

-46

Wak

tu B

oost

Mak

sim

um22

-45

Boos

t Se

tpoi

nt22

-75

Perli

nd. S

iklu

s Pe

ndek

6-23

Ter

min

al 5

4 A

rus

Ting

gi20

-73

Leve

l Um

pan

Bal

ik M

in.

2-10

Fun

gsi B

rake

22-4

6 W

aktu

Boo

st M

aksi

mum

22-7

6 In

terv

al a

ntar

a St

art

6-24

Ter

min

al 5

4 Re

f Rd

h/N

ilai U

mp-

Balik

20-7

4 Le

vel U

mpa

n B

alik

Mak

s.2-

16 A

rus

Mak

s. re

m A

C22

-26

Fung

si P

ompa

Ker

ing

22-7

7 Ru

n T

ime

Min

imum

6-25

Ter

min

al 5

4 Re

f Ti

nggi

/Nila

iU

mp-

Balik

20-7

9 Tu

ning

Oto

mat

is P

ID2-

17 P

engo

ntro

l teg

anga

n b

erle

bih

22-2

7 Tu

nda

Pom

pa K

erin

g5-

01 M

ode

Term

inal

27

6-26

Ter

min

al 5

4 Te

tapa

n W

aktu

Filt

erQ

3-4

Peng

atur

an A

plik

asi

1-73

Sta

rt M

elay

ang

22-8

0 Ko

mpe

nsas

i Alir

an5-

02 T

erm

inal

29

Mod

e

6-27

Liv

e Ze

ro T

erm

inal

54

Q3-

40 F

ungs

i Kip

as1-

71 P

enun

daan

sta

rt22

-81

Perk

iraan

Kur

va L

inea

r-Ku

adra

t5-

12 T

erm

inal

27

Inpu

t D

igita

l

6-00

Wak

tu Is

tirah

at A

rus/

Teg.

t'la

lurd

h22

-60

Fung

si B

elt

Putu

s1-

80 F

ungs

i saa

t St

op22

-82

Perh

itung

an T

itik

Kerja

5-13

Ter

min

al 2

9 In

put

Dig

ital

6-01

Fun

gsi I

stira

hat

arus

/teg

. t'la

lurd

h22

-61

Tors

i Bel

t Pu

tus

2-00

Aru

s Pe

naha

n D

C/Pr

apan

as22

-83

Kece

p. p

d T

iada

Alir

an [R

PM]

5-40

Rel

ai F

ungs

i

4-56

Per

inga

tan

Um

pan

Bal

ik R

enda

h22

-62

Tund

a Be

lt P

utus

4-10

Ara

h K

ecep

atan

Mot

or22

-84

Kece

p. p

d T

iada

Alir

an [H

z]1-

73 S

tart

Mel

ayan

g

4-57

Per

inga

tan

Um

pan

Bal

ik T

ingg

i4-

64 P

'atu

ran

Pin

tas

Sem

i-Aut

oQ

3-41

Fun

gsi P

ompa

22-8

5 Ke

cep.

pd

Titi

k Ra

nc. [

RPM

]1-

86 K

ecep

atan

Trip

Ren

dah

[RPM

]

20-2

0 Fu

ngsi

Um

pan

Bal

ik1-

03 K

arak

teris

tik T

orsi

22-2

0 Pe

ngat

uran

Aut

o D

aya

Rend

ah22

-86

Kece

p. p

d T

itik

Ranc

. [H

z]1-

87 K

ecep

atan

Trip

Ren

dah

[Hz]

Tabe

l 5.3

Str

uktu

r M

enu

Cep

at

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

42 MG11AI9B - VLT® merek dagang terdaftar Danfoss

55

Page 47: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

5.5.

2St

rukt

ur M

enu

Uta

ma

0-**

Ope

rasi

/Tam

pila

n0-

0*Pe

ngat

uran

Das

ar0-

01Ba

hasa

0-02

Uni

t Ke

cepa

tan

Mot

or0-

03Pe

ngat

uran

Wila

yah

0-04

Stat

us O

pera

si s

aat

Day

a hi

dup

0-05

Uni

t M

odus

Lok

al0-

1*O

pera

si P

enga

tura

n0-

10Pe

ngat

uran

akt

if0-

11Pe

ngat

uran

Pem

rogr

aman

0-12

Peng

atur

an in

i Ber

hubu

ngan

ke

0-13

Pem

baca

an: P

enga

tura

n t

erhu

bung

0-14

Pem

baca

an: P

'atu

ran

Pro

g. /

Sal

uran

0-2*

Tam

pila

n L

CP0-

20Ta

mpi

lan

Bar

is 1

,1 K

ecil

0-21

Tam

pila

n B

aris

1,2

Kec

il0-

22Ta

mpi

lan

Bar

is 1

,3 K

ecil

0-23

Tam

pila

n B

aris

2 B

esar

0-24

Tam

pila

n B

aris

3 B

esar

0-25

Men

u P

ribad

iku

0-3*

Pbac

a. C

ust.

LCP

0-30

Uni

t Pe

mba

caan

Cus

tom

0-31

Nila

i Min

. Pem

baca

an C

usto

m0-

32N

ilai M

aks.

Pem

baca

an C

usto

m0-

37Te

ks T

ampi

lan

10-

38Te

ks T

ampi

lan

20-

39Te

ks T

ampi

lan

30-

4*To

mbo

l LCP

0-40

[Man

ual]

tom

bol p

d L

CP0-

41[O

ff] t

ombo

l pd

LCP

0-42

(Nya

la O

tom

atis

) To

mbo

l pad

a LC

P0-

43[R

eset

] to

mbo

l pd

LCP

0-44

Tom

bol [

Off/

Rese

t] p

ada

LCP

0-45

Kunc

i [By

pass

Driv

e] p

ada

LCP

0-5*

Copy

/sim

pan

0-50

Copy

LCP

0-51

Copy

Pen

gatu

ran

0-6*

Kata

San

di0-

60Kt

. san

di M

enu

Uta

ma

0-61

Aks

es k

e M

enu

Uta

ma

tanp

a kt

. San

di0-

65Sa

ndi M

enu

Prib

adi

0-66

Aks

es k

e M

enu

Prib

adi t

anpa

San

di0-

67A

kses

Kat

a Sa

ndi B

us0-

7*Pe

ngat

uran

Jam

0-70

Tang

gal d

an W

aktu

0-71

Form

at T

gl.

0-72

Form

at W

aktu

0-74

DST

/Sum

mer

time

0-76

DST

/Sta

rt S

umm

ertim

e0-

77D

ST/A

khir

Sum

mer

time

0-79

Mas

alah

Jam

0-81

Har

i Ker

ja0-

82H

ari K

erja

Tam

baha

n0-

83Bu

kan

Har

i Ker

ja T

amba

han

0-89

Pem

baca

an T

gl. d

an W

aktu

1-**

Beba

n d

an M

otor

1-0*

Peng

atur

an U

mum

1-00

Mod

e Ko

nfig

uras

i1-

03Ka

rakt

eris

tik T

orsi

1-06

Sear

ah J

arum

Jam

1-1*

Pem

iliha

n M

otor

1-10

Kons

truk

si M

otor

1-1*

VVC+

PM

1-14

Dam

ping

Gai

n1-

15Lo

w S

peed

Filt

er T

ime

Cons

t.1-

16H

igh

Spe

ed F

ilter

Tim

e Co

nst.

1-17

Volta

ge fi

lter

time

cons

t.1-

2*D

ata

Mot

or1-

20D

aya

Mot

or [k

W]

1-21

Day

a m

otor

[HP]

1-22

Tega

ngan

Mot

or1-

23Fr

ekue

nsi M

otor

1-24

Aru

s M

otor

1-25

Kece

pata

n N

omin

al M

otor

1-26

Tors

i Ter

ukur

Kon

trol

Mot

or1-

28Pe

riksa

Rot

asi M

otor

1-29

Peny

esua

ian

Mot

or O

tom

atis

(AM

A)

1-3*

L'ju

tan

Dat

a M

oto

1-30

Resi

stan

si S

tato

r (R

s)1-

31Re

sist

ansi

Rot

or (R

r)1-

35Re

akta

nsi U

tam

a (X

h)1-

36Re

sist

ansi

Ker

ugia

n B

esi (

Rfe)

1-37

Indu

ktan

si s

umbu

-d (L

d)1-

39Ku

tub

Mot

or1-

40EM

F Ba

lik p

ada

1000

RPM

1-46

Posi

tion

Det

ectio

n G

ain

1-5*

T. T

'gan

t. b

eban

1-50

Mag

netis

asi m

otor

pad

a Ke

cepa

tan

Nol

1-51

Mgn

et. N

orm

. Kec

. Min

. [RP

M]

1-52

Mag

net.

Nor

m. K

ec. M

in. [

Hz]

1-58

Flys

tart

Tes

t Pu

lses

Cur

rent

1-59

Flys

tart

Tes

t Pu

lses

Fre

quen

cy1-

6*T'

gant

Bbn

P'a

tur

1-60

Kom

pens

asi B

eban

Kec

epat

an R

enda

h1-

61Ko

mpe

nsas

i Beb

an K

ecep

atan

Tin

ggi

1-62

Kom

pens

asi S

lip1-

63Te

tapa

n W

aktu

Kom

pens

asi S

lip1-

64Pe

reda

man

Res

onan

si1-

65Te

tapa

n W

aktu

per

edam

an r

eson

ansi

1-66

Aru

s m

in. p

ada

Kece

pata

n R

enda

h1-

7*Pe

nyes

uaia

n S

tart

1-70

PM S

tart

Mod

e1-

71Pe

nund

aan

sta

rt1-

72Fu

ngsi

sta

rt1-

73St

art

Mel

ayan

g1-

77Ke

cepa

tan

Sta

rt M

ax C

ompr

esso

r[R

PM]

1-78

Kece

pata

n S

tart

Max

Com

pres

sor

[Hz]

1-79

Wak

tu S

tart

Max

Kom

pres

sor

hing

gatr

ip1-

8*St

op p

enye

suai

an1-

80Fu

ngsi

saa

t St

op1-

81Fu

ngsi

dar

i kcp

tn. m

in. p

d s

top

[RPM

]1-

82Ke

c. M

in u

tk F

ungs

i B'h

enti

[Hz]

1-86

Kece

pata

n T

rip R

enda

h [R

PM]

1-87

Kece

pata

n T

rip R

enda

h [H

z]1-

9*Su

hu M

otor

1-90

Prot

eksi

pd

ter

mal

mot

or1-

91Ki

pas

Ekst

erna

l Mot

or1-

93Su

mbe

r Th

erm

isto

r2-

**Br

ake

2-0*

Brak

e D

C2-

00A

rus

Pena

han

DC/

Prap

anas

2-01

Aru

s Br

ake

DC

2-02

Wak

tu P

enge

rem

an D

C2-

03Ke

cepa

tan

Pen

yela

an R

em D

C [R

PM]

2-04

Kece

pata

n P

enye

laan

Rem

DC

[Hz]

2-06

Park

ing

Cur

rent

2-07

Park

ing

Tim

e2-

1*Fu

ngsi

Ene

rgi B

rake

2-10

Fung

si B

rake

2-11

Taha

nan

Bra

ke2-

12Ba

tas

Day

a Br

ake

(kW

)2-

13Pe

man

taua

n D

aya

Brak

e2-

15Ce

k Br

ake

2-16

Aru

s M

aks.

rem

AC

2-17

Peng

ontr

ol t

egan

gan

ber

lebi

h3-

**Re

fere

nsi /

Ram

p3-

0*Ba

tas

Refe

rens

i3-

02Re

fere

nsi M

inim

um3-

03Re

fere

nsi M

aksi

mum

3-04

Fung

si R

efer

ensi

3-1*

Refe

rens

i3-

10Re

fere

nsi p

rese

t3-

11Ke

cepa

tan

Jog

[Hz]

3-13

Situ

s Re

fere

nsi

3-14

Refe

rens

i rel

atif

pres

et3-

15Su

mbe

r 1

Refe

rens

i3-

16Su

mbe

r 2

Refe

rens

i3-

17Su

mbe

r 3

Refe

rens

i3-

19Ke

cepa

tan

Jog

[RPM

]3-

4*Ra

mp

13-

41W

aktu

tan

jaka

n R

amp

13-

42W

aktu

Tur

unan

Ram

p 1

3-5*

Ram

p 2

3-51

Wak

tu t

anja

kan

Ram

p 2

3-52

Wak

tu T

urun

an R

amp

23-

8*Ra

mp

lain

3-80

Wak

tu R

amp

Jog

3-81

Wak

tu R

amp

Sto

p C

epat

3-82

Wak

tu S

tart

3-9*

Pot.m

eter

Dig

ital

3-90

Uku

ran

ste

p3-

91Ra

mp

Tim

e3-

92Pe

mul

ihan

Day

a3-

93Ba

tas

Mak

sim

um3-

94Ba

tas

Min

imum

3-95

Penu

ndaa

n T

anja

kan

4-**

Bata

s /

Perin

gata

n4-

1*Ba

tas

Mot

or4-

10A

rah

Kec

epat

an M

otor

4-11

Bata

san

Ren

dah

Kec

epat

an M

otor

[RPM

]

4-12

Bata

san

Ren

dah

Kec

epat

an M

otor

[Hz]

4-13

Bata

san

Tin

ggi K

ecep

atan

Mot

or [R

PM]

4-14

Bata

san

Tin

ggi K

ecep

atan

Mot

or [H

z]4-

16M

ode

Mot

or B

atas

an T

orsi

4-17

Mod

e ge

nera

tor

Bata

san

Tor

si4-

18Ba

tas

Aru

s4-

19Fr

ekue

nsi O

utpu

t M

aks.

4-5*

Sesu

ai P

erin

gata

n4-

50A

rus

Perin

gata

n L

emah

4-51

Aru

s Pe

ringa

tan

Tin

ggi

4-52

Kece

pata

n P

erin

gata

n R

enda

h4-

53Ke

cepa

tan

Per

inga

tan

Tin

ggi

4-54

Perin

gata

n R

efer

ensi

Ren

dah

4-55

Perin

gata

n R

efer

ensi

Tin

ggi

4-56

Perin

gata

n U

mpa

n B

alik

Ren

dah

4-57

Perin

gata

n U

mpa

n B

alik

Tin

ggi

4-58

Fung

si F

asa

Mot

or H

ilang

4-6*

Kece

pata

n p

inta

s4-

60Ke

cepa

tan

Pin

tas

Dar

i [RP

M]

4-61

Kece

pata

n P

inta

s D

ari [

Hz]

4-62

Kece

pata

n P

inta

s ke

[RPM

]4-

63Ke

cepa

tan

Pin

tas

Ke [H

z]4-

64P'

atur

an P

inta

s Se

mi-A

uto

5-**

Dig

ital I

n/O

ut5-

0*M

ode

I/O d

igita

l5-

00M

ode

I/O D

igita

l5-

01M

ode

Term

inal

27

5-02

Term

inal

29

Mod

e5-

1*D

igita

l Inp

ut5-

10Te

rmin

al 1

8 In

put

Dig

ital

5-11

Term

inal

19

Inpu

t D

igita

l5-

12Te

rmin

al 2

7 In

put

Dig

ital

5-13

Term

inal

29

Inpu

t D

igita

l5-

14Te

rmin

al 3

2 In

put

Dig

ital

5-15

Term

inal

33

Inpu

t D

igita

l5-

16In

put

Dig

ital T

erm

inal

X30

/25-

17In

put

Dig

ital T

erm

inal

X30

/35-

18In

put

Dig

ital T

erm

inal

X30

/45-

19Te

rmin

al 3

7 Sa

fe S

top

5-3*

Dig

ital O

utpu

t5-

30Te

rmin

al 2

7 di

gita

l out

put

5-31

Term

inal

29

Dig

ital o

utpu

t5-

32Te

rm X

30/6

Dig

i Out

(MCB

101

)5-

33Te

rm X

30/7

Dig

i Out

(MCB

101

)5-

4*Re

lai

5-40

Rela

i Fun

gsi

5-41

Penu

ndaa

n O

n (H

idup

), Re

lai

5-42

Penu

ndaa

n O

ff (m

ati),

Rel

ai5-

5*In

put

Puls

a5-

50Te

rm. 2

9 Fr

ekue

nsi R

enda

h5-

51Te

rm. 2

9 Fr

ekue

nsi T

ingg

i5-

52Te

rm. 2

9 Re

f Re

ndah

/Nila

i Um

p-ba

lik5-

53Te

rm. 2

9 Re

f Ti

nggi

/Nila

i Um

p-ba

lik5-

54Te

tapa

n W

aktu

Filt

er P

ulsa

#29

5-55

Term

. 33

Frek

uens

i Ren

dah

5-56

Term

. 33

Frek

uens

i Tin

ggi

5-57

Term

. 33

Ref

Rend

ah/N

ilai U

mp-

balik

5-58

Term

. 33

Ref

Ting

gi/N

ilai U

mp-

balik

5-59

Teta

pan

Wak

tu F

ilter

Pul

sa #

33

5-6*

Out

put

Puls

a5-

60Va

riabe

l Out

put

Puls

a Te

rmin

al 2

75-

62Fr

ek. M

aks.

Kel

uara

n P

ulsa

#27

5-63

Varia

bel O

utpu

t Pu

lsa

Term

inal

29

5-65

Frek

. Mak

s. K

elua

ran

Pul

sa #

295-

66Va

r. O

utpu

t Pu

lsa

Di T

erm

. X30

/65-

68Fr

ek. M

aks.

Kel

uara

n P

ulsa

#X3

0/6

5-8*

I/O O

ptio

ns5-

80A

HF

Cap

Rec

onne

ct D

elay

5-9*

Bus

Terk

ontr

ol5-

90Ko

ntro

l Bus

Rel

ai &

Dig

ital

5-93

Kont

rol B

us P

ulsa

Kel

uar

#27

5-94

Pra-

Sete

l Tim

eout

Pul

sa K

elua

r #2

75-

95Ko

ntro

l Bus

Pul

sa K

elua

r #2

95-

96Pr

a-Se

tel T

imeo

ut P

ulsa

Kel

uar

#29

5-97

Kont

rol B

us #

X30/

6 Pu

lsa

Out

5-98

Pras

etel

Istir

ahat

#X3

0/6

Puls

a O

ut6-

**A

nalo

g In

/Out

6-0*

Mod

e I/O

Ana

log

6-00

Wak

tu Is

tirah

at A

rus/

Teg.

t'la

lu r

dh6-

01Fu

ngsi

Istir

ahat

aru

s/te

g. t

'lalu

rdh

6-02

Fung

si T

imeo

ut L

ive

Zero

Mod

eKe

baka

ran

6-1*

Inpu

t A

nalo

g 5

36-

10Te

rmin

al 5

3 Te

gang

an R

enda

h6-

11Te

rmin

al 5

3 Te

gang

an T

ingg

i6-

12Te

rmin

al 5

3 A

rus

Rend

ah6-

13Te

rmin

al 5

4 A

rus

Ting

gi6-

14Te

rmin

al 5

3 Re

f Rd

h/N

ilai U

mp-

Balik

6-15

Term

inal

53

Ref

Ting

gi/N

ilai U

mp-

Balik

6-16

Teta

pan

Wak

tu F

ilter

Ter

min

al 5

36-

17Li

ve Z

ero

Ter

min

al 5

36-

2*In

put

Ana

log

54

6-20

Term

inal

54

Tega

ngan

Ren

dah

6-21

Term

inal

54

Tega

ngan

Tin

ggi

6-22

Term

inal

54

Aru

s Re

ndah

6-23

Term

inal

54

Aru

s Ti

nggi

6-24

Term

inal

54

Ref

Rdh/

Nila

i Um

p-Ba

lik6-

25Te

rmin

al 5

4 Re

f Ti

nggi

/Nila

i Um

p-Ba

lik6-

26Te

rmin

al 5

4 Te

tapa

n W

aktu

Filt

er6-

27Li

ve Z

ero

Ter

min

al 5

46-

3*In

put

Ana

log

X30

/11

6-30

Term

inal

X30

/11

Tega

ngan

Ren

dah

6-31

Term

inal

X30

/11

Tega

ngan

Tin

ggi

6-34

Term

. X30

/11

Nil.

Ref/

Um

p.Bl

k. R

d.6-

35Te

rm. X

30/1

1 N

il.Re

f/U

mp.

Blk.

Tg.

6-36

Teta

pan

Wak

tu F

ilter

Ter

min

al X

30/1

16-

37Li

ve Z

ero

Ter

m. X

30/1

16-

4*In

put

Ana

log

X30

/12

6-40

Term

inal

X30

/12

Tega

ngan

Ren

dah

6-41

Term

inal

X30

/12

Tega

ngan

Tin

ggi

6-44

Term

. X30

/12

Nil.

Ref/

Um

p.Bl

k. R

d.6-

45Te

rm. X

30/1

2 N

il.Re

f/U

mp.

Blk.

Tg.

6-46

Teta

pan

Wak

tu F

ilter

Ter

min

al X

30/1

26-

47Li

ve Z

ero

Ter

m. X

30/1

26-

5*O

utpu

t A

nalo

g 4

26-

50Te

rmin

al 4

2 O

utpu

t6-

51Te

rmin

al 4

2 Sk

ala

Out

put

Min

.6-

52Te

rmin

al 4

2 Sk

ala

Out

put

Mak

s.

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 43

5 5

Page 48: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

6-53

Kont

rol B

us K

elua

ran

Ter

min

al 4

26-

54Pr

a-Se

tel T

ime-

Out

Klu

aran

Ter

m. 4

26-

55Fi

lter

Kelu

aran

Ana

log

6-6*

Out

put

Ana

log

X30

/86-

60Ke

luar

an T

erm

inal

X30

/86-

61Sk

ala

Min

. Ter

min

al X

30/8

6-62

Skal

a M

aks.

Ter

min

al X

30/8

6-63

Kont

rol B

us O

utpu

t Te

rm. X

30/8

6-64

Tim

eout

Pra

sete

l Out

put

Term

. X30

/88-

**Ko

m. d

an P

iliha

n8-

0*Pe

ngat

uran

Um

um8-

01Ba

gian

Kon

trol

8-02

Sum

ber

Kont

rol

8-03

Wak

tu T

imeo

ut K

ontr

ol8-

04Fu

ngsi

Tim

eout

Kon

trol

8-05

Fung

si A

khir

dar

i Ist

iraha

t8-

06Re

set

Tim

eout

Kon

trol

8-07

Pem

icu

Dia

gnos

a8-

08Pe

mba

caan

Pen

yarin

gan

8-09

Com

mun

icat

ion

Cha

rset

8-1*

Peng

atur

an K

ontr

ol8-

10Pr

ofil

Kont

rol

8-13

Kata

Sta

tus

STW

Dap

at D

ikon

figur

asi

8-3*

P'at

uran

t'm

inal

8-30

Prot

okol

8-31

Ala

mat

8-32

Baud

Rat

e8-

33Pa

ritas

/ B

it S

top

8-34

Estim

asi s

iklu

s w

aktu

8-35

Penu

ndaa

n t

angg

apan

Min

imum

8-36

Tund

a Re

spon

s M

aksi

mum

8-37

Penu

ndaa

n In

ter-

Char

Mak

s8-

4*Se

t pr

otok

ol M

C F

C8-

40Pe

mili

han

tel

egra

m8-

42PC

D M

enul

is k

onfig

uras

i8-

43PC

D M

emba

ca k

onfig

uras

i8-

5*D

igita

l/Bus

8-50

Pem

iliha

n C

oast

ing

8-52

Pilih

an B

rake

DC

8-53

pem

iliha

n s

tart

8-54

Pem

balik

an T

erpi

lih8-

55Pe

ngat

uran

Ter

pilih

8-56

Pem

iliha

n r

efer

ensi

pre

set

8-7*

BACn

et8-

70Co

ntoh

Per

angk

at B

ACn

et8-

72M

aste

r M

aks

MS/

TP8-

73Bi

ngka

i Inf

o M

aks

MS/

TP8-

74"I-

Am

" La

yana

n8-

75Sa

ndi I

nisi

alis

asi

8-8*

Dia

gnos

tik P

ort

FC8-

80Ju

mla

h P

esan

Bus

8-81

Jum

lah

Ksa

lah.

Bus

8-82

Pesa

n S

lave

Dite

rima

8-83

Jml K

esal

ahan

Sla

ve8-

84Pe

san

Sla

ve T

erki

rim8-

85W

aktu

Sla

ve H

abis

Err

or8-

89Pe

rhitu

ngan

Dia

gnos

a8-

9*Bu

s Jo

g8-

90Ke

cepa

tan

Bus

Jog

1

8-91

Kece

pata

n B

us J

og 2

8-94

Um

pan

bal

ik B

us 1

8-95

Um

pan

bal

ik B

us 2

8-96

Um

pan

bal

ik B

us 3

9-**

Prof

ibus

9-00

Setp

oint

9-07

Nila

i Akt

ual

9-15

Konf

igur

asi T

ulis

PCD

9-16

Konf

igur

asi B

aca

PCD

9-18

Ala

mat

Nod

e9-

22Pe

mili

han

Tel

egra

m9-

23Pa

ram

eter

unt

uk S

inya

l9-

27Ed

it P

aram

eter

9-28

Kont

rol P

rose

s9-

44Pe

nghi

tung

Pes

an K

erus

akan

9-45

Kode

Ker

usak

an9-

47N

omor

Ker

usak

an9-

52Pe

nghi

tung

Situ

asi K

erus

akan

9-53

Kata

Per

inga

tan

Pro

fibus

9-63

Baud

Rat

e A

ktua

l9-

64Id

entif

ikas

i Pira

nti

9-65

Nom

or P

rofil

9-67

Kata

Kon

trol

19-

68Ka

ta S

tatu

s 1

9-71

Sim

pan

Nila

i Dat

a Pr

ofib

us9-

72Pr

ofib

usD

riveR

eset

9-75

DO

Iden

tific

atio

n9-

80Pa

ram

eter

ter

defin

isi (

1)9-

81Pa

ram

eter

ter

defin

isi (

2)9-

82Pa

ram

eter

ter

defin

isi (

3)9-

83Pa

ram

eter

ter

defin

isi (

4)9-

84Pa

ram

eter

(5)

yang

Dite

ntuk

an9-

90Pe

ruba

han

Par

amet

er (1

)9-

91Pe

ruba

han

Par

amet

er (2

)9-

92Pe

ruba

han

Par

amet

er (3

)9-

93Pe

ruba

han

par

amet

er (4

)9-

94Pe

ruba

han

par

amet

er (5

)9-

99Pr

ofib

us R

evis

ion

Cou

nter

10-*

*Fi

eldb

us C

AN

10-0

*P'

atur

an B

'sam

a10

-00

Prot

okol

CA

N10

-01

Pem

iliha

n B

aud

Rat

e10

-02

MA

C ID

10-0

5P'

htg.

Kes

alah

an P

engi

riman

P'b

aca

10-0

6P'

htg.

Kes

alah

an P

ener

imaa

n P

'bac

a10

-07

Pem

baca

an p

engh

itung

an B

us O

ff10

-1*

Dev

iceN

et10

-10

Pem

iliha

n J

enis

Dat

a Pr

oses

10-1

1Tu

lis K

onfig

Dat

a Pr

oses

10-1

2Ba

ca K

onfig

Dat

a Pr

oses

10-1

3Pa

ram

eter

Per

inga

tan

10-1

4Re

fere

nsi j

arin

gan

10-1

5Ko

ntro

l Jar

inga

n10

-2*

Filte

r CO

S10

-20

COS

Filte

r 1

10-2

1CO

S Fi

lter

210

-22

COS

Filte

r 3

10-2

3CO

S Fi

lter

410

-3*

Aks

es P

aram

eter

10-3

0In

deks

Uru

t10

-31

Peny

impa

nan

Nila

i Dat

a10

-32

Revi

si D

evic

enet

10-3

3Se

lalu

Sim

pan

10-3

4Ko

de P

rodu

k D

evic

eNet

10-3

9Pa

ram

eter

Dev

icen

et F

11-*

*Lo

nWor

ks11

-0*

ID L

onW

orks

11-0

0ID

Neu

ron

11-1

*Fu

ngsi

LO

N11

-10

Prof

il D

rive

11-1

5Ka

ta P

erin

gata

n L

ON

11-1

7Re

visi

XIF

11-1

8Re

visi

Lon

Wor

ks11

-2*

Aks

es P

aram

. LO

N11

-21

Sim

pan

Nila

i Dat

a12

-**

Ethe

rnet

12-0

*P'

atur

an IP

12-0

0Tu

gas

Ala

mat

IP12

-01

Ala

mat

IP12

-02

Lapi

san

Jar

inga

n12

-03

Gat

eway

Def

ault

12-0

4Se

rver

DH

CP12

-05

Kont

rak

Kada

luar

sa12

-06

Nam

a Se

rver

12-0

7N

ama

Dom

ain

12-0

8N

ama

Hos

t12

-09

Ala

mat

Fis

ik12

-1*

Para

met

er L

ink

Ethe

rnet

12-1

0St

atus

Lin

k12

-11

Dur

asi L

ink

12-1

2N

egos

iasi

Oto

mat

is12

-13

Kcpt

an. L

ink

12-1

4D

uple

x Li

nk12

-2*

Dat

a Pr

oses

12-2

0H

al K

ontr

ol12

-21

Tulis

Kon

fig D

ata

Pros

es12

-22

Baca

Kon

fig D

ata

Pros

es12

-27

Prim

ary

Mas

ter

12-2

8Pe

nyim

pana

n N

ilai D

ata

12-2

9Se

lalu

Sim

pan

12-3

*Et

herN

et/IP

12-3

0Pa

ram

eter

Per

inga

tan

12-3

1Re

fere

nsi j

arin

gan

12-3

2Ko

ntro

l Jar

inga

n12

-33

Revi

si C

IP12

-34

Kode

Pro

duk

CIP

12-3

5Pa

ram

eter

ED

S12

-37

Peng

uran

gan

Tim

er C

OS

12-3

8Fi

lter

COS

12-4

*M

odbu

s TC

P12

-40

Stat

us P

aram

eter

12-4

1Sl

ave

Mes

sage

Cou

nt12

-42

Slav

e Ex

cept

ion

Mes

sage

Cou

nt12

-8*

Laya

nan

Eth

erne

t La

in12

-80

Serv

er F

TP12

-81

Serv

er H

TTP

12-8

2La

yana

n S

MTP

12-8

9Po

rt S

alur

an S

oket

tra

nspa

ran

12-9

*La

yana

n E

ther

net

Lanj

utan

12-9

0D

iagn

osa

kabe

l12

-91

Aut

o C

ross

Ove

r12

-92

Men

cari

IGM

P12

-93

Panj

ang

Kab

el S

alah

12-9

4Pr

otek

si B

adai

Pem

anca

r12

-95

Filte

r Ba

dai P

eman

car

12-9

6Po

rt C

onfig

12-9

8P'

hitu

ng A

ntar

muk

a12

-99

Peng

hitu

ng M

edia

13-*

*Lo

gika

Cer

das

13-0

*Pe

ngat

uran

SLC

13-0

0M

ode

Peng

ontr

ol S

L13

-01

Star

t Pe

ristiw

a13

-02

Hen

tikan

Per

istiw

a13

-03

Rese

t SL

C13

-1*

Pem

band

ing

13-1

0Su

ku O

pera

si P

emba

ndin

g13

-11

Ope

rato

r Pe

mba

ndin

g13

-12

Nila

i Pem

band

ing

13-2

*Ti

mer

s13

-20

Tim

er P

engo

ntro

l SL

13-4

*Pe

ratu

ran

Log

ika

13-4

0A

tura

n L

ogik

a Bo

olea

n 1

13-4

1O

pera

tor

Atu

ran

Log

ika

113

-42

Atu

ran

Log

ika

Bool

ean

213

-43

Ope

rato

r A

tura

n L

ogik

a 2

13-4

4A

tura

n L

ogik

a Bo

olea

n 3

13-5

*Ke

adaa

n13

-51

Peris

tiwa

Peng

ontr

ol S

L13

-52

Tind

akan

Pen

gont

rol S

L14

-**

Fung

si K

husu

s14

-0*

Switc

hing

Pem

balik

14-0

0Po

la s

witc

hing

14-0

1Fr

ekue

nsi s

witc

hing

14-0

3Ke

lebi

han

mod

ulas

i14

-04

PWM

Aca

k14

-1*

Sum

tg

ny'

l./pd

m14

-10

Kega

gala

n p

ower

list

rik14

-11

Tega

ngan

pow

er L

istr

ik p

ada

Mas

alah

14-1

2Fu

ngsi

pd

Ket

idak

-sei

mba

ngan

Sum

b.14

-2*

Fung

si R

eset

14-2

0M

ode

Rese

t14

-21

Wak

tu R

esta

rt O

tom

atis

14-2

2M

odus

Ope

rasi

14-2

3Pe

ngat

uran

Jen

is K

ode

14-2

5Pe

nund

aan

Trip

pad

a Ba

tasa

n T

orsi

14-2

6Pn

unda

.Trip

pd

Kru

sak

Pmbl

k.14

-28

Peng

atur

an P

rodu

ksi

14-2

9Ko

de la

yana

n14

-3*

Ktrl

bat

as a

rus.

14-3

0Kt

rl B

atas

aru

s, P

engu

atan

Pro

posi

onal

14-3

1Kt

rl B

atas

aru

s, W

aktu

Inte

gras

i14

-32

Kont

rol B

atas

Aru

s, W

aktu

Filt

er14

-4*

Opt

imas

i Ene

rgi

14-4

0Ti

ngka

t VT

14-4

1M

agne

tisas

i Min

imum

AEO

14-4

2Fr

ekue

nsi M

inim

um A

EO14

-43

Cosp

hi M

otor

14-5

*Li

ngku

ngan

14-5

0Fi

lter

RFI

14-5

1Ko

mpe

nsas

i DC

Lin

k14

-52

Kont

rol K

ipas

14-5

3M

onito

r Ki

pas

14-5

5Fi

lter

Kelu

aran

14-5

9Ju

mla

h N

yata

Uni

t In

vert

er14

-6*

Penu

runa

n D

aya

Aut

o14

-60

Fung

si p

ada

Suhu

Leb

ih14

-61

Fung

si p

d L

ebih

Beb

an In

vert

er14

-62

Aru

s Pe

nuru

nan

Leb

ih B

eban

Inv.

14-9

*Pe

ngat

uran

Sal

ah14

-90

Ting

kat

keru

saka

n15

-**

Info

. Fre

k. K

onvr

t15

-0*

Dat

a O

pera

si15

-00

Jam

Pen

gope

rasi

an15

-01

Jam

Put

aran

15-0

2Pe

nghi

tung

kW

h15

-03

Peny

alaa

n15

-04

Kele

biha

n S

uhu

15-0

5Ke

leb.

Teg

anga

n15

-06

Rese

t pe

nghi

tung

kW

h15

-07

Peng

hitu

ng R

eset

Jam

Put

aran

15-0

8Ju

mla

h S

tart

15-1

*Pe

ngat

. Log

Dat

a15

-10

Sum

ber

log

15-1

1In

terv

al L

oggi

ng15

-12

Peris

tiwa

Pem

icu

15-1

3M

ode

Logg

ing

15-1

4Sa

mpe

l Seb

elum

Pem

icu

15-2

*Lo

g h

isto

ris15

-20

Log

his

toris

: Per

istiw

a15

-21

Log

His

toris

: Nila

i15

-22

Log

his

toris

: Wak

tu15

-23

Log

His

toris

: Tan

ggal

dan

Wak

tu15

-3*

Log

Ala

rm15

-30

Log

Ala

rm: K

ode

Kesa

laha

n15

-31

Log

Ala

rm: N

ilai

15-3

2Lo

g A

larm

: Wak

tu15

-33

Log

Ala

rm: T

angg

al d

an W

aktu

15-4

*Id

ent.

Fre

k. K

onv.

15-4

0Je

nis

FC15

-41

Bagi

an D

aya

15-4

2Te

gang

an15

-43

Vers

i Per

angk

at L

unak

15-4

4U

ntai

an J

enis

Kod

e Te

ruru

t15

-45

Unt

aian

Jen

is k

ode

Akt

ual

15-4

6N

o O

rder

Kon

vert

er F

reku

ensi

15-4

7N

o o

rder

kar

tu d

aya

15-4

8N

o ID

LCP

15-4

9Ka

rtu

Kon

trol

ID S

W15

-50

Kart

u D

aya

ID S

W15

-51

Nom

or S

eria

l Kon

vert

er F

reku

ensi

15-5

3N

o s

eria

l kar

tu d

aya

15-5

5Ve

ndor

URL

15-5

6N

ama

Vend

or15

-59

CSIV

Nam

a Fi

le15

-6*

Iden

t Pi

lihan

15-6

0Pi

lihan

Ter

angk

ai

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

44 MG11AI9B - VLT® merek dagang terdaftar Danfoss

55

Page 49: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

15-6

1Ve

rsi S

W P

iliha

n15

-62

Nom

or P

iliha

n P

esan

an15

-63

Nom

or S

eri P

iliha

n15

-70

Pilih

an d

i Slo

t A

15-7

1Ve

rsi S

W P

iliha

n S

lot

A15

-72

Pilih

an d

i Slo

t B

15-7

3Ve

rsi S

W P

iliha

n S

lot

B15

-74

Pilih

an p

ada

Slot

C0

15-7

5Sw

Ver

sion

Ops

i di S

lot

C015

-76

Pilih

an p

ada

Slot

C1

15-7

7Sw

Ver

sion

Ops

i di S

lot

C115

-8*

Ope

ratin

g D

ata

II15

-80

Fan

Run

ning

Hou

rs15

-81

Pres

et F

an R

unni

ng H

ours

15-9

*In

fo P

aram

eter

15-9

2Pa

ram

eter

ter

defin

isi

15-9

3Pa

ram

ater

Mod

ifika

si15

-98

Driv

e Id

entif

ikas

i15

-99

Met

adat

a Pa

ram

eter

16-*

*Pe

mba

caan

Dat

a16

-0*

Stat

us U

mum

16-0

0Ka

ta K

ontr

ol16

-01

Refe

rens

i [U

nit]

16-0

2Re

fere

nsi %

16-0

3Ka

ta S

tatu

s16

-05

Nila

i Akt

ual U

tam

a [%

]16

-09

Pem

baca

an c

usto

m16

-1*

Stat

us M

otor

16-1

0D

aya

[kW

]16

-11

Day

a [h

p]16

-12

Tega

ngan

Mot

or16

-13

Frek

uens

i16

-14

Aru

s M

otor

16-1

5Fr

ekue

nsi [

%]

16-1

6To

rsi [

Nm

]16

-17

Kece

pata

n [R

PM]

16-1

8Te

rmal

Mot

or16

-20

Sudu

t M

otor

16-2

2To

rsi [

%]

16-2

6D

aya

Difi

lter

[kW

]16

-27

Day

a D

ifilte

r [h

p]16

-3*

Stat

us F

rek.

kon

v.16

-30

Tega

ngan

DC

link

16-3

2En

ergi

Bra

ke /

det

.16

-33

Ener

gi B

rake

/ 2

mnt

.16

-34

Suhu

Hea

tsin

k16

-35

Term

al P

emba

lik16

-36

Aru

s N

omin

al In

vert

er16

-37

Aru

s M

aks.

Inve

rter

16-3

8Ko

ndis

i Pen

gont

rol S

L16

-39

Suhu

Kar

tu K

ontr

ol16

-40

Peny

angg

a Lo

ggin

g T

elah

Pen

uh16

-41

Bufe

r M

emor

i Pen

uh16

-43

Stat

us T

imed

Act

ions

16-4

9A

rus

Sum

ber

Mas

alah

16-5

*Re

f &

Um

p-ba

lik16

-50

Refe

rens

i Eks

tern

al16

-52

Um

pan

Bal

ik [U

nit]

16-5

3Re

fere

nsi D

igi P

ot

16-5

4U

mp.

Bal

ik 1

[Uni

t]16

-55

Um

p. B

alik

2 [U

nit]

16-5

6U

mp.

Bal

ik 3

[Uni

t]16

-58

Kelu

aran

PID

[%]

16-6

*In

put

& O

utpu

t16

-60

Inpu

t D

igita

l16

-61

Term

inal

53

Pega

tura

n s

witc

h16

-62

Inpu

t A

nalo

g 5

316

-63

Term

inal

54

peng

atur

an s

witc

h16

-64

Inpu

t A

nalo

g 5

416

-65

Out

put

Ana

log

42

[mA

]16

-66

Out

put

Dig

ital [

bin]

16-6

7In

put

Puls

a #2

9 [H

z]16

-68

Inpu

t Pu

lsa

#33

[Hz]

16-6

9O

utpu

t Pu

lsa

#27

[Hz]

16-7

0O

utpu

t Pu

lsa

#29

[Hz]

16-7

1O

utpu

t Re

lai [

bin]

16-7

2Pe

nghi

tung

A16

-73

Peng

hitu

ng B

16-7

5M

asuk

Ana

log

X30

/11

16-7

6M

asuk

Ana

log

X30

/12

16-7

7Ke

luar

Ana

log

X30

/8 [m

A]

16-8

*Fi

eldb

us &

Por

t FC

16-8

0Fi

eldb

us C

TW 1

16-8

2Fi

eldb

us R

EF 1

16-8

4Ko

m. P

iliha

n S

TW16

-85

Port

FC

CTW

116

-86

Port

FC

REF

116

-9*

P'ba

caan

Dia

gnos

a16

-90

Kata

Ala

rm16

-91

Ala

rm w

ord

216

-92

Kata

Per

inga

tan

16-9

3Ka

ta P

erin

gata

n 2

16-9

4Ek

st. K

ata

Stat

us16

-95

Kata

Sta

tus

Ekst

. 216

-96

Kata

Pem

elih

araa

n18

-**

Info

& B

acaa

n18

-0*

Log

Pem

elih

araa

n18

-00

Log

Pem

elih

araa

n: It

em18

-01

Log

Pem

elih

araa

n: T

inda

kan

18-0

2Lo

g P

emel

ihar

aan:

Wak

tu18

-03

Log

Pem

elih

araa

n: T

angg

al d

an W

aktu

18-1

*Lo

g M

odus

Keb

akar

an18

-10

Log

Mod

us K

ebak

aran

: Per

istiw

a18

-11

Log

Mod

e Ke

baka

ran:

Wak

tu18

-12

Log

Mod

e Ke

baka

ran:

Tan

ggal

dan

Wak

tu18

-3*

Inpu

t &

Out

put

18-3

0In

put

Ana

log

X42

/118

-31

Inpu

t A

nalo

g X

42/3

18-3

2In

put

Ana

log

X42

/518

-33

Out

Ana

log

X42

/7 [V

]18

-34

Out

Ana

log

X42

/9 [V

]18

-35

Out

Ana

log

X42

/11

[V]

18-3

6M

asuk

an a

nalo

g X

48/2

[mA

]18

-37

Mas

ukan

Suh

u X

48/4

18-3

8M

asuk

an S

uhu

X48

/718

-39

Mas

ukan

Suh

u X

48/1

018

-5*

Ref.

& U

mpa

n b

alik

18-5

0Ta

npa

Sens

or P

emba

caan

[uni

t]20

-**

Loop

Ter

tutu

p D

rive

20-0

*U

mpa

n B

alik

20-0

0Su

mbe

r U

mpa

n B

alik

120

-01

Konv

ersi

Um

pan

Bal

ik 1

20-0

2U

nit

Sum

ber

Um

p. B

alik

120

-03

Sum

ber

Um

pan

Bal

ik 2

20-0

4Ko

nver

si U

mpa

n B

alik

220

-05

Uni

t Su

mbe

r U

mp.

Bal

ik 2

20-0

6Su

mbe

r U

mpa

n B

alik

320

-07

Konv

ersi

Um

pan

Bal

ik 3

20-0

8U

nit

Sum

ber

Um

p. B

alik

320

-12

Refe

rens

i/Uni

t U

mpa

n B

alik

20-1

3Re

fere

nsi/U

mpa

n b

alik

Min

imum

20-1

4Re

fere

nsi/U

mpa

n B

alik

Mak

sim

um20

-2*

Um

p. B

alik

/Set

poin

t20

-20

Fung

si U

mpa

n B

alik

20-2

1Se

tpoi

nt 1

20-2

2Se

tpoi

nt 2

20-2

3Se

tpoi

nt 3

20-3

*U

mpa

n b

alik

Lan

jut

Konv

.20

-30

Pend

ingi

n20

-31

Pend

ingi

n D

idef

inis

i P'g

una

A1

20-3

2Pe

ndin

gin

Did

efin

isi P

'gun

a A

220

-33

Pend

ingi

n D

idef

inis

i P'g

una

A3

20-3

4D

uct

1 A

rea

[m2]

20-3

5D

uct

1 A

rea

[in2]

20-3

6D

uct

2 A

rea

[m2]

20-3

7D

uct

2 A

rea

[in2]

20-3

8Fa

ktor

kep

adat

an u

dara

[%]

20-6

*Ti

dak

Ada

Sen

sor

20-6

0Ta

npa

Sens

or U

nit

20-6

9In

form

asi t

anpa

Sen

sor

20-7

*Tu

ning

aut

o P

ID20

-70

Jeni

s Lo

op T

ertu

tup

20-7

1Pe

rfor

ma

PID

20-7

2Pe

rub.

Out

put

PID

20-7

3Le

vel U

mpa

n B

alik

Min

.20

-74

Leve

l Um

pan

Bal

ik M

aks.

20-7

9Tu

ning

Oto

mat

is P

ID20

-8*

Peng

atur

an D

asar

PID

20-8

1Ko

ntro

l Nor

mal

/Ter

balik

PID

20-8

2Ke

cep.

Sta

rt P

ID [R

PM]

20-8

3Ke

cep.

Sta

rt P

ID [H

z]20

-84

Leba

r Pi

ta R

efer

ensi

On

20-9

*Pe

ngon

trol

PID

20-9

1PI

D A

nti T

ergu

lung

20-9

3Pe

role

han

Pro

pors

i. PI

D20

-94

Wak

tu In

tegr

al P

ID20

-95

Wak

tu D

ifere

nsia

l PID

20-9

6Ba

tasa

n P

engu

at D

if. P

ID21

-**

Loop

Ter

tutu

p E

kst.

21-0

*Tu

ning

aut

o E

ks. C

L21

-00

Jeni

s Lo

op T

ertu

tup

21-0

1Pe

rfor

ma

PID

21-0

2Pe

rub.

Out

put

PID

21-0

3Le

vel U

mpa

n B

alik

Min

.21

-04

Leve

l Um

pan

Bal

ik M

aks.

21-0

9Tu

ning

Oto

mat

is P

ID

21-1

*Re

f./FB

1 C

L Ek

st.

21-1

0U

nit

Um

p. B

alik

/Ref

. 1 E

kst.

21-1

1Re

fere

nsi M

in. 1

Eks

t.21

-12

Refe

rens

i Mak

s. 1

Eks

t.21

-13

Sum

ber

Refe

rens

i 1 E

kst.

21-1

4Su

mbe

r U

mp.

Bal

ik 1

Eks

t.21

-15

Setp

oint

1 E

kst.

21-1

7Re

fere

nsi 1

Eks

t. [U

nit]

21-1

8U

mp.

Bal

ik 1

Eks

t. [U

nit]

21-1

9O

utpu

t 1

Ekst

. [%

]21

-2*

PID

1 C

L Ek

st.

21-2

0Ko

ntro

l Nor

mal

/Ter

balik

1 E

kst.

21-2

1Pe

role

han

Pro

pors

iona

l 1 E

kst.

21-2

2W

aktu

Inte

gral

1 E

kst.

21-2

3W

aktu

Dife

rens

iasi

1 E

kst.

21-2

4Bt

s. P

erol

ehan

Dif.

1 E

kst.

21-3

*Re

f./FB

2 C

L Ek

st.

21-3

0U

nit

Um

p. B

alik

/Ref

. 2 E

kst.

21-3

1Re

fere

nsi M

in. 2

Eks

t.21

-32

Refe

rens

i Mak

s. 2

Eks

t.21

-33

Sum

ber

Refe

rens

i 2 E

kst.

21-3

4Su

mbe

r U

mp.

Bal

ik 2

Eks

t.21

-35

Setp

oint

2 E

kst.

21-3

7Re

fere

nsi 2

Eks

t. [U

nit]

21-3

8U

mp.

Bal

ik 2

Eks

t. [U

nit]

21-3

9O

utpu

t 2

Ekst

. [%

]21

-4*

PID

2 C

L Ek

st.

21-4

0Ko

ntro

l Nor

mal

/Ter

balik

2 E

kst.

21-4

1Pe

role

han

Pro

pors

iona

l 2 E

kst.

21-4

2W

aktu

Inte

gral

2 E

kst.

21-4

3W

aktu

Dife

rens

iasi

2 E

kst.

21-4

4Bt

s. P

erol

ehan

Dif.

2 E

kst.

21-5

*Re

f./FB

3 C

L Ek

st.

21-5

0U

nit

Um

p. B

alik

/Ref

. 3 E

kst.

21-5

1Re

fere

nsi M

in. 3

Eks

t.21

-52

Refe

rens

i Mak

s. 3

Eks

t.21

-53

Sum

ber

Refe

rens

i 3 E

kst.

21-5

4Su

mbe

r U

mp.

Bal

ik 3

Eks

t.21

-55

Setp

oint

3 E

kst.

21-5

7Re

fere

nsi 3

Eks

t. [U

nit]

21-5

8U

mp.

Bal

ik 3

Eks

t. [U

nit]

21-5

9O

utpu

t 3

Ekst

. [%

]21

-6*

PID

3 C

L Ek

st.

21-6

0Ko

ntro

l Nor

mal

/Ter

balik

3 E

kst.

21-6

1Pe

role

han

Pro

pors

iona

l 3 E

kst.

21-6

2W

aktu

Inte

gral

3 E

kst.

21-6

3W

aktu

Dife

rens

iasi

3 E

kst.

21-6

4Bt

s. P

erol

ehan

Dif.

3 E

kst.

22-*

*A

pl. F

ungs

i22

-0*

Lain

-lain

22-0

0Tu

nda

Inte

rlock

Eks

tern

al22

-01

Wak

tu F

ilter

Day

a22

-2*

Det

eksi

Tia

da A

liran

22-2

0Pe

ngat

uran

Aut

o D

aya

Rend

ah22

-21

Det

eksi

Day

a Re

ndah

22-2

2D

etek

si K

ecep

. Ren

dah

22-2

3Fu

ngsi

Tia

da A

liran

22-2

4Tu

nda

Tiad

a A

liran

22-2

6Fu

ngsi

Pom

pa K

erin

g

22-2

7Tu

nda

Pom

pa K

erin

g22

-3*

Tuni

ng D

aya

Tiad

a A

liran

22-3

0D

aya

Tiad

a A

liran

22-3

1Fa

ktor

Kor

eksi

Day

a22

-32

Kece

p. R

enda

h [R

PM]

22-3

3Ke

cep.

Ren

dah

[Hz]

22-3

4D

aya

Kece

p. R

enda

h [k

W]

22-3

5D

aya

Kece

p. R

enda

h [H

P]22

-36

Kece

p. T

ingg

i [RP

M]

22-3

7Ke

cep.

Tin

ggi [

Hz]

22-3

8D

aya

Kece

p. T

ingg

i [kW

]22

-39

Day

a Ke

cep.

Tin

ggi [

HP]

22-4

*M

ode

Stan

dby

22-4

0Ru

n T

ime

Min

imum

22-4

1W

aktu

Tid

ur M

inim

um22

-42

Kece

p. W

ake-

Up

[RPM

]22

-43

Kece

p. W

ake-

Up

[Hz]

22-4

4Se

lisih

Ref

./FB

Wak

e-U

p22

-45

Boos

t Se

tpoi

nt22

-46

Wak

tu B

oost

Mak

sim

um22

-5*

Akh

ir K

urva

22-5

0A

khir

dr

Fung

si K

urva

22-5

1A

khir

dr

Tund

a Ku

rva

22-6

*D

etek

si B

elt

Putu

s22

-60

Fung

si B

elt

Putu

s22

-61

Tors

i Bel

t Pu

tus

22-6

2Tu

nda

Belt

Put

us22

-7*

Perli

nd. S

iklu

s Pe

ndek

22-7

5Pe

rlind

. Sik

lus

Pend

ek22

-76

Inte

rval

ant

ara

Star

t22

-77

Run

Tim

e M

inim

um22

-78

Wak

tu J

alan

Min

Ove

rrid

e22

-79

Nila

i Wak

tu J

alan

Min

Ove

rrid

e22

-8*

Flow

Com

pens

atio

n22

-80

Kom

pens

asi A

liran

22-8

1Pe

rkira

an K

urva

Lin

ear-

Kuad

rat

22-8

2Pe

rhitu

ngan

Titi

k Ke

rja22

-83

Kece

p. p

d T

iada

Alir

an [R

PM]

22-8

4Ke

cep.

pd

Tia

da A

liran

[Hz]

22-8

5Ke

cep.

pd

Titi

k Ra

nc. [

RPM

]22

-86

Kece

p. p

d T

itik

Ranc

. [H

z]22

-87

Tek.

pd

Kec

ep. T

iada

Alir

an22

-88

Teka

nan

pd

Kec

ep. T

eruk

ur22

-89

Alir

an p

d T

itik

Ranc

anga

n22

-90

Alir

an p

d K

ecep

. Ter

ukur

23-*

*Fu

ngsi

ber

basi

s-w

aktu

23-0

*Ti

ndak

an B

erw

aktu

23-0

0O

N W

aktu

23-0

1O

N T

inda

kan

23-0

2O

FF W

aktu

23-0

3O

FF T

inda

kan

23-0

4Ke

jadi

an23

-0*

Tim

ed A

ctio

ns S

ettin

gs23

-08

Mod

e Ti

med

Act

ions

23-0

9Ti

med

Act

ions

Rea

ktifv

asi

23-1

*Pe

mel

ihar

aan

23-1

0Ite

m P

emel

ihar

aan

23-1

1Ti

ndak

an P

emel

ihar

aan

23-1

2D

asar

Wak

tu P

emel

ihar

aan

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 45

5 5

Page 50: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

23-1

3In

terv

al W

aktu

Pem

elih

araa

n23

-14

Tgl.

dan

Wak

tu P

emel

ihar

aan

23-1

*Re

set

Pem

elih

araa

n23

-15

Rese

t Ka

ta P

emel

ihar

aan

23-1

6Te

ks P

emel

ihar

aan

23-5

*Lo

g E

nerg

i23

-50

Reso

lusi

Log

Ene

rgi

23-5

1St

art

Perio

de23

-53

Log

Ene

rgi

23-5

4Re

set

Log

Ene

rgi

23-6

*Tr

endi

ng23

-60

Varia

bel T

rend

23-6

1D

ata

Bin

Kon

tinu

23-6

2D

ata

Bin

Ber

wak

tu23

-63

Star

t Pe

riode

Ber

wak

tu23

-64

Stop

Per

iode

Ber

wak

tu23

-65

Nila

i Bin

Mak

sim

um23

-66

Rese

t D

ata

Bin

Kon

tinu

23-6

7Re

set

Dat

a Bi

n B

erw

aktu

23-8

*Pe

nghi

t. K

emba

li23

-80

Fakt

or R

efer

ensi

Day

a23

-81

Biay

a En

ergi

23-8

2In

vest

asi

23-8

3H

emat

Ene

rgi

23-8

4H

emat

Bia

ya24

-**

Apl

2 F

ungs

i24

-0*

Mod

e Ke

baka

ran

24-0

0Fu

ngsi

Mod

e Ke

baka

ran

24-0

1Ko

nfig

uras

i Mod

e Ke

baka

ran

24-0

2U

nit

Mod

e Ke

baka

ran

24-0

3Fi

re M

ode

Min

Ref

eren

ce24

-04

Fire

Mod

e M

ax R

efer

ence

24-0

5Re

fere

nsi P

rase

tel M

ode

Keba

kara

n24

-06

Refe

rens

i Set

ting

Mod

e Ke

baka

ran

24-0

7Su

mbe

r U

mpa

n B

alik

Mod

e Ke

baka

ran

24-0

9Pe

nang

anan

Ala

rm M

ode

Keba

kara

n24

-1*

Bypa

ss D

rive

24-1

0Fu

ngsi

Jal

an P

inta

s D

rive

24-1

1W

aktu

Tun

da B

ypas

s D

rive

24-9

*Fu

ngsi

Mul

ti-M

otor

24-9

0Fu

ngsi

Mot

or H

ilang

24-9

1Ko

effis

ien

Mot

or 1

Hila

ng24

-92

Koef

fisie

n M

otor

2 H

ilang

24-9

3Ko

effis

ien

Mot

or 3

Hila

ng24

-94

Koef

fisie

n M

otor

4 H

ilang

24-9

5Fu

ngsi

Rot

or T

erku

nci

24-9

6Ko

effis

ien

Rot

or 1

Ter

kunc

i24

-97

Koef

fisie

n R

otor

2 T

erku

nci

24-9

8Ko

effis

ien

Rot

or 3

Ter

kunc

i24

-99

Koef

fisie

n R

otor

4 T

erku

nci

25-*

*Pe

ngon

trol

Kas

kade

25-0

*Pe

ngat

uran

Sis

tem

25-0

0Pe

ngon

trol

Kas

kade

25-0

2St

art

Mot

or25

-04

Sikl

us P

ompa

25-0

5Po

mpa

Uta

ma

Teta

p25

-06

Jum

lah

Pom

pa25

-2*

Peng

atur

an L

ebar

Pita

25-2

0Ba

ndw

idth

Sta

ging

25-2

1Ke

sam

ping

. Leb

ar P

ita25

-22

Leba

r Pi

ta K

ecep

. Tet

ap25

-23

Tund

a St

agin

g S

BW25

-24

Tund

a D

esta

ging

SBW

25-2

5W

aktu

OBW

25-2

6D

esta

ge p

d T

iada

-Alir

an25

-27

Fung

si S

tagi

ng25

-28

Wak

tu F

ungs

i Sta

ging

25-2

9Fu

ngsi

Des

tage

25-3

0W

aktu

Fun

gsi D

esta

ge25

-4*

Peng

atur

an S

tagi

ng25

-40

Tund

a Ra

mp

Dow

n25

-41

Tund

a Ra

mp

Up

25-4

2A

mba

ng S

tagi

ng25

-43

Am

bang

Des

tagi

ng25

-44

Kece

p. S

tagi

ng [R

PM]

25-4

5Ke

cep.

Sta

ging

[Hz]

25-4

6Ke

cepa

tan

Des

tagi

ng [R

PM]

25-4

7Ke

cepa

tan

Des

tagi

ng [H

z]25

-5*

Peng

atur

an B

erga

ntia

n25

-50

Pom

pa U

tam

a Be

rgan

tian

25-5

1Pe

ristiw

a Be

rgan

tian

25-5

2In

terv

al W

aktu

Ber

gant

ian

25-5

3N

ilai T

imer

Ber

gant

ian

25-5

4W

aktu

Pra

defin

isi B

erga

ntia

n25

-55

Berg

anti

jk B

eban

< 5

0%25

-56

Mod

e St

agin

g p

d P

erga

ntia

n25

-58

Penu

ndaa

an J

alan

Pom

pa B

'ikut

25-5

9Pe

nund

aaan

Jal

an P

ower

Lis

trik

25-8

*St

atus

25-8

0St

atus

Kas

kade

25-8

1St

atus

Pom

pa25

-82

Pom

pa U

tam

a25

-83

Stat

us R

elai

25-8

4W

aktu

Pom

pa O

N25

-85

Wak

tu R

elai

ON

25-8

6Re

set

Peng

hitu

ng R

elai

25-9

*Se

rvis

25-9

0Sa

ling

Kun

ci P

ompa

25-9

1Be

rgan

tian

Man

ual

26-*

*O

psi I

/O A

nalo

g26

-0*

Mod

e I/O

Ana

log

26-0

0M

ode

Term

inal

X42

/126

-01

Mod

e Te

rmin

al X

42/3

26-0

2M

ode

Term

inal

X42

/526

-1*

Inpu

t A

nalo

g X

42/1

26-1

0Te

gang

an R

enda

h T

erm

. X42

/126

-11

Tega

ngan

Tin

ggi T

erm

. X42

/126

-14

Nila

i Ref

/Um

p.Bl

k. R

ndh.

Ter

m. X

42/1

26-1

5N

ilai R

ef/U

mp.

Blk.

Tgg

i Ter

m. X

42/1

26-1

6Fi

lter

Wak

tu C

onst

ant

Term

. X42

/126

-17

Live

Zer

o T

erm

. X42

/126

-2*

Inpu

t A

nalo

g X

42/3

26-2

0Te

gang

an R

enda

h T

erm

. X42

/326

-21

Tega

ngan

Tin

ggi T

erm

. X42

/326

-24

Nila

i Ref

/Um

p.Bl

k. R

ndh.

Ter

m. X

42/3

26-2

5N

ilai R

ef/U

mp.

Blk.

Tgg

i Ter

m. X

42/3

26-2

6Fi

lter

Wak

tu C

onst

ant

Term

. X42

/326

-27

Live

Zer

o T

erm

. X42

/3

26-3

*In

put

Ana

log

X42

/526

-30

Tega

ngan

Ren

dah

Ter

m. X

42/5

26-3

1Te

gang

an T

ingg

i Ter

m. X

42/5

26-3

4N

ilai R

ef/U

mp.

Blk.

Rnd

h. T

erm

. X42

/526

-35

Nila

i Ref

/Um

p.Bl

k. T

ggi T

erm

. X42

/526

-36

Filte

r W

aktu

Con

stan

t Te

rm. X

42/5

26-3

7Li

ve Z

ero

Ter

m. X

42/5

26-4

*Ke

luar

Ana

log

X42

/726

-40

Out

put

Term

inal

X42

/726

-41

Skal

a M

in. T

erm

inal

X42

/726

-42

Skal

a M

aks.

Ter

min

al X

42/7

26-4

3Ko

ntro

l Bus

Ter

min

al X

42/7

26-4

4Pr

a-se

tel T

imeo

ut T

erm

inal

X42

/726

-5*

Kelu

ar A

nalo

g X

42/9

26-5

0O

utpu

t Te

rmin

al X

42/9

26-5

1Sk

ala

Min

. Ter

min

al X

42/9

26-5

2Sk

ala

Mak

s. T

erm

inal

X42

/926

-53

Kont

rol B

us T

erm

inal

X42

/926

-54

Pra-

sete

l Tim

eout

Ter

min

al X

42/9

26-6

*Ke

luar

Ana

log

X42

/11

26-6

0O

utpu

t Te

rmin

al X

42/1

126

-61

Skal

a M

in. T

erm

inal

X42

/11

26-6

2Sk

ala

Mak

s. T

erm

inal

X42

/11

26-6

3Ko

ntro

l Bus

Ter

min

al X

42/1

126

-64

Pra-

sete

l Tim

eout

Ter

min

al X

42/1

130

-**

Fitu

r Kh

usus

30-2

*A

dv. S

tart

Adj

ust

30-2

2Lo

cked

Rot

or D

etec

tion

30-2

3Lo

cked

Rot

or D

etec

tion

Tim

e [s

]31

-**

Ops

i Byp

ass

31-0

0M

ode

Bypa

ss31

-01

Tund

a W

aktu

Sta

rt B

ypas

s31

-02

Tund

a W

aktu

Trip

Byp

ass

31-0

3A

ktiv

asi M

ode

Uji

31-1

0Ka

ta S

tatu

s By

pass

31-1

1Ja

m B

erja

lan

Byp

ass

31-1

9Re

mot

e By

pass

Act

ivat

ion

35-*

*Pi

lihan

Inpu

t Se

nsor

35-0

*M

asuk

an S

uhu

Mod

e35

-00

Term

. X48

/4 S

atua

n S

uhu

35-0

1Te

rm. X

48/4

Tip

e In

put

35-0

2Te

rm. X

48/7

Sat

uan

Suh

u35

-03

Term

. X48

/7 T

ipe

Inpu

t35

-04

Term

. X48

/10

Satu

an S

uhu

35-0

5Te

rm. X

48/1

0 Ti

pe In

put

35-0

6Fu

ngsi

Per

inga

tan

Sen

sor

Suhu

35-1

*M

asuk

an S

uhu

X48

/435

-14

Term

. X48

/4 F

ilter

Wak

tu K

onst

an35

-15

Term

. X48

/4 M

onito

r Su

hu35

-16

Term

. X48

/4 B

atas

Suh

u T

eren

dah

35-1

7Te

rm. X

48/4

Bat

as S

uhu

Ter

tingg

i35

-2*

Mas

ukan

Suh

u X

48/7

35-2

4Te

rm. X

48/7

Filt

er W

aktu

Kon

stan

35-2

5Te

rm. X

48/7

Mon

itor

Suhu

35-2

6Te

rm. X

48/7

Bat

as S

uhu

Ter

enda

h35

-27

Term

. X48

/7 B

atas

Suh

u T

ertin

ggi

35-3

*M

asuk

an S

uhu

X48

/10

35-3

4Te

rm. X

48/1

0 Fi

lter

Wak

tu K

onst

an35

-35

Term

. X48

/10

Mon

itor

Suhu

35-3

6Te

rm. X

48/1

0 Ba

tas

Suhu

Ter

enda

h35

-37

Term

. X48

/10

Bata

s Su

hu T

ertin

ggi

35-4

*M

asuk

an a

nalo

g X

48/2

35-4

2Te

rm. X

48/2

Aru

s Re

ndah

35-4

3Te

rm. X

48/2

Aru

s Te

rtin

ggi

35-4

4Te

rm. X

48/2

Nila

i Ter

enda

h R

ef./F

eedb

.35

-45

Term

. X48

/2 N

ilai T

ertin

ggi R

ef./F

eedb

.35

-46

Term

. X48

/2 F

ilter

Wak

tu K

onst

an35

-47

Term

. X48

/2 L

ive

Zero

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

46 MG11AI9B - VLT® merek dagang terdaftar Danfoss

55

Page 51: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

5.6 Program jauh dengan MCT 10 Set-upPerangkat Lunak

Danfoss merupakan program perangkat lunak yangtersedia untuk pengembangan, penyimpanan, danmentransfer program. konverter frekuensi. MCT 10 Set-upPerangkat Lunak memungkinkan pengguna untuksambung PC ke konverter frekuensi dan melakukanprogram live dari pada menggunakan LCP. Dan juga,semua program konverter frekuensi dapat dilakukan off-line dan didownload ke konverter frekuensi. Atau profilkonverter frekuensi keseluruhan dapat dimuat ke PC untukpenyimpanan cadangan atau analisa.

Konektor USB atau terminal RS-485 tersedia untukmenyambungkan ke konverter frekuensi.

MCT 10 Set-up Perangkat Lunak tersedia untuk downloadbebas biaya di www.VLT-software.com. CD juga tersediadengan meminta nomor bagian 130B1000. Untuk informasiselanjutnya, lihat Petunjuk Pengoperasian.

Tentang Program Konverter F... VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 47

5 5

Page 52: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

6 Contoh Pengaturan Aplikasi

6.1 Pendahuluan

CATATAN!Kabel jumper diperlukan antara terminal 12 (atau13) danterminal 37 untuk konverter frekuensi untuk mengope-rasikan pada saat menggunakan angka program standarpabrik.

Contoh di bagian ini dimaksud sebagai referensi cepatuntuk aplikasi umum.

• Pengaturan Parameter merupakan angka standarregional kecuali yang ditunjukkan (dipilih di0-03 Pengaturan Wilayah)

• Parameter yang dihubungkan dengan terminaldan pengaturan terlihat di gambar berikutnya

• Di mana pengaturan saklar untuk terminal analogA53 atau A54 diperlukan, dan juga terlihat

6.2 Contoh Aplikasi

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

130B

B929

.10 Fungsi P'aturan

1-29 PenyesuaianMotor Otomatis(AMA)

[1] AktifkanAMA lengkap

5-12 Terminal 27Input Digital

[2]* Coastterbalik

* = Nilai standar

Catatan/komentar: Grupparameter 1-2* harus diaturmenurut motor

Tabel 6.1 AMA dengan T27 Tersambung

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

130B

B930

.10 Fungsi P'aturan

1-29 PenyesuaianMotor Otomatis(AMA)

[1] AktifkanAMA lengkap

5-12 Terminal 27Input Digital

[0] Tidak adaoperasi

* = Nilai standar

Catatan/komentar: Grupparameter 1-2* harus diaturmenurut motor

Tabel 6.2 AMA tanpa T27 yang Tersambung

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

A53

U - I

-10 - +10V

+

-

130B

B926

.10 Fungsi P'aturan

6-10 Terminal 53TeganganRendah 0.07 V*

6-11 Terminal 53Tegangan Tinggi

10 V*

6-14 Terminal 53Ref Rdh/NilaiUmp-Balik

0 Hz

6-15 Terminal 53Ref Tinggi/NilaiUmp-Balik

1500 Hz

* = Nilai standar

Catatan/komentar:

Tabel 6.3 Referensi Kecepatan Analog (Tegangan)

Contoh Pengaturan Aplikasi VLT® Petunjuk Operasional Drive HVAC

48 MG11AI9B - VLT® merek dagang terdaftar Danfoss

66

Page 53: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

130B

B802

.10 Fungsi P'aturan

5-10 Terminal 18Input Digital

[8] Start*

5-12 Terminal 27Input Digital

[0] Tidak adaoperasi

5-19 Terminal 37Berhenti Aman

[1] AlarmStop Aman

* = Nilai standar

Catatan/komentar:Pada saat 5-12 Terminal 27Input Digital diatur ke [0] Tidakada Operasi, kabel jumper ke27 tidak diperlukan.

Tabel 6.4 Perintah Mulai/Stop dengan Stop Aman

130B

B805

.11

Speed

Start (18)

Ilustrasi 6.1 Perintah Mulai/Stop dengan Stop Aman

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

130B

B803

.10 Fungsi P'aturan

5-10 Terminal 18Input Digital

[9] Startterkunci

5-12 Terminal 27Input Digital

[6] StopTerbalik

* = Nilai standar

Catatan/komentar:Pada saat 5-12 Terminal 27Input Digital diatur ke [0] Tidakada Operasi, kabel jumper ke27 tidak diperlukan.

Tabel 6.5 Pulsa Mulai/Berhenti

Speed

130B

B806

.10

Latched Start (18)

Stop Inverse (27)

Ilustrasi 6.2 Start (penganjakan) terkunci/Menghentikanpembalikan

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

130B

B934

.10 Fungsi P'aturan

5-10 Terminal 18Input Digital

[8] Start

5-11 Terminal 19Input Digital

[10]Pembalikan*

5-12 Terminal 27Input Digital

[0] Tidakada operasi

5-14 Terminal 32Input Digital

[16] Presetref bit 0

5-15 Terminal 33Input Digital

[17] Presetref bit 1

3-10 Referensipreset

Preset ref. 0Preset ref. 1Preset ref. 2Preset ref. 3

25%50%75%100%

* = Nilai standar

Catatan/komentar:

Tabel 6.6 Start/Stop dengan Mundur dan Kecepatan Preset 4

Contoh Pengaturan Aplikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 49

6 6

Page 54: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

130B

B928

.10 Fungsi P'aturan

5-11 Terminal 19Input Digital

[1] Reset

* = Nilai standar

Catatan/komentar:

Tabel 6.7 Reset Alarm Eksternal

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

A53

U - I

≈ 5kΩ

130B

B683

.10 Fungsi P'aturan

6-10 Terminal 53TeganganRendah 0.07 V*

6-11 Terminal 53Tegangan Tinggi

10 V*

6-14 Terminal 53Ref Rdh/NilaiUmp-Balik

0 Hz

6-15 Terminal 53Ref Tinggi/NilaiUmp-Balik

1500 Hz

* = Nilai standar

Catatan/komentar:

Tabel 6.8 Referensi Kecepatan(menggunakan potentiometer manual)

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

130B

B804

.10 Fungsi P'aturan

5-10 Terminal 18Input Digital

[8] Start*

5-12 Terminal 27Input Digital

[19] TahanReferensi

5-13 Terminal 29Input Digital

[21]MenaikkanKecepatan

5-14 Terminal 32Input Digital

[22]TurunkanKecepatan

* = Nilai standar

Catatan/komentar:

Tabel 6.9 Menaikkan/Menurunkan Kecepatan

S t a r t ( 1 8 )

F r e e z e r e f ( 2 7 )

S p e e d u p ( 2 9 )

S p e e d d o w n ( 3 2 )

S p e e d

R e f e r e n c e

130B

B840

.10

Ilustrasi 6.3 Menaikkan/Menurunkan Kecepatan

Contoh Pengaturan Aplikasi VLT® Petunjuk Operasional Drive HVAC

50 MG11AI9B - VLT® merek dagang terdaftar Danfoss

66

Page 55: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

R1R2

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

01

02

03

04

05

06

-

616869

RS-485

+

130B

B685

.10 Fungsi P'aturan

8-30 Protokol FC*

8-31 Alamat 1*

8-32 Baud Rate 9600*

* = Nilai standar

Catatan/komentar:Pilh protokol, alamat dan baudrate di parameter yang terteradiatas.

Tabel 6.10 Koneksi Jaringan RS-485

KEWASPADAANThermistor harus menggunakan penguatan atau melipat-gandakan insulasi untuk memenuhi persyaratan.

Parameter

FC

+24 V

+24 V

D IN

D IN

D IN

COM

D IN

D IN

D IN

D IN

+10 V

A IN

A IN

COM

A OUT

COM

12

13

18

19

20

27

29

32

33

37

50

53

54

55

42

39

A53

U - I

130B

B686

.11 Fungsi P'aturan

1-90 Proteksi pdtermal motor

[2] Tripthermistor

1-93 SumberThermistor

[1] Masukananalog 53

* = Nilai standar

Catatan/komentar:Pada saat peringatan hanyadiinginkan, 1-90 Proteksi pdtermal motor harus diatur keperingatan Thermistor [1].

Tabel 6.11 Termistor Motor

Contoh Pengaturan Aplikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 51

6 6

Page 56: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

7 Status Pesan

7.1 Status Layar

Pada saat konverter frekuensi di modus status, pesanstatus dihasilkan secara otomatis dari diantara konverterfrekuensi dan muncul di bagian bawah layar(lihatIlustrasi 7.1.)

Status799RPM 7.83A 36.4kW

0.000

53.2%

1(1)

AutoHandO

RemoteLocal

RampingStopRunningJogging...Stand by

130B

B037

.11

1 2 3

Ilustrasi 7.1 Status Layar

a. Bagian yang pertama pada status menunjukkandi mana asal-mula perintah stop/mulai.

b. Bagian yang kedua di status menunjukkan dimana asal-mula kontrol kecepatan.

c. Bagian yang terakhir dari status memberikanstatus konverter frekuensi yang ada. Semuanya inimemperlihatkan keadaan konverter frekuensipada modus operasional.

CATATAN!Pada modus otomatis/jauh, konverter frekuensimemerlukan perintah eksternal untuk menjalankan fungsi.

7.2 Definisi Pesan Status

Tabel tiga berikutnya menentukan arti dari tampilan katastatus pesan.

Modus OperasiMati Konverter frekuensi tidak bereaksi terhadap

kontrol sinyal sampai [Otomatis Aktif] atau[Tangan Aktif] ditekan

Auto Aktif Konverter frekuensi dikontrol dari terminalkontrol dan/atau komunikasi serial.

Tombol navigasi pada LCP mengontrolkonverter frekuensi. Berhentikan perintah,reset, membalik, rem DC, dan sinyal lainnyayang ditetapkan ke terminal kontrol yangdapat menolak kontrol lokal.

Tabel 7.1 Modus Operasi Status Pesan

Situs Referensi

Jauh Referensi kecepatan diberikan dari sinyaleksternal, komunikasi serial, atau referensi pra-setel internal.

Lokal Konverter frekuensi menggunakan [TanganAktif] atau angkareferensi dari LCP.

Tabel 7.2 Situs Referensi Status Pesan

Status OperasiRem AC Rem AC dipilih pada 2-10 Fungsi Brake. Rem

AC membuat kelebihan magnit pada motoryang berakibat pengontrol memperlambanjalannya.

Selesai AMA OK Penyesuaian motor otomatis (AMA) dibawasecara sukses.

AMA siap AMA siap untuk memulai. Tekan [Hand On]untuk mulai.

AMA berjalan Proses AMA sedang berlangsung.

Pengereman Pemotong rem sedang dalam beroperasi.Energi Generatif diserap oleh resistor rem.

Rem maks. Pemotong rem sedang dalam beroperasi.Batas daya untuk resistor rem ditentukan di2-12 Batas Daya Brake (kW) telah tercapai.

Meluncur • Peluncuran terbalik dipillih sebagai fungsiuntuk input digital (grup parameter 5-1*Input Digital). Terminal koresponding tidaktersambung.

• Peluncuran diaktifkan oleh komunikasiserial

Status Pesan VLT® Petunjuk Operasional Drive HVAC

52 MG11AI9B - VLT® merek dagang terdaftar Danfoss

77

Page 57: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Status OperasiKtrl Bus Ramp-bawah

Kontrol Ramp-bawah terpilih di14-10 Kegagalan power listrik.

• Tegangan listrik di bawah angka yangditetapkan di 14-11 Tegangan power Listrikpada Masalah pada masalah listrik

• Konverter frekuensi ramp bawah motordengan menggunakan pengontrol rampbawah

Arus Tinggi Arus output konverter frekuensi diatas batasyang diatur di 4-51 Arus Peringatan Tinggi.

Arus Rendah Arus output konverter frekuensi dibawahbatas yang diatus di 4-52 Kecepatan PeringatanRendah

Tahan DC Penahan DC terpilih di 1-80 Fungsi saat Stopdan perintah berhenti telah aktif. Motorditahan oleh arus DC yang diatur di 2-00 ArusPenahan DC/Prapanas.

Stop DC Motor ditahan dengan arus DC (2-01 ArusBrake DC) untuk waktu khusus (2-02 WaktuPengereman DC).

• Rem DC diaktifkan di 2-03 KecepatanPenyelaan Rem DC [RPM] dan perintahBerhenti aktif.

• Rem DC (terbalik) terpilih sebagai fungsiuntuk input digital (grup parameter 5-1*Input Digital). Terminal koresponding tidakaktif.

• Rem DC diaktifkan melalui komunikasiserial.

Umpan baliktinggi

Jumlah semua umpan-balik aktif diatas batasumpan-balik yang diatur di 4-57 PeringatanUmpan Balik Tinggi.

Umpan Balikrendah

Jumlah dari semua umpan-balik di bawahbatas umpan-balik yang diatur di4-56 Peringatan Umpan Balik Rendah.

Tahan keluaran referensi jauh aktif yang menahan kecepatanyang ada.

• Output diam terpilih sebagai fungsi untukinput digital (grup parameter 5-1* InputDigital). Terminal koresponding telah aktif.Kontrol kecepatan hanya memungkinkanmelalui fungsi terminal dengan kecepatanbertambah dan berkurang.

• Penahanan ramp diaktifkan melaluikomunikasi serial.

Permintaanoutput diam

Perintah output diam telah diberikan, tetapisampai izin sinyal berjalan yang diterima,motor tetap berhenti.

Status OperasiRef. diam Referensi Diam terpilih sebagai fungsi untuk

input digital (grup parameter 5-1* InputDigital). Terminal koresponding telah aktif.Konverter frekuensi menyimpan referensiaktual. Perubahan referensi sekarang hanyamemungkinkan melalui fungsi terminaldengan kecepatan bertambah dan berkurang.

Permintaan jog Perintah jog telah diberikan, tetapi sampai izinsinyal berjalan diterima via input digital,motor berhenti

Jogging Motor sedang berjalan sebagai yangdiprogram di 3-19 Kecepatan Jog [RPM].

• Jog terpilih sebagai fungsi untuk inputdigital (grup parameter 5-1* Input Digital).Terminal koresponding (contoh Terminal29) aktif.

• Fungsi Jog diaktifkan melalui komunikasiserial.

• Fungsi jog terpilih sebagai reaksi untukmemonitor fungsi (Contoh Tidak adasinyal). Fungsi monitoring aktif.

Periksa motor Pada 1-80 Fungsi saat Stop, Pemeriksaan Motorterpilih. Perintah stop aktif. Untuk memastikanmotor telah tersambung ke konverterfrekuensi, arus pengujian permanenditetapkan ke motor.

Kontrol OVC Kontrol tegangan berlebih diaktifkan di2-17 Pengontrol tegangan berlebih. Motor yangtersambung memasok konverter frekuensidengan energi generatif. Kontrol kelebihantegangan menyesuaikan rasio V/Hz untukmenjalankan motor di modus pengontrol danmencegah konverter frekuensi dari trip.

Daya Mati (Untuk konverter frekuensi hanya denganpasokan daya 24 V eksternal yang diinstal.)Pasokan sumber listrik ke konverter frekuensidilepas, tetapi kartu kontrol di pasok dengan24 V eksternal.

Mds perlindung Modus perlindungan aktif. Unit telahterdeteksi status kritis (arus berlebih ataukelebihan tegangan).

• Untuk menghindari trip, frekuensiswitching dikurangi ke 4 kHz.

• Jika memungkinkan, modus perlindunganberakhir setelah perkiraan 10 d

• Modus perlindungan dapat dibatasi di14-26 Pnunda.Trip pd Krusak Pmblk.

Status Pesan VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 53

7 7

Page 58: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Status OperasiQStop Motor diberhentikan dengan menggunakan

3-81 Waktu Ramp Stop Cepat.

• Berhenti cepat terbalik terpilih sebagaifungsi untuk input digital (grup parameter5-1*). Terminal koresponding tidak aktif.

• Fungsi berhenti cepat diakftifkan melaluikomunikasi serial.

SedangMenanjak

Motor bertambah/berkurang denganmenggunakan Ramp atas/Bawah aktif.Reference, batas angka atau perhentian belumtercapai.

Ref. tinggi Jumlah semua referensi aktif diatas batasreferensi yang diatur di 4-55 PeringatanReferensi Tinggi.

Ref. rendah Jumlah semua referensi aktif di bawah batasreferensi yang diatur di 4-54 PeringatanReferensi Rendah.

Jalan pd ref Konverter frekuensi berjalan di kisaranreferensi. Angka umpan-balik mencocokkanangka titik penetapan.

Jalankanpermintaan

Perintah mulai telah diberikan, tetapi motordihentikan sampai sinyal berjalan yangdiperbolehkan diterima melalui input digital.

Berjalan Konverter frekuensi berjalan motor.

Mode Tidur Fungsi penyimpanan energi diaktifkan. Motoryang ada telah berhenti, tetapi akan memulaikembali secara otomatis pada saat diperlukan.

Kecepatan tinggi Kecepatan motor diatas angka yangditetapkan di 4-53 Kecepatan Peringatan Tinggi.

Kecepatanrendah

Kecepatan motor di bawah angka yangditetapkan di 4-52 Kecepatan PeringatanRendah.

Standby Pada modus In Otomatis Aktif, konverterfrekuensi memulai motor dengan sinyal mulaidari input digital atau komunikasi serial.

Tunda Start Pada 1-71 Penundaan start, Waktu mulai tundadiatur. Perintah mulai diaktifkan dan motorakan memulai setelah waktu tunda mulaitelah berakhir.

Start fwd/rev Mulai maju dan mulai terbalik dipilih sebagaifungsi untuk dua input digital yang berbedayang berbeda (grup parameter 5-1* InputDigital). Motor memulai maju atau terbaliktergantung pada terminal korespondingdiaktifkan.

Stop Konverter frekuensi telah menerima perintahberhenti dari , input digital atau komunikasiserial.

Trip Alarm terjadi dan motor dihentikan. Pada saatalarm dinonaktifka, konverter frekuensi dapatdireset secara manual dengan menekan[Reset] atau secara jauh mengontrol denganterminal kontrol atau komunikasi serial.

Status OperasiTrip Terkunci Alarm terjadi dan motor dihentikan. Pada saat

alarm dinonaktifkan, daya harus disikluskan kekonverter frekuensi. Konverter frekuensi dapatkemudian direset secara manual denganmenekan [Reset] atau secara jauh olehterminal kontrol atau komunikasi serial.

Tabel 7.3 Status Operasi Status Pesan

Status Pesan VLT® Petunjuk Operasional Drive HVAC

54 MG11AI9B - VLT® merek dagang terdaftar Danfoss

77

Page 59: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

8 Peringatan dan Alarm

8.1 Sistem Monitoring

Konverter frekuensi memonitor kondisi daya input, output,dan faktor motor dan indikator perfoma sistem lainnya.Peringatan atau alarm tidak menunjukkan internal masalahke konverter frekuensi. Pada beberapa masalah, haltersebut menunjukkan kegagalan kondisi dari teganganinput, beban motor atau suhu, sinyal eksternal, atau arealain yang dimonitor oleh logika internal konverterfrekuensi. Pastikan untuk menginvestigasi eksterior area inike konverter frekuensi sebagai yang ditunjukkan di alarmatau peringatan.

8.2 Jenis Peringatan dan Alarm

PeringatanPeringatan muncul pada saat kondisi alarm yangmendatang atau pada saat kondisi operasi yang tidaknormal terjadi dan mengakibatkan alarm pada konverterfrekuensi. Peringatan menghapus dengan sendirinya padasaat kondisi yang tidak normal dinonaktifkan.

AlarmTripAlarm yang dihasilkan pada saat konverter frekuensi ditrip,artinya, konverter frekuensi menutup operasi untukmencegah konverter frekuensi atau kerusakan sistem.Motor akan diluncur untuk berhenti. Logika konverterfrekuensi akan berlanjut untuk mengoperasikan danmemonitor status konverter frekuensi. Setelah kondisibermasalah telah selesai, konverter frekuensi dapat direset.Rem kemudian akan siap untuk memulai pengoperasiankembali.

Trip dapat direset dalam 4 cara

• Tekan [Reset] pada LCP

• Perintah input reset digital

• Komunikasi serial reset perintah input

• Reset otomatis

Alarm yang menyebabkan konverter frekuensi menjaditrip-lock memerlukan daya input di cycle. Motor akandiluncur untuk berhenti. Logika konverter frekuensi akanberlanjut untuk mengoperasikan dan memonitor statuskonverter frekuensi. Hilangnya daya input ke konverterfrekuensi dan koreksi penyebab masalah, kemudiankembalikan daya. Tindakan ini membuat konverterfrekuensi masuk dalam kondisi trip sebagai yang dijelaskandiatas dan mungkinkan di reset dalam 4 cara.

8.3 Tampilan Peringatan dan Alarm

130B

P085

.11

Status0.0Hz 0.000psi 0.00A

0.0Hz1:0 - Off

!Live zero error [W2]Off Remote Stop

!1(1)

Ilustrasi 8.1 Peringatan Tampilan

Alarm atau alarm trip-lock akan berkedip pada tampilandengan nomor alarm.

130B

P086

.11

Status0.0Hz 0.000kW 0.00A

0.0Hz0

Earth Fault [A14]Auto Remote Trip

1(1)

Ilustrasi 8.2 Tampilan Alarm

Di samping teks, kode alarm pada tampilan konverterfrekuensi LCP, terdapat pula tiga status lampu indikator.

Autoon Reset

Handon Off

Back

Cancel

InfoOKOn

Alarm

Warn.

130B

B467

.10

Ilustrasi 8.3 Status Lampu Indikator

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 55

8 8

Page 60: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Peringatan LED LED Alarm

Peringatan NYALA Mati

Alarm Mati Nyala (Berkedip)

Trip-Lock NYALA Nyala (Berkedip)

Tabel 8.1 Penjelasan Status Lampu Indikator

8.4 Definisi Peringatan dan Alarm

Tabel 8.2 menentukan apabila peringatan ditampilkan sebelum alarm, dan apabila alarm trip pada unit atau trip menguncipada unit.

No. Keterangan Peringatan

Alarm/Trip Alarm/TripTerkunci

Referensi Parameter

1 10 Volt rendah X

2 Kesalahan live zero (X) (X) 6-01 Fungsi Istirahat arus/teg.t'lalu rdh

4 Fasa listrik hilang (X) (X) (X) 14-12 Fungsi pd Ketidak-seimbangan Sumb.

5 Tegangan hubungan DC tinggi X

6 Tegangan hubungan DC rendah X

7 DC kelebihan tegangan X X

8 DC kekurangan tegangan X X

9 Inverter lebih beban X X

10 ETR Motor kelebihan suhu (X) (X) 1-90 Proteksi pd termal motor

11 Termistor Motor kelebihan suhu (X) (X) 1-90 Proteksi pd termal motor

12 Batas Torsi X X

13 Kelebihan arus X X X

14 Masalah pembumian (tanah) X X X

15 Ketidakcocokan perangkat keras X X

16 Hubung singkat X X

17 Timeout kata kontrol (X) (X) 8-04 Fungsi Timeout Kontrol

18 Gagal Start X 1-77 Kecepatan Start MaxCompressor [RPM], 1-79 WaktuStart Max Kompressor hingga

trip, 1-03 Karakteristik Torsi

23 Masalah Kipas Internal X

24 Masalah Kipas Eksternal X 14-53 Monitor Kipas

25 Hubung singkat tahanan rem X

26 Batas daya tahanan rem (X) (X) 2-13 Pemantauan Daya Brake

27 Hubung singkat pemotong rem X X

28 Periksa rem (X) (X) 2-15 Cek Brake

29 Driver over temperature (Suhu driveketinggian)

X X X

30 Fasa motor U hilang (X) (X) (X) 4-58 Fungsi Fasa Motor Hilang

31 Fasa motor V hilang (X) (X) (X) 4-58 Fungsi Fasa Motor Hilang

32 Fasa motor W hilang (X) (X) (X) 4-58 Fungsi Fasa Motor Hilang

33 Inrush rusak X X

34 Masalah komunikasi fieldbus X X

35 Di luar jangkauan frekuensi X X

36 Gagal hantaran X X

37 Fasa tidak seimbang X X

38 Masalah internal X X

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

56 MG11AI9B - VLT® merek dagang terdaftar Danfoss

88

Page 61: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

No. Keterangan Peringatan

Alarm/Trip Alarm/TripTerkunci

Referensi Parameter

39 Heatsink sensor X X

40 Lebih beban pada Terminal Keluaran Digital27

(X) 5-00 Mode I/O Digital,5-01 Mode Terminal 27

41 Lebih beban pada Terminal Keluaran Digital29

(X) 5-00 Mode I/O Digital,5-02 Terminal 29 Mode

42 Lebih beban Keluaran Digital pada X30/6 (X) 5-32 Term X30/6 Digi Out (MCB101)

42 Lebih beban Keluaran Digital pada X30/7 (X) 5-33 Term X30/7 Digi Out (MCB101)

46 Pasokan kartu daya X X

47 Pasok 24V rend X X X

48 Pasok 1.8V rendah X X

49 Batas kecepatan X (X) 1-86 Kecepatan Trip Rendah[RPM]

50 Kalibrasi AMA gagal X

51 AMA periksa Unom dan Inom X

52 AMA Inom rend X

53 Motor AMA terlalu besar X

54 Motor AMA terlalu kecil X

55 Parameter AMA di luar jangkauan X

56 AMA diputus oleh pengguna X

57 Timeout AMA X

58 Masalah internal AMA X X

59 Batas arus X

60 Interlock Eksternal X

62 Frekuensi Keluaran pada Batas Maksimum X

64 Batas Tegangan X

65 Papan Kontrol Suhu-lebih X X X

66 Heat sink Suhu Rendah X

67 Konfigurasi Opsi sudah Berubah X

69 Pwr. Suhu Kartu X X

70 Konfigurasi FC td benar X

71 PTC 1 Berhenti Aman X X1)

72 Bahaya Gagal X1)

73 Henti Auto Restart

76 Pengaturan unit power X

77 Md Daya Kurang

79 Konfig PS bnr X X

80 Inisialisasi Drive ke Nilai Standar X

91 Pengaturan masukan analog 54 salah X

92 TidakadaAliran X X 22-2*

93 Pompa Kering X X 22-2*

94 Ujung Kurva X X 22-5*

95 Sabuk Putus X X 22-6*

96 Start Ditunda X 22-7*

97 Stop Ditunda X 22-7*

98 Masalah Jam X 0-7*

201 M Kebakaran Aktif

202 Batas M Kebakaran Terlampaui

203 Motor Tidak Ada

204 Rotor terkunci

243 IGBT Rem X X

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 57

8 8

Page 62: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

No. Keterangan Peringatan

Alarm/Trip Alarm/TripTerkunci

Referensi Parameter

244 Suhu heatsink X X X

245 Heatsink sensor X X

246 Pasokan k daya X X

247 Suhu kartu daya X X

248 Konfig PS bnr X X

250 Suku cadang baru X

251 Kode Jenis Baru X X

Tabel 8.2 Daftar Kode Alarm/Peringatan

(X) Tergantung parameter1) Tidak bisa Setel ulang otomatis lewat 14-20 Mode Reset

Informasi peringatan/alarm di bawah ini menentukankondisi peringatan/alarm, yang menyediakan penyebabkemungkinan untuk kondisi, dan perbaikan detail atauprosedur pemecahanmasalah

PERINGATAN 1, 10 Volt rendahTegangan kartu kontrol di bawah 10V dari terminal 50.Hilangkan beberapa beban dari terminal 50, karena bebanpasokan 10 V terlalu berlebih. Maks. 15 mA atau minimum590 Ω.

Kondisi ini dapat disebabkan oleh sambungan potenti-ometer pendek atau kabel yang tidak sesuai padapotentiometer.

Pemecahan masalahMelepaskan kabel dari terminal 50. Apabila peringatanjelas, masalah ada di kabel pelanggan. Apabila peringatantidak jelas, ganti kartu kontrol.

PERINGATAN/ALARM 2, Arus/Tegangan Terlalu RendahPeringatan atau alarm ini hanya muncul apabila diprogramoleh pengguna di 6-01 Fungsi Istirahat arus/teg. t'lalu rdh.Sinyal pada satu dari salah satuinput analog kurang dari50% dari nilai minimum yang diprogram untuk inputtersebut. Kerusakan kabel atau kesalaham perangkat yangmengirim sinyal dapat menyebabkan kondisi ini.

Pemecahan masalahPeriksa koneksi pada semua terminalinput.analog. Terminal kartu kontrol 53 dan 54untuk sinyal, terminal 55 umum. MCB 101terminal 11 dan 12 untuk sinyal, terminal 10umum. MCB 109 terminal 1,3, 5 untuk sinyal,terminal 2, 4, 6 umum).

Periksa bahwa pengaturan program konverterfrekuensi dan switch cocok dengan jenis sinyalanalog.

Melakukan Tes Sinyal Terminal Input.

PERINGATAN/ALARM 4, Fasa listrik hilangSatu fasa hilang pada bagian pasokan, atau ketidakseim-bangan tegangan listrik terlalu tinggi. Pesan ini jugamuncul untuk masalah dalam penyearah input pada

konverter frekuensi. Opsi diprogram pada 14-12 Fungsi pdKetidak-seimbangan Sumb..

Pemecahan masalahPeriksa tegangan pasokan dan arus pasokan ke konverterfrekuensi.

PERINGATAN 5, Tegangan hubungan DC tinggiRangkaian tegangan lanjutan (DC) lebih tinggi dari batasperingatan tegangan tinggi. Batas tergantung padategangan konverter frekuensi yang terukur. Unit masihaktif.

PERINGATAN 6, Tegangan hubungan DC rendahTegangan sirkuit lanjutan (DC) lebih rendah dari batasperingatan tegangan rendah. Batas tergantung padategangan konverter frekuensi yang terukur. Unit masihaktif.

PERINGATAN/ALARM 7, DC tegangan berlebihJika tegangan rangkaian lanjutan melampaui batas,konverter frekuensi akan mengalami trip setelah waktutertentu.

Pemecahan masalahSambungkan dengan tahanan rem

Panjangkan waktu ramp

Ubah jenis ramp

Aktifkan fungsi di 2-10 Fungsi Brake

Tambah 14-26 Pnunda.Trip pd Krusak Pmblk.

Apabila alarm/peringatan terjadi selama dayamenurun, solusinya menggunakan cadangankinetik (14-10 Kegagalan di Sumber)

PERINGATAN/ALARM 8, DC kekurangan teganganApabila tegangan sirkuit lanjutan (hubungan DC) turundibawah batas tegangan, konverter frekuensi memeriksaapabila pasokan cadangan 24 V DC terhubung. Jika tidakada pasokan cadangan 24 V DC yang terhubung, konverterfrekuensi akan mengalami trip setelah waktu yangditetapkan tertunda. Penundaan waktu bervariasi denganukuran unit.

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

58 MG11AI9B - VLT® merek dagang terdaftar Danfoss

88

Page 63: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Pemecahan masalahPeriksa bahwa tegangan pasokan cocok dengantegangan konverter frekuensi.

Melakukan tes Tegangan Input.

Melakukan pemeriksaan ringan tes sirkuit.

PERINGATAN/ALARM 9, Inverter kelebihan bebanKonverter frekuensi akan berhenti bekerja karena kelebihanbeban (arus terlalu tinggi dalam waktu yang terlalu lama).Penghitung untuk proteksi inverter termal elektronikmemberikan peringatan pada 98% dan akan mengalamitrip pada 100%, dan alarm akan berbunyi. Konverterfrekuensi tidak dapat direset hingga penghitung berada dibawah 90%. Masalahnya, bahwa konverter frekuensi beroperasi denganbeban berlebih lebih dari 100% untuk waktu yang terlalulama.

Pemecahan masalahPerbandingan arus output terlihat di keypaddengan arus pengukuran konver frekuensi.

Perbandingan arus keluaran terlihat pada LCPdengan arus motor yang terukur.

Menampilkan Beban Drive Termal pada LCP danmonitor nilai. Ketika sedang berjalan diataskonverter frekuensi secara terus-menerus padaarus yang terukur, penghitung ditingkatkan.Ketika sedang berjalan di bawah konverterfrekuensi secara terus-menerus pada arus yangterukur, penghitung menurunkan

PERINGATAN/ALARM 10, Kelebihan beban pada motorMenurut proteksi termal elektronik (ETR), motor terlalupanas. Pilih apabila konverter frekuensi memberikanperingatan atau alarm ketika penghitung mencapai 100%di 1-90 Proteksi pd termal motor. Kerusakannya terjadi padasaat motor beroperasi di atas 100% untuk waktu yangterlalu lama.

Pemecahan masalahPeriksa untuk motor kepanasan.

Periksalah apabila motor secara mekanikkelebihan beban

Periksa bahwa arus motor diatur di 1-24 ArusMotor telah benar.

Data motor di parameter 1-20 melalui 1-25ditetapkan secara benar.

Apabila kipas eksternal telah digunakan, periksadi1-91 Kipas Eksternal Motor yang telah terpilih.

Jalankan Penalaan 1-29 Penyesuaian MotorOtomatis (AMA) AMA di dapat mengaturpengontrol frekuensi ke motor lebih akurat danmengurangi beban thermal.

PERINGATAN/ALARM 11, Suhu thermistor motor terlalutinggiPeriksa apakah thermistor terputus. Pilih apabila konverterfrekuensi memberikan peringatan atau alarm di1-90 Proteksi pd termal motor.

Pemecahan masalahPeriksa untuk motor kepanasan.

Periksalah apabila motor secara mekanikkelebihan beban.

Pada saat menggunakan terminal 53 atau 54,periksa thermistor untuk disambung secara benarantara terminal 53 atau 54 (input tegangananalog) dan terminal 50 (pasokan +10 V). Jugaperiksa saklar terminal untuk 53 atau 54 diaturuntuk tegangan. Periksa 1-93 Sumber Thermistormemilih terminal 53 atau 54.

Pada saat menggunakan input digital 18 atau 19,periksalah thermistor tersambung secara benarantara terminal 18 atau 19 (haya input digitalPNP) dan terminal 50. Periksa 1-93 SumberThermistor memilih terminal 18 atau 19.

PERINGATAN/ALARM 12, Batas TorsiTorsi telah melebihi angka di 4-16 Mode Motor BatasanTorsi atau angka di 4-17 Mode generator Batasan Torsi.14-25 Penundaan Trip pada Batasan Torsi dapatmengubahnya hanya dari kondisi peringatan ke peringatanberikut yang diikuti oleh alarm.

Pemecahan masalahApabila batas torsi motor melebihi selama rampatas, perpanjang waktu ramp atas.

Apabila batas torsi generator melebihi selamaramp bawah, perpanjang waktu ramp bawah.

Apabila batas torsi terjadi pada saat beroperasi,tingkatkan batas torsi yang memungkinkan.Pastikan sistem dapat beroperasi secara amanpada torsi yang lebih tinggi.

Periksa aplikasi untuk arus yang berlebih padamotor.

PERINGATAN/ALARM 13, Arus lebihBatas arus puncak inverter (kira-kira 200% dari arus yangterukur) terlampaui. Peringatan akan berakhir sekitar 1.5detik, dan konverter frekuensi akan mengalami trip danmembunyikan alarm. Kesalahan ini disebabkan oleh bebankejutan atau akselerasi cepat dengan beban inersia tinggi.Dapat juga terlihat setelah cadangan kinetik apabilaakselerasi selama ramp atas cepat. Jika perpanjangankontrol rem mekanis yang dipilih, trip bisa diatur ulangsecara eksternal.

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 59

8 8

Page 64: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Pemecahan masalahLepaskan daya dan periksa apabila poros motordapat diputar.

Periksa untuk ukuran motor dapat sesuai dengankonverter frekuensi.

Periksa parameter 1-20 sampai ke 1-25. periksadata motor.

ALARM 14, Masalah pembumian (tanah)Terdapat arus dari fasa output ke pembumian, baik didalam kabel di antara konverter frekuensi dan motor,maupun di dalam motor itu sendiri.

Pemecahan masalah:Lepaskan daya ke konverter frekuensi danperbaiki masalah arde.

Periksa untuk masalah arde di motor denganmengukur resistensi ke arde dari motor danmotor dengan megohmmeter.

ALARM 15, Ketidakcocokan perangkat kerasPilihan sesuai tidak beroperasi dengan perangkat keraspapan kontrol yang ada atau perangkat lunak.

Catat nilai dari parameter berikut ini dan hubungi pemasokDanfoss anda:

15-40 Jenis FC

15-41 Bagian Daya

15-42 Tegangan

15-43 Versi Perangkat Lunak

15-45 Untaian Jenis kode Aktual

15-49 Kartu Kontrol ID SW

15-50 Kartu Daya ID SW

15-60 Pilihan Terangkai

15-61 Versi SW Pilihan (untuk setiap slot pilihan)

ALARM 16, Sirkuit pendekTerdapat sirkuit-pendek di motor atau kabel motor.

Lepaskan daya ke konverter frekuensi dan perbaiki sirkuitpendek.

PERINGATAN/ALARM 17, Timeout kata kontrolTak ada komunikasi ke konverter frekuensi.Peringatan hanya menjadi aktif bila 8-04 Fungsi IstirahatKata Kontrol TIDAK diatur ke [0] [Off].Apabila 8-04 Fungsi Istirahat Kata Kontrol diatur ke Stop [5]dan Trip, peringatan muncul dan penurunan ramp bawahsampai berhenti dan kemudian menampilkan alarm.

Pemecahan masalah:Periksa sambungan pada kabel komunikasi serial.

Tambah 8-03 Waktu Istirahat Kata Kontrol

Periksa operasi dari peralatan komunikasi.

Pastikan instalasi yang benar didasarkan padapersyaratan EMC.

ALARM 18, Start gagalKecepatan tidak mampu melebihi 1-77 Kecepatan Start MaxCompressor [RPM] selama mulai diantara waktu yangmemungkinkan.(atur di 1-79 Waktu Start Max Kompressorhingga trip). Hal ini dapat disebabakan oleh motor yangdiblok.

PERINGATAN 23, Masalah kipas internalFungsi peringatan kipas merupakan fungsi perlindungantambahan yang akan memeriksa apakah kipas berjalan/dipasang. Peringatan kipas dapat dinonaktifkan pada14-53 Monitor Kipas ([0] Nonaktif).

Untuk filter Frame D, E, dan F, peraturan arus tegangan kekipas dimonitor.

Pemecahan masalahPeriksa untuk operasi kipas yang benar.

Putaran daya ke konverter frekuensi dan periksakipas telah beroperasi secara singkat padapermulaan.

Periksa sensor pada heatsink dan kartu kontrol.

PERINGATAN 24, Masalah kipas eksternalFungsi peringatan kipas merupakan fungsi perlindungantambahan yang akan memeriksa apakah kipas berjalan/dipasang. Peringatan kipas dapat dinonaktifkan pada14-53 Monitor Kipas ([0] Nonaktif).

Pemecahan masalahPeriksa untuk operasi kipas yang benar.

Putaran daya ke konverter frekuensi dan periksakipas telah beroperasi secara singkat padapermulaan.

Periksa sensor pada heatsink dan kartu kontrol.

PERINGATAN 25, Sirkuit pendek tahanan remTahanan rem dimonitor sewaktu operasi. Apabila sirkuitpendek terjadi, fungsi rem dinonaktifkan dan munculperingatan. Konverter fungsi masih beroperasional tetapitanpa fungsi rem. Lepas daya ke konverter frekuensi danganti resistor rem (lihat 2-15 Cek Brake).

PERINGATAN/ALARM 26, Batas daya tahanan remDaya yang dialihkan ke resistor rem dihitung sebagaijumlah angka terhadap waktu berjalan dalam kurun 120detik terakhir. Kalkulasi didasarkan pada tegangan sirkuitlanjutan dan angka resistensi rem ditetapkan di 2-16 ArusMaks. rem AC. Peringatan akan aktif bila pemborosan remlebih tinggi dari 90% dari daya resistensi rem. Apabila Trip[2] terpilih di 2-13 Pemantauan Daya Brake, konverterfrekuensi akan trip pada saat pemborosan dayapengereman mencapai 100%.

PERINGATAN/ALARM 27, Masalah pemotong remTransistor rem dimonitor selama beroperasi dan apabilasirkuit pendek terjadi, fungsi rem dinonaktifkan danperingatan akan muncul. Konverter frekuensi akan tetapberoperasi, tetapi karena ada hubung singkat padatransistor rem, maka daya yang jumlahnya cukup besar

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

60 MG11AI9B - VLT® merek dagang terdaftar Danfoss

88

Page 65: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

akan dialihkan ke tahanan rem, walaupun alat sedang tidakaktif.Lepaskan daya ke konverter frekuensi dan gantilah tahananrem.

PERINGATAN/ALARM 28, Pemeriksaan rem telah gagalTahanan rem tidak terhubung atau tidak bekerja.Periksa 2-15 Cek Brake.

ALARM 29, Suhu heatsinkSuhu maksimum heatsink sudah dilampaui. Masalah suhutidak dapat me-reset ulang sampai suhu turun di bawahsuhu heatsink yang ditentukan. Trip dan poin resetberbeda didasarkan pada ukuran daya konverter frekuensi.

Pemecahan masalahPeriksa untuk kondisi berikut.

Suhu sekitar terlalu tinggi.

Kabel motor terlalu panjang.

Penghapusan aliran udara di atas dan dibawahkonverter frekuensi tidak benar.

Aliran udara yang diblok disekeliling konverterfrekuensi.

Kipas heatsink rusak.

Heatsink kotor.

ALARM 30, Fasa motor U hilangFasa motor U antara konverter frekuensi dan motor telahhilang.

Lepaskan daya dari konverter frekuensi dan periksa fasamotor U.

ALARM 31, Fasa motor V hilangFasa motor V antara konverter frekuensi dan motor telahhilang.

Hilangkan daya dari konverter frekuensi dan periksa fasamotor V.

ALARM 32, Fasa motor W hilangFasa motor W antara konverter frekuensi dan motor telahhilang.

Lepaskan daya dari konverter frekuensi dan periksa fasamotor W.

ALARM 33, Inrush rusakTerlalu banyak terjadi kenaikan daya dalam waktu yangsingkat. Memungkinkan pendinginan unit untuk mengope-rasikan suhu.

PERINGATAN/ALARM 34, Masalah komunikasi fieldbusfieldbus di kartu opsi komunikasi pada fieldbus tidakbekerja secara benar.

PERINGATAN/ALARM 36, Gagal hantaranPeringatan/alarm ini hanya aktif apabila pasokan teganganke konverter frekuensi hilang dan 14-10 Kegagalan powerlistrik TIDAK diatur ke [0] Tidak ada Fungsi. Periksa sekeringke konverter frekuensi dan pasokan daya hantaran listrik keunit.

ALARM 38, Masalah internalPada saat masalah internal terjadi, nomor kode yangditentukan tabel di Tabel 8.3 ditampilkan.

Pemecahan masalahPutaran daya

Periksa bahwa opsi diinstal secara benar

Periksa untuk pelepasan atau hilangnya kabel

Penting untuk menghubungi Danfoss pemasok ataulayanan departemen Anda. Catatan nomor kode untukarah pemecah masalah lebih lanjut.

No. Teks0 Port serial tidak dapat diinisialisasi. Hubungi

pemasok Danfoss atau LayananDepartemenDanfoss Anda.

256-258 Data EEPROM daya rusak atau terlalu tua. Gantikartu daya.

512-519 Masalah intern. Hubungi pemasok Danfoss atauLayanan DepartemenDanfoss Anda.

783 Nilai parameter di luar batas dari batas min/maks

1024-1284 Masalah intern. Hubungi Danfoss pemasok atauDanfoss Departemen Layanan Anda.

1299 Opsi SW pada slot A terlalu tua

1300 Opsi SW pada slot B terlalu tua

1315 Opsi SW pada slot A tidak didukung (tidakdiizinkan)

1316 Opsi SW pada slot B tidak didukung (tidakdiizinkan)

1379-2819 Masalah intern. Hubungi pemasok Danfoss atauLayanan DepartemenDanfoss Anda.

2561 Ganti kartu kontrol

2820 Stack overflow LCP

2821 Port serial overflow

2822 Port USB overflow

3072-5122 Nilai parameter di luar batas

5123 Opsi dalam slot A: Perangkat keras tidakkompatibel dengan perangkat keras Papan kontrol

5124 Opsi dalam slot B: Perangkat keras tidakkompatibel dengan perangkat keras Papan kontrol

5376-6231 Masalah intern. Hubungi pemasok Danfoss atauLayanan DepartemenDanfoss Anda.

Tabel 8.3 Masalah Internal Kode

ALARM 39, Heatsink sensorTidak ada umpan balik dari sensor suhu heat sink.

Sinyal dari sensor termal IGBT tidak tersedia pada kartudaya. Masalah mungkin ada pada kartu daya, pada kartudrive gate, atau kabel ribbon antara papan daya dan kartudrive gate.

PERINGATAN 40, Lebih beban pada terminal keluarandigital 27Periksa beban terkoneksi ke terminal 27 atau hilangkankoneksi hubung singkat. Periksa 5-00 Mode I/O Digital dan5-01 Mode Terminal 27.

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 61

8 8

Page 66: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

PERINGATAN 41, Lebih beban pada terminal keluarandigital 29Periksa beban terkoneksi ke terminal 29 atau hilangkankoneksi hubung singkat. Periksa 5-00 Mode I/O Digital dan5-02 Terminal 29 Mode.

PERINGATAN 42, Lebih beban Keluaran Digital pada X30/6atau Lebih Beban Keluaran Digital pada X30/7Untuk X30/6, periksa beban terkoneksi ke X30/6 atauhilangkan koneksi hubungan singkat. Periksa 5-32 TermX30/6 Digi Out (MCB 101).

Untuk X30/7, periksa beban terkoneksi ke X30/7 atauhilangkan koneksi hubungan singkat. Periksa 5-33 TermX30/7 Digi Out (MCB 101).

ALARM 45, Masalah arde 2Masalah Pembumian (tanah) pada permulaan.

Pemecahan masalahPeriksa untuk pembumian (arde) yang benar danlepaskan sambungan.

Periksa untuk ukuran kabel yang benar.

Periksa kabel motor untuk sirkuit pendek atauarus bocor.

ALARM 46, Pasokan kartu dayaPasokan pada kartu daya melebihi kapasitas.

Ada tiga pasokan daya yang dibuat oleh pasokan dayamodus switch (SMPS) pada kartu daya: 24 V, 5 V, ± 18 V.Ketika didayakan dengan 24 V DC dengan opsi MCB 107,hanya pasokan 24 V dan 5 V dimonitor. Ketika didayakandengan tegangan hantaran listrik tiga fasa, ketiga pasokantersebut dimonitor.

Pemecahan masalahPeriksa untuk kartu daya yang rusak.

Periksa untuk kartu kontrol yang rusak.

Periksa untuk kartu opsi yang rusak.

Apabila pasokan daya 24 V DC digunakan,pastikan pasokan daya yang sesuai.

PERINGATAN 47, Pasokan 24 V rendah24 V DCV diukur pada kartu kontrol. Pasokan daya DC 24 Veksternal mungkin kelebihan beban, jika tidak hubungipemasok Danfoss anda.

PERINGATAN 48, Pasokan 1,8 V rendahPasokan 1,8 V DC yang digunakan pada kartu kontrolberada di luar batas yang diperbolehkan. Pasokan dayadiukur pada kartu kontrol. Periksa untuk kartu kontrol yangrusak. Apabila kartu opsi telah ada, periksa untuk kondisitegangan yang berlebih.

PERINGATAN 49, Batas kecepatanKetika kecepatan tidak di kisaran jangkauan yangditentukan pada 4-11 Batasan Rendah Kecepatan Motor[RPM] dan 4-13 Batasan Tinggi Kecepatan Motor [RPM],,konverter frekuensi muncul peringatan. Ketika kecepatandibawah batas yang ditentukan pada 1-86 Kecepatan Trip

Rendah [RPM] (kecuali ketika memulai atau berhenti), driveakan mengalami trip.

ALARM 50, Kalibrasi AMA gagalHubungi pemasok Danfoss atau LayananDepartemenDanfoss Anda.

ALARM 51, AMA periksa Unom dan Inom

Pengaturan tegangan motor, arus motor dan daya motormungkin salah. Periksa pengaturan di parameter 1-20 ke1-25.

ALARM 52, AMA Inom rendahArus motor terlalu lemah. Periksa pengaturan.

ALARM 53, Motor AMA terlalu besarMotor terlalu besar untuk Penalaan otomatis untukberoperasi.

ALARM 54, Motor AMA terlalu kecilMotor terlalu kecil untuk melaksanakan AMA.

ALARM 55, AMA Parameter di luar jangkauanNilai parameter dari motor berada di luar jangkauan yangditerima. AMA tidak akan bekerja.

ALARM 56, AMA diputus oleh penggunaPengguna diputus oleh AMA.

ALARM 57, Masalah internal AMACoba memulai AMA kembali. Pengulangan memulaikembali dapat terjadi kepanasan pada motor

ALARM 58, AMA masalah internalHubungi pemasok Danfoss anda.

PERINGATAN 59, Batas arusArus motor di atas dari nilai pada 4-18 Batas Arus. Datamotor di parameter 1-20 sampai ke 1-25 ditetapkan secarabenar. Tambahkan batas arus. Pastikan sistem dapatberoperasi secara aman pada batas yang lebih tinggi.

PERINGATAN 60, Interlock eksternalSinyal input digital menunjukkan masalah kondisi eksternalke konverter frekuensi. Interlock eksternal memerintahkonverter frekuensi ke trip. Hapus kondisi masalaheksternal. Untuk melanjutkan operasi normal, tetapkan 24V DC ke terminal yang diprogram untuk interlock eksternal.Reset konverter frekuensi.

PERINGATAN 62, Frekuensi Keluaran pada batas maksimumFrekuensi output telah mencapai nilai yang ditetapkan di4-19 Frekuensi Output Maks.. Periksa aplikasi untukmenentukan penyebab. Peningkatan batas frekuensioutput. Pastikan sistem dapat beroperasi secara aman padafrekuensi output yang lebih tinggi. Peringatan akan hilangpada saat output turun di bawah batas maksimum.

PERINGATAN/ALARM 65, Kartu kontrol lebih suhuSuhu untuk menghentikan kerja kartu kontrol adalah 80°C.

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

62 MG11AI9B - VLT® merek dagang terdaftar Danfoss

88

Page 67: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Pemecahan masalah

• Periksa suhu operasi untuk batas su operasi disekitarnya

• Periksa untuk filter yang tersumbat

• Periksa operasi kipas

• Periksa kartu kontrol

PERINGATAN 66, Suhu heatsink rendahKonverter frekuensi terlalu dingin untuk beroperasi.Peringatan ini didasarkan pada sensor suhu pada modulIGBT.Tambahkan suhu sekitar dari unit. Dan juga, arus aliranyang kecil dapat dipasok ke pengontrol frekuensi kapansaja motor dihentikan dengan mengatur 2-00 Arus PenahanDC/Prapanas di 5% dan 1-80 Fungsi saat Stop

ALARM 67, Opsi modul konfigurasi sudah berubahSatu atau beberapa opsi telah ditambahkan atau dihapussejak daya yang terakhir kali turun. Periksa bahwaperubahan konfigurasi ditujukan dan melakukan reset.

ALARM 68, Penghentian Aman diaktifkanHilangnya sinyal 24 V DC pada terminal 37 menyebabkanmenjadi trip. Untuk melanjutkan operasi normal, tetapkan24 V DC ke terminal 37 dan reset filter.

ALARM 69, Suhu kartu dayaSensor suhu pada kartu daya terlalu panas atau dingin.

Pemecahan masalahPeriksa suhu operasi untuk batas su operasi disekitarnya.

Periksa untuk filter yang tersumbat.

Periksa operasi kipas.

Periksa kartu daya.

ALARM 70, Konfigurasi Konverter Frekuensi Tidak SahKartu kontrol dan kartu daya tidak cocok. Hubungipemasok Anda dengan kode jenis unit dari pelat nama danjumlah bagian dari kartu untuk memeriksa kecocokan.

ALARM 80, Inisialisasi Drive ke nilai standarPengaturan parameter diinisialisasikan ke pengaturanstandar setelah reset manual. Reset unit untuk menghapusalarm.

ALARM 92, Tiada aliranTidak ada kondisi aliran yang terdeteksi di sistem.22-23 Fungsi Tiada Aliran diatur untuk alarm. Sistempemecahan masalah dan reset konverter frekuensi setelahmasalah telah terselesaikan.

ALARM 93, Pompa keringTidak ada kondisi aliran pada sistem dengan pengope-rasian konverter frekuensi di kecepatan yang tinggi dapatmenunjukkan pompa Kering. 22-26 Fungsi Pompa Keringdiatur untuk alarm. Sistem pemecahan masalah dan resetkonverter frekuensi setelah masalah telah terselesaikan.

ALARM 94, Ujung kurvaUmpan balik lebih rendah dari poin set. Hal inimenunjukkan kebocoran pada sistem. 22-50 Akhir dr FungsiKurva diatur untuk alarm. Sistem pemecahan masalah danreset konverter frekuensi setelah masalah telah tersele-saikan.

ALARM 95, Sabuk putusTorsi di bawah tingkat torsi untuk tidak ada beban,menunjukkan sabuk putus. 22-60 Fungsi Belt Putus diaturuntuk alarm. Sistem pemecahan masalah dan resetkonverter frekuensi setelah masalah telah terselesaikan.

ALARM 96, Start ditundaStart motor telah ditunda karena proteksi putaran pendek.22-76 Interval antara Start diaktifkan. Sistem pemecahanmasalah dan reset konverter frekuensi setelah masalahtelah terselesaikan.

PERINGATAN 97, Stop ditundaPemberhentian motor telah ditunda karena proteksiputaran pendek. 22-76 Interval antara Start diaktifkan.Sistem pemecahan masalah dan reset konverter frekuensisetelah masalah telah terselesaikan.

PERINGATAN 98, Masalah jamWaktu tidak diatur atau jam RTC gagal. Reset jam di0-70 Tanggal dan Waktu.

PERINGATAN 200, Mode kebakaranPeringatan ini menunjukkan konverter frekuensi yangdioperasikan di modus kebakaran. Peringatan menjadihilang pada saat modus kebakaran tidak aktif. Lihat datamodus kebakaran di log alarm.

PERINGATAN 201, Modus kebakaran aktifIni menunjukan konverter frekuensi telah masuk ke moduskebakaran. Daya cycle ke unit untuk menghilangkanperingatan. Lihat data modus kebakaran di log alarm.

PERINGATAN 202, Modus kebakaran batas terlampauiPada saat mengoperasikan modus kebakaran, kondisi satualarm atau lebih telah diabaikan di mana secara normalterjadi trip pada unit. Pengoperasian pada kondisi inimembatalkan garansi unit. Daya cycle ke unit untukmenghilangkan peringatan. Lihat data modus kebakaran dilog alarm.

PERINGATAN 203, Motor tidak adaDengan konverter frekuensi mengoperasikan multi-motor,kondisi di bawah-beban terdeteksi. Hal ini menunjukkanmotor yang hilang. Periksa sistem untuk operasi yangsesuai.

PERINGATAN 204, Rotor terkunciDengan konverter frekuensi mengoperasikan multi-motorkondisi kelebihan beban terdeteksi. Ini membuat rotorterkunci. Memeriksa motor untuk pengoperasian yangbenar.

PERINGATAN 250, Suku cadang baruKomponen di konverter frekuensi telah diganti. Resetkonverter frekuensi untuk operasi normal.

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 63

8 8

Page 68: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

PERINGATAN 251, Kodejenis baruKartu daya atau komponen lain telah diganti dan kodejenisberubah. Reset untuk menghilangkan peringatan danlanjutkan operasi normal.

Peringatan dan Alarm VLT® Petunjuk Operasional Drive HVAC

64 MG11AI9B - VLT® merek dagang terdaftar Danfoss

88

Page 69: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

9 Dasar Pemecahan masalah

9.1 Memulai dan Operasi

Gejala Penyebab kemungkinan Pengujian Solusi

Tampilan gelap/Tidak adafungsi

Daya input tidak ada Lihat Tabel 3.1 Periksa sumber daya input

Sekering hilang atau bukasekering atau pemotong sirkuit ditrip

Lihat buka sekering dan pemotongsirkuit trip pada tabel ini untukpenyebab kemungkinan

Rekomendasi berikut disediakan

Tidak ada daya ke LCP Periksa kabel LCP untuksambungan yang benar atau rusak

Ganti kabel yang bermasalah LCPatau sambungan

Cara pintas di tegangan kontrol(terminal 12 atau 50) atau padaterminal kontrol

Periksa pasokan/masukan tegangankontrol 24 V untuk pasokanterminal 12/13 ke 20-39 atau 10 Vuntuk terminal 50 ke 55

Menyambung terminal secarabenar

Salah LCP (LCP dari VLT® 2800atau 5000/6000/8000/ FCD atauFCM)

Gunakan hanya LCP 101 (P/N130B1124) atau LCP 102 (P/N130B1107)

Pengaturan kontras salah Tekan [Status] + []/[] untuk

menyesuaikan kontras

Tampilan (LCP) rusak Uji menggunakan LCP yangberbeda

Ganti kabel yang bermasalah LCPatau sambungan

Pasokan/masukan teganganinternal atau SMPS rusak

Hubungi pemasok

Tampilan sesekali

Pasokan daya kelebihan beban(SMPS) karena sambungan kontrolyang tidak benar atau masalahdiantara konverter frekuensi

Untuk memecahkan masalah dikabel kontrol, putuskan semuakabel kontrol dengan melepas blokterminal.

Apabila tampilan tetap menyala,masalah ada di kabel kontrol.Periksa kabel untuk sambunganpendek atau tidak benar. Apabilatampilan tidak tampak, ikutiprosedur untuk tampilan gelap.

Dasar Pemecahan masalah VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 65

9 9

Page 70: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Gejala Penyebab kemungkinan Pengujian Solusi

Motor tidak bekerja

Saklar layanan terbuka atausambungan motor hilang

Periksa apabila motor tersambungdan sambungan tidak diganggu(oleh saklar layanan atau perangkatlain).

Sambung motor dan periksa saklarlayanan

Tidak ada daya hantaran listrikdengan kartu opsi 24 V DC

Apabila tampilan berfungsi tetapitidak ada output, periksa dayahantaran listrik yang ditetapkan kekonverter frekuensi.

Terapkan daya hantaran listrikuntuk jalankan unit

LCP Stop Periksa apabila [Tidak aktif] telahditekan

Tekan [Otomatis Aktif] atau[Tangan Aktif] (tergantung padamodus operasi) untuk jalankanmotor

Sinyal start hilang (Standby) Periksa 5-10 Terminal 18 InputDigital untuk pengaturan yangbenar untuk terminal 18 (gunakanpengaturan standar)

Terapkan sinyal start yang berlakuuntuk mulai motor

Sinyal luncur motor aktif(Meluncur)

Periksa 5-12 Peluncuran terbalikuntuk pengaturan yang benar diterminal 27 (gunakan pengaturanstandar)..

Tetapkan 24 V pada terminal 27atau program terminal ini ke Tidakada operasi

Sumber sinyal referensi salah Periksa sinyal referensi: Lokal, jauhatau referensi bus? Referensi pra-setel aktif? Sambungan terminalbenar? Ukurang terminal benar?Sinyal referensi tersedia?

Program pengaturan yang benar.Periksa 3-13 Situs Referensi. Aturreferensi pra-setel aktif di grupReferensi 3-1*. Periksa untuk kabelyang benar. Periksa ukuranterminal. Periksa sinyal referensi.

Motor berjalan di arah yangsalah

Batas rotasi motor Periksalah apakah 4-10 ArahKecepatan Motor telah diaturdengan benar.

Program pengaturan yang benar

Aktifkan sinyal pembalikan Periksa apabila perintahpembalikan telah diprogram untukterminal di grup parameter inputDigital 5-1*..

Nonaktifkan sinyal pembalikan

Sambungan fasa motor salah Lihat 3.7 Periksa Rotasi Motor dimanual ini

Motor tidak mencapaikecepatan maksimum

Batas frekuensi diatur salah Periksa batas output di4-13 Batasan Tinggi KecepatanMotor [RPM], 4-14 Batasan TinggiKecepatan Motor [Hz] dan4-19 Frekuensi Output Maks..

Program batas yang benar

Sinyal input referensi tidak diukursecara benar

Periksa penskalaan sinyal inputreferensi di modus I/O Analog 6-0*dan grup parameter Referensi 3-1*.Batas referensi di grup parameter3-0* Batas Referensi.

Program pengaturan yang benar

Kecepatan motor tidakstabil

Parameter parameter tidak benar Periksa semua pengaturanparameter motor, termasuk semuapengaturan kompensasi motor.Untuk operasi loop tertutup,periksa pengaturan PID.

Periksa pengaturan di grupparameter modus Analog I/O 6-0*.Untuk operasi loop tertutup,periksa pengaturan di grupparameter Umpan-balik 20-0*..

Motor berjalan kasar

Magnetisasi berlebih Periksa untuk pengaturan motortidak benar di semua parametermotor

Periksa pengaturan motor di grupparameter 1-2* Data motor, 1-3*Data motor Lanjut, dan 1-5* bebanIndep. Pengaturan.

Dasar Pemecahan masalah VLT® Petunjuk Operasional Drive HVAC

66 MG11AI9B - VLT® merek dagang terdaftar Danfoss

99

Page 71: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Gejala Penyebab kemungkinan Pengujian Solusi

Motor tidak akan berhentiPengaturan tidak benar diparameter rem. Terlalu pendekwaktu ramp bawah

Periksa parameter rem. Periksapengaturan waktu ramp

Periksa grup parameter Rem DC2-0* dan batas Referensi 3-0*.

Buka sekering daya atautrip pemotong sirkuit

Fasa ke fasa singkat Motor atau panel mempunyaihubungan fasa ke fasa yangsingkat. Periksa fasa motor danpanel untuk hubungan singkat

Penghapusan hubungan singkatterdeteksi

Kelebihan beban pada motor Motor kelebihan beban untukaplikasi

Menjalankan uji permulaan danmemeriksa arus motor diantaraspesifikasi. Apabila arus motormelebihi arus beban namapelatpenuh, motor hanya berjalandengan pengurangan beban.Mengulas spesifikasi untuk aplikasi.

Sambungan hilang Melakukan pra-permulaan periksauntuk sambungan yang hilang

Kencangkan kenduran sambungan

Arus listrik yang tidakseimbang lebih besar dari3%

Masalah dengan daya hantaranlistrik (Lihat deskripsi kehilanganfasa hantaran listrik 4 Alarm)

Putar daya input ke posisi satukonverter frekuensi: A ke B, B ke C,C ke A.

Apabila ketidakseimbangan kakimengikuti kabel, hal itu merupakanmasalah daya. Periksa pasokandaya daya sumber listrik.

Masalah dengan konverterfrekuensi

Putar daya input ke posisi satukonverter frekuensi: A ke B, B ke C,C ke A.

Apabila ketidakseimbangan kakipada terminal input yang sama, haltersebut merupakan masalahdengan unit. Hubungi pemasok.

Ketidakseimbangan arusmotor lebih besar dari 3%

Masalah dengan motor atau kabelmotor

Putar motor output ke posisipertama: U ke V, V ke W, W ke U.

Apabila ketidaseimbangan kakimengikuti kabel, masalahnyaberada di motor atau kabel motor.Periksa motor dan kabel motor.

Masalah dengan konverterfrekuensi

Putar motor output ke posisipertama: U ke V, V ke W, W ke U.

Apabila ketidakseimbangan kakitetap pada terminal output, haltersebut merupakan masalahdengan unit. Hubungi pemasok.

Derau akustik atau getaran(seperti pisau kipasmembuat suara ataugetaran pada frekuensitertentu)

Gema, seperti pada sistem motor/kipas

Membuat frekuensi kritikal bypassdengan menggunakan parameterdi grup parameter 4-6* KecepatanBypass

Periksa apabila suara dan/ataugetaran dapat dikurangi denganbatas yang dapat diterima

Menonaktifkan modulasi yangberlebih di 14-03 Kelebihanmodulasi.

Mengubah pattern switching danfrekuensi di grup parameter 14-0*Switching Inverter

Peningkatan Peredaman Resonansidi 1-64 Peredaman Resonansi.

Tabel 9.1 Pemecahan masalah

Dasar Pemecahan masalah VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 67

9 9

Page 72: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

10 Spesifikasi

10.1 Bergantung-daya Spesifikasi

Masukan hantaran listrik 200-240 V AC - Kelebihan beban normal 110% untuk 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P1K11.1

P1K51.5

P2K22.2

P3K03

P3K73.7

Sasis/IP20(A2+A3 dapat diubah ke IP21 dengan menggunakan kit konversi.(Lihat juga Pemasangan Mekanis dan IP21/Jenis 1 kit Penutup diPanduan Rancangan.))

A2 A2 A2 A3 A3

IP55/Jenis 12 A4/A5 A4/A5 A4/A5 A5 A5

IP66/NEMA 4X A4/A5 A4/A5 A4/A5 A5 A5

Keluaran Poros Tipikal [HP] pada 208 V 1.5 2.0 2.9 4.0 4.9

Arus keluaran

Berkelanjutan (3 x 200-240 V) [A] 6.6 7.5 10.6 12.5 16.7

Sesekali (3 x 200-240 V) [A] 7.3 8.3 11.7 13.8 18.4

Berkelanjutan kVA (208 V AC) [kVA] 2.38 2.70 3.82 4.50 6.00

Arus masukan maks.

Berkelanjutan (3 x 200-240 V) [A] 5.9 6.8 9.5 11.3 15.0

Sesekali (3 x 200-240 V) [A] 6.5 7.5 10.5 12.4 16.5

Spesifikasi tambahan

Perkiraan kehilangan daya pada beban maks. terukur [W] 4) 63 82 116 155 185

IP20, IP21 bagian penampang kabel maks (hantaran listrik, motor,

rem dan beban pemakaian bersama) [mm2 (AWG)]

4, 4, 4 (12, 12, 12)(min. 0.2 (24))

IP55, IP66 bagian penampang kabel maks (hantaran listrik, motor,

rem dan beban pemakaian bersama) [mm2 (AWG)]4, 4, 4 (12, 12, 12)

Bagian penampang kabel maks. dengan pemutusan 6, 4, 4 (10, 12, 12)

Penutup berat IP20 [kg] 4.9 4.9 4.9 6.6 6.6

Penutup berat IP21 [kg] 5.5 5.5 5.5 7.5 7.5

Penutup berat IP55 [kg] (A4/A5) 9.7/13.5 9.7/13.5 9.7/13.5 13.5 13.5

Penutup berat IP66 [kg] (A4/A5 9.7/13.5 9.7/13.5 9.7/13.5 13.5 13.5

Efisiensi 3) 0.96 0.96 0.96 0.96 0.96

Tabel 10.1 Pasokan Hantaran listrik 200-240 V AC

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

68 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 73: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Masukan hantaran listrik 3x200-240 V AC - Kelebihan beban normal 110% untuk 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P5K55.5

P7K57.5

P11K11

P15K15

P18K18.5

IP20/"Sasis(B3+4 dan C3+4 dapat diubah menjadi IP21 menggunakan kit konversi.(Lihat juga di item pemasangan Mekanik dan IP21/Jenis 1 kit Penutuppada Panduan Rancangan.))

B3 B3 B3 B4 B4

IP21/NEMA 1 B1 B1 B1 B2 C1

IP55/Jenis 12 B1 B1 B1 B2 C1

IP66/NEMA 4X B1 B1 B1 B2 C1

Keluaran Poros Tipikal [HP] pada 208 V 7.5 10 15 20 25

Arus keluaran

Berkelanjutan (3 x 200-240 V) [A] 24.2 30.8 46.2 59.4 74.8

Sesekali (3 x 200-240 V) [A] 26.6 33.9 50.8 65.3 82.3

Berkelanjutan kVA (208 V AC) [kVA] 8.7 11.1 16.6 21.4 26.9

Arus masukan maks.

Berkelanjutan (3 x 200-240 V) [A] 22.0 28.0 42.0 54.0 68.0

Sesekali (3 x 200-240 V) [A] 24.2 30.8 46.2 59.4 74.8

Spesifikasi Tambahan

Perkiraan kehilangan daya pada beban maks. terukur [W] 4) 269 310 447 602 737

Bagian penampang kabel maks. IP20 (hantaran listrik, rem, motor danbeban pemakaian bersama)

10, 10 (8,8-) 35,-,- (2,-,-) 35 (2) 50 (1)

IP21, IP55, IP66 bagian penampang kabel maks (hantaran listrik, motor)

[mm2/AWG]10, 10 (8,8-)

35, 25, 25(2, 4, 4)

50 (1)

IP21, IP55, IP66 maks. penampang silang (rem, beban pemakaian

bersama) [mm2/AWG]16, 10, 16 (6, 8, 6)

35,-,- (2,-,-)50 (1)

Penutup berat IP20 [kg] 12 12 12 23.5 23.5

Penutup berat IP21 [kg] 23 23 23 27 45

Penutup berat IP55 [kg] 23 23 23 27 45

Penutup berat IP66 [kg] 23 23 23 27 45

Efisiensi 3) 0.96 0.96 0.96 0.96 0.96

Tabel 10.2 Pasokan Hantaran listrik 3x200-240 V AC

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 69

10 10

Page 74: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Masukan hantaran listrik 3x200-240 V AC - Kelebihan beban normal 110% untuk 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P22K22

P30K30

P37K37

P45K45

IP20/"Sasis(B3+4 dan C3+4 dapat diubah menjadi IP21 menggunakan kit konversi. (Lihatjuga di item pemasangan Mekanik dan IP21/Jenis 1 kit Penutup pada PanduanRancangan.))

C3 C3 C4 C4

IP21/NEMA 1 C1 C1 C2 C2

IP55/Jenis 12 C1 C1 C2 C2

IP66/NEMA 4X C1 C1 C2 C2

Keluaran Poros Tipikal [HP] pada 208 V 30 40 50 60

Arus keluaran

Berkelanjutan (3 x 200-240 V) [A] 88.0 115 143 170

Sesekali (3 x 200-240 V) [A] 96.8 127 157 187

Berkelanjutan kVA (208 V AC) [kVA] 31.7 41.4 51.5 61.2

Arus masukan maks.

Berkelanjutan (3 x 200-240 V) [A] 80.0 104.0 130.0 154.0

Sesekali (3 x 200-240 V) [A] 88.0 114.0 143.0 169.0

Spesifikasi Tambahan

Perkiraan kehilangan daya pada beban maks. terukur [W] 4) 845 1140 1353 1636

Bagian penampang kabel maks. IP20 (hantaran listrik, rem, motor dan bebanpemakaian bersama)

150 (300 MCM)

IP21, IP55, IP66 bagian penampang kabel maks (hantaran listrik, motor) [mm2/AWG]

150 (300 MCM)

IP21, IP55, IP66 maks. penampang silang (rem, beban pemakaian bersama) [mm2/AWG]

95 (3/0)

Penutup berat IP20 [kg] 35 35 50 50

Penutup berat IP21 [kg] 45 45 65 65

Penutup berat IP55 [kg] 45 45 65 65

Penutup berat IP66 [kg] 45 45 65 65

Efisiensi 3) 0.97 0.97 0.97 0.97

Tabel 10.3 Pasokan Hantaran listrik 3x200-240 V AC

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

70 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 75: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Masukan hantaran listrik 3 x 380-480 V AC - Kelebihan beban normal 110% selama 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P1K11.1

P1K51.5

P2K22.2

P3K03

P4K04

P5K55.5

P7K57.5

Keluaran Poros Tipikal [HP] pada 460 V 1.5 2.0 2.9 4.0 5.0 7.5 10

IP 20/Sasis(A2+A3 dapat diubah menjadi IP21 dengan menggunakan kitkonversi. (Lihat juga di item Pemasangan mekanik dan IP 21/Jenis 1 kit Penutup di Panduan Rancangan.))

A2 A2 A2 A2 A2 A3 A3

IP55/Jenis 12 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5

IP66/NEMA 4X A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5

Arus keluaran

Berkelanjutan (3 x 380-440 V) [A] 3 4.1 5.6 7.2 10 13 16

Sesekali (3 x 380-440 V) [A] 3.3 4.5 6.2 7.9 11 14.3 17.6

Berkelanjutan (3 x 441-480 V) [A] 2.7 3.4 4.8 6.3 8.2 11 14.5

Sesekali (3 x 441-480 V) [A] 3.0 3.7 5.3 6.9 9.0 12.1 15.4

Berkelanjutan kVA (400 V AC) [kVA] 2.1 2.8 3.9 5.0 6.9 9.0 11.0

Berkelanjutan kVA (460 V AC) [kVA] 2.4 2.7 3.8 5.0 6.5 8.8 11.6

Arus masukan maks.

Berkelanjutan (3 x 380-440 V) [A] 2.7 3.7 5.0 6.5 9.0 11.7 14.4

Sesekali (3 x 380-440 V) [A] 3.0 4.1 5.5 7.2 9.9 12.9 15.8

Berkelanjutan (3 x 441-480 V) [A] 2.7 3.1 4.3 5.7 7.4 9.9 13.0

Sesekali (3 x 441-480 V) [A] 3.0 3.4 4.7 6.3 8.1 10.9 14.3

Spesifikasi tambahan

Perkiraan kehilangan daya pada beban maks. terukur [W] 4) 58 62 88 116 124 187 255

IP20, IP21. penampang kabel maks (hantaran listrik, motor, rem

dan beban pemakaian bersama) [mm2/AWG] 2)

4, 4, 4 (12, 12, 12)(min. 0.2 (24))

IP55, IP66 bagian penampang kabel maks (hantaran listrik,motor, rem dan beban pemakaian bersama)

[mm2/AWG] 2)

4, 4, 4 (12, 12, 12)

Bagian penampang kabel maks. dengan pemutusan 6, 4, 4 (10, 12, 12)

Penutup berat IP20 [kg] 4.8 4.9 4.9 4.9 4.9 6.6 6.6

Penutup berat IP21 [kg]

Penutup berat IP55 [kg] (A4/A5) 9.7/13.5 9.7/13.5 9.7/13.5 9.7/13.5 9.7/13.5 14.2 14.2

Penutup berat IP66 [kg] (A4/A5 9.7/13.5 9.7/13.5 9.7/13.5 9.7/13.5 9.7/13.5 14.2 14.2

Efisiensi 3) 0.96 0.97 0.97 0.97 0.97 0.97 0.97

Tabel 10.4 Pasokan/masukan Hantaran listrik 3 x 380-480 V AC

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 71

10 10

Page 76: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Masukan hantaran listrik 3 x 380-480 V AC - Kelebihan beban normal 110% selama 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P11K11

P15K15

P18K18.5

P22K22

P30K30

Keluaran Poros Tipikal [HP] pada 460 V 15 20 25 30 40

IP20/Sasis (B3+4 dan C3+4 dapat diubah menjadi IP21 denganmenggunakan kit konversi (Silahkan konta Danfoss)

B3 B3 B3 B4 B4

IP21/NEMA 1 B1 B1 B1 B2 B2

IP55/Jenis 12 B1 B1 B1 B2 B2

IP66/NEMA 4X B1 B1 B1 B2 B2

Arus keluaran

Berkelanjutan (3 x 380-439 V) [A] 24 32 37.5 44 61

Sesekali (3 x 380-439 V) [A] 26.4 35.2 41.3 48.4 67.1

Berkelanjutan (3 x 440-480 V) [A] 21 27 34 40 52

Sesekali (3 x 440-480 V) [A] 23.1 29.7 37.4 44 61.6

Berkelanjutan kVA (400 V AC) [kVA] 16.6 22.2 26 30.5 42.3

Berkelanjutan kVA 460 V AC) [kVA] 16.7 21.5 27.1 31.9 41.4

Arus masukan maks.

Berkelanjutan (3 x 380-439 V) [A] 22 29 34 40 55

Sesekali (3 x 380-439 V) [A] 24.2 31.9 37.4 44 60.5

Berkelanjutan (3 x 440-480 V) [A] 19 25 31 36 47

Sesekali (3 x 440-480 V) [A] 20.9 27.5 34.1 39.6 51.7

Spesifikasi tambahan

Perkiraan kehilangan dayapada beban maks. terukur [W] 4) 278 392 465 525 698

Bagian penampang kabel maks. IP20 (hantaran listrik, rem, motor danbeban pemakaian bersama)

16, 10, - (8, 8, -) 35, -, - (2, -, -) 35 (2)

IP21, IP55, IP66 bagian penampang kabel maks (hantaran listrik, motor)

[mm2 (AWG)]10, 10, 16 (6, 8, 6) 35, 25, 25 (2, 4, 4) 50 (1)

IP21, IP55, IP66 bagian penampang kabel maks (rem, beban pemakaian

bersama) [mm2 (AWG)]10, 10, - (8, 8, -) 35, -, - (2, -, -) 50 (1)

Dengan pemutusan dengan saklar termasuk: 16/6

Penutup berat IP20 [kg] 12 12 12 23.5 23.5

Penutup berat IP21 [kg] 23 23 23 27 27

Penutup berat IP55 [kg] 23 23 23 27 27

Penutup berat IP66 [kg] 23 23 23 27 27

Efisiensi 3) 0.98 0.98 0.98 0.98 0.98

Tabel 10.5 Pasokan/masukan Hantaran listrik 3 x 380-480 V AC

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

72 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 77: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Masukan hantaran listrik 3 x 380-480 V AC - Kelebihan beban normal 110% selama 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P37K37

P45K45

P55K55

P75K75

P90K90

Keluaran Poros Tipikal [HP] pada 460 V 50 60 75 100 125

IP20/Sasis (B3+4 dan C3+4 dapat diubah menjadi IP21 denganmenggunakan kit konversi (Silahkan konta Danfoss)

B4 C3 C3 C4 C4

IP21/NEMA 1 C1 C1 C1 C2 C2

IP55/Jenis 12 C1 C1 C1 C2 C2

IP66/NEMA 4X C1 C1 C1 C2 C2

Arus keluaran

Berkelanjutan (3 x 380-439 V) [A] 73 90 106 147 177

Sesekali (3 x 380-439 V) [A] 80.3 99 117 162 195

Berkelanjutan (3 x 440-480 V) [A] 65 80 105 130 160

Sesekali (3 x 440-480 V) [A] 71.5 88 116 143 176

Berkelanjutan kVA (400 V AC) [kVA] 50.6 62.4 73.4 102 123

Berkelanjutan kVA 460 V AC) [kVA] 51.8 63.7 83.7 104 128

Arus masukan maks.

Berkelanjutan (3 x 380-439 V) [A] 66 82 96 133 161

Sesekali (3 x 380-439 V) [A] 72.6 90.2 106 146 177

Berkelanjutan (3 x 440-480 V) [A] 59 73 95 118 145

Sesekali (3 x 440-480 V) [A] 64.9 80.3 105 130 160

Spesifikasi tambahan

Perkiraan kehilangan dayapada beban maks. terukur [W] 4) 739 843 1083 1384 1474

Bagian penampang kabel maks. IP20 (hantaran listrik, rem, motor danbeban pemakaian bersama)

50 (1) 150 (300 MCM)

IP21, IP55, IP66 bagian penampang kabel maks (hantaran listrik, motor)

[mm2 (AWG)] 150 (300 MCM)

IP21, IP55, IP66 bagian penampang kabel maks (rem, beban pemakaian

bersama) [mm2 (AWG)] 95 (3/0)

Dengan pemutusan dengan saklar termasuk: 35/2 35/2 70/3/0185/

kcmil350

Penutup berat IP20 [kg] 23.5 35 35 50 50

Penutup berat IP21 [kg] 45 45 45 65 65

Penutup berat IP55 [kg] 45 45 45 65 65

Penutup berat IP66 [kg] 45 45 45 65 65

Efisiensi 3) 0.98 0.98 0.98 0.98 0.99

Tabel 10.6 Pasokan/masukan Hantaran listrik 3 x 380-480 V AC

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 73

10 10

Page 78: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Masukan hantaran listrik 3 x 525-600 V AC - Kelebihan beban normal 110% selama 1 menit

Ukuran: P1K1 P1K5 P2K2 P3K0 P3K7 P4K0 P5K5 P7K5 P11K

Keluaran Poros Tipikal [kW] 1.1 1.5 2.2 3 3.7 4 5.5 7.5 11

IP20/Sasis A3 A3 A3 A3 A2 A3 A3 A3 B3

IP21/NEMA 1 A3 A3 A3 A3 A2 A3 A3 A3 B1

IP55/Jenis 12 A5 A5 A5 A5 A5 A5 A5 A5 B1

IP66/NEMA 4X A5 A5 A5 A5 A5 A5 A5 A5 B1

Arus keluaran

Berkelanjutan (3 x 525-550 V) [A] 2.6 2.9 4.1 5.2 - 6.4 9.5 11.5 19

Sesekali (3 x 525-550 V) [A] 2.9 3.2 4.5 5.7 - 7.0 10.5 12.7 21

Berkelanjutan (3 x 525-600 V) [A] 2.4 2.7 3.9 4.9 - 6.1 9.0 11.0 18

Sesekali (3 x 525-600 V) [A] 2.6 3.0 4.3 5.4 - 6.7 9.9 12.1 20

Berkelanjutan kVA (525 V AC) [kVA] 2.5 2.8 3.9 5.0 - 6.1 9.0 11.0 18.1

Berkelanjutan kVA (575V AC) [kVA] 2.4 2.7 3.9 4.9 - 6.1 9.0 11.0 17.9

Arus masukan maks.

Berkelanjutan (3 x 525-600 V) [A] 2.4 2.7 4.1 5.2 - 5.8 8.6 10.4 17.2

Sesekali (3 x 525-600 V) [A] 2.7 3.0 4.5 5.7 - 6.4 9.5 11.5 19

Spesifikasi tambahan

Perkiraan kehilangan daya pada beban maks. terukur[W] 4)

50 65 92 122 - 145 195 261 300

IP20 penampang silang maks. (hantaran listrik, motor,

rem dan beban pemakaian bersama) [mm2]/[AWG]

4, 4, 4 (12, 12, 12)(min. 0.2 (24))

IP55, IP66 maks. penampang silang (hantaran listrik,

motor, rem dan beban pemakaian bersama) [mm2]/[AWG]

4, 4, 4 (12, 12, 12)(min. 0.2 (24))

Maks. penampang silang dengan pemutusan 6, 4, 4 (12, 12, 12)

Pemutusan dengan saklar termasuk: 4/12

Berat IP20 [kg] 6.5 6.5 6.5 6.5 - 6.5 6.6 6.6 12

Berat IP21/55 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 14.2 14.2 23

Efisiensi 4) 0.97 0.97 0.97 0.97 - 0.97 0.97 0.97 0.98

Tabel 10.7 5) Rem dan beban pemakaian bersama 95 / 4/0

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

74 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 79: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Masukan hantaran listrik 3 x 525-600 V AC - Kelebihan beban normal 110% selama 1 menit

Ukuran: P15K P18K P22K P30K P37K P45K P55K P75K P90K

Keluaran Poros Tipikal [kW] 15 18.5 22 30 37 45 55 75 90

IP20/Sasis B3 B3 B4 B4 B4 C3 C3 C4 C4

IP21/NEMA 1 B1 B1 B2 B2 C1 C1 C1 C2 C2

IP55/Jenis 12 B1 B1 B2 B2 C1 C1 C1 C2 C2

IP66/NEMA 4X B1 B1 B2 B2 C1 C1 C1 C2 C2

Arus keluaran

Berkelanjutan (3 x 525-550 V) [A] 23 28 36 43 54 65 87 105 137

Sesekali (3 x 525-550 V) [A] 25 31 40 47 59 72 96 116 151

Berkelanjutan (3 x 525-600 V) [A] 22 27 34 41 52 62 83 100 131

Sesekali (3 x 525-600 V) [A] 24 30 37 45 57 68 91 110 144

Berkelanjutan kVA (525 V AC) [kVA] 21.9 26.7 34.3 41 51.4 61.9 82.9 100 130.5

Berkelanjutan kVA (575V AC) [kVA] 21.9 26.9 33.9 40.8 51.8 61.7 82.7 99.6 130.5

Arus masukan maks.

Berkelanjutan (3 x 525-600 V) [A] 20.9 25.4 32.7 39 49 59 78.9 95.3 124.3

Sesekali (3 x 525-600 V) [A] 23 28 36 43 54 65 87 105 137

Spesifikasi tambahan

Perkiraan kehilangan daya pada beban maks.terukur [W] 4)

400 475 525 700 750 850 1100 1400 1500

IP20 penampang silang maks. (hantaran listrik,motor, rem dan beban pemakaian bersama)

[mm2]/[AWG]

IP55, IP66 maks. penampang silang (hantaranlistrik, motor, rem dan beban pemakaian

bersama) [mm2]/[AWG]

Maks. penampang silang dengan pemutusan

Pemutusan dengan saklar termasuk:

Berat IP20 [kg] 12 12 23.5 23.5 23.5 35 35 50 50

Berat IP21/55 [kg] 23 23 27 27 27 45 45 65 65

Efisiensi 4) 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98

Tabel 10.8 5) Rem dan beban pemakaian bersama 95/ 4/0

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 75

10 10

Page 80: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

10.1.1 Pasokan/masukan Hantaran listrik 3 x 525-690 V AC

Beban lebih normal 110% selama 1 menit

Konverter FrekuensiKeluaran Poros Tipikal [kW]

P1K11.1

P1K51.5

P2K22.2

P3K03

P4K04

P5K55.5

P7K57.5

Penutup IP20 (saja) A3 A3 A3 A3 A3 A3 A3

Arus keluaran

Berkelanjutan (3x525-550 V) [A] 2.1 2.7 3.9 4.9 6.1 9 11

Sesekali (3x525-550 V) [A] 2.3 3.0 4.3 5.4 6.7 9.9 12.1

KVA berkelanjutan (3x551-690 V) [A] 1.6 2.2 3.2 4.5 5.5 7.5 10

KVA sesekali (3x551-690 V) [A] 1.8 2.4 3.5 4.9 6.0 8.2 11

Berkelanjutan kVA 525 V AC 1.9 2.6 3.8 5.4 6.6 9 12

Berkelanjutan kVA 690 V AC 1.9 2.6 3.8 5.4 6.6 9 12

Arus masukan maks.

Berkelanjutan (3x525-550 V) [A] 1.9 2.4 3.5 4.4 5.5 8 10

Sesekali (3x525-550 V) [A] 2.1 2.6 3.8 8.4 6.0 8.8 11

KVA berkelanjutan (3x551-690 V) [A] 1.4 2.0 2.9 4.0 4.9 6.7 9

KVA sesekali (3x551-690 V) [A] 1.5 2.2 3.2 4.4 5.4 7.4 9.9

Spesifikasi tambahan

IP20 max. cable cross section5) (mains, motor,

brake and load sharing) [mm2]/(AWG)[0.2-4]/(24-10)

Perkiraan kehilangan daya pada beban maks.terukur [W] 4)

44 60 88 120 160 220 300

Penutup, berat IP20 [kg] 6.6 6.6 6.6 6.6 6.6 6.6 6.6

Efisiensi 4) 0.96 0.96 0.96 0.96 0.96 0.96 0.96

Tabel 10.9 Pasokan/masukan Hantaran listrik 3 x 525-690 V AC

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

76 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 81: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Beban lebih normal 110% selama 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P11K15

P15K18.5

P18K22

P22K30

P45K45

P55K55

Keluaran Poros Tipikal [HP] pada 575 V 16.4 20.1 24 33 60 75

IP21/NEMA 1 B2 B2 B2 B2 - -

IP55/NEMA 12 B2 B2 B2 B2 - -

IP20/Sasis - - - - C3 C3

Arus keluaran

Berkelanjutan (3 x 525-550 V) [A] 19 23 28 36 54 65

Sesekali (3 x 525-550 V) [A] 20.9 25.3 30.8 39.6 59.4 71.5

Berkelanjutan (3 x 551-690 V) [A] 18 22 27 34 52 62

Sesekali (3 x 551-690 V) [A] 19.8 24.2 29.7 37.4 57.2 68.2

Berkelanjutan kVA (550 V AC) [kVA] 18.1 21.9 26.7 34.3 51.4 62

Berkelanjutan kVA (575 V AC) [kVA] 17.9 21.9 26.9 33.8 62.2 74.1

Berkelanjutan kVA (690 V AC) [kVA] 21.5 26.3 32.3 40.6 62.2 74.1

Arus masukan maks.

Berkelanjutan (3 x 525-690 V) [A] 19.5 24 29 36 - -

Sesekali (3 x 525-690 V) [A] 21.5 26.4 31.9 39.6 - -

Berkelanjutan (3 x 525-550 V) [A] - - - - 52 63

Sesekali (3 x 525-550 V) [A] - - - - 57.2 69.3

Berkelanjutan (3 x 551-690 V) [A] - - - - 50 60

Sesekali (3 x 551-690 V) [A - - - - 55 66

Pra-sekering1) maks. [A] 63 63 63 80 100 125

Spesifikasi tambahan

Perkiraan kehilangan daya

pada beban maks. terukur [W] 4)285 335 375 430 592 720

Ukuran kabel maks. (hantaran listrik, motor, rem) [mm2]/(AWG) 2) [35]/(1/0) [50]/(1)

Berat IP21 [kg] 27 27 27 27 - -

Berat IP55 [kg] 27 27 27 27 - -

Berat IP20 [kg] - - - - 35 35

Efisiensi 4) 0.98 0.98 0.98 0.98 0.98 0.98

Tabel 10.10 Pasokan Sumber Listrik 3 x 525-690 V AC IP20-Sasis/IP21-IP55/NEMA 1-NEMA 12

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 77

10 10

Page 82: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Beban lebih normal 110% selama 1 menit

Konverter frekuensiKeluaran Poros Tipikal [kW]

P30K37

P37K45

P45K55

P55K75

P75K90

Keluaran Poros Tipikal [HP] pada 575 V 40 50 60 75 100

IP21/NEMA 1 C2 C2 C2 C2 C2

IP55/NEMA 12 C2 C2 C2 C2 C2

Arus keluaran

Berkelanjutan (3 x 525-550 V) [A] 43 54 65 87 105

Sesekali (3 x 525-550 V) [A] 47.3 59.4 71.5 95.7 115.5

Berkelanjutan (3 x 551-690 V) [A] 41 52 62 83 100

Sesekali (3 x 551-690 V) [A] 45.1 57.2 68.2 91.3 110

Berkelanjutan kVA (550 V AC) [kVA] 41 51.4 61.9 82.9 100

Berkelanjutan kVA (575 V AC) [kVA] 40.8 51.8 61.7 82.7 99.6

Berkelanjutan kVA (690 V AC) [kVA] 49 62.1 74.1 99.2 119.5

Arus masukan maks.

Berkelanjutan (3 x 525-690 V) [A] 49 59 71 87 99

Sesekali (3 x 525-690 V) [A] 53.9 64.9 78.1 95.7 108.9

Pra-sekering1) maks. [A] 100 125 160 160 160

Spesifikasi tambahan

Perkiraan kehilangan daya pada beban maks. terukur [W] 4) 592 720 880 1200 1440

Ukuran kabel maks. (hantaran listrik, motor, rem) [mm2]/(AWG) 2) [95]/(4/0)

Berat IP21 [kg] 65 65 65 65 65

Berat IP55 [kg] 65 65 65 65 65

Efisiensi 4) 0.98 0.98 0.98 0.98 0.98

Tabel 10.11 Pasokan Sumber Listrik 3 x 525-690 V AC IP21-IP55/NEMA 1-NEMA 12

1) Untuk jenis sekering lihat 10.3 Tabel sekering2) Ukuran Kawat Amerika3) Diukur mempergunakan kabel motor bersekat sepanjang 5 m padabeban dan frekuensi terukur4) Kehilangan daya tipikal adalah pada kondisi beban normal dan

diharapkan berada di dalam ±15% (toleransi bertautan denganberbagai kondisi tegangan dan kabel).Nilai didasarkan pada efisiensi motor khas (garis batas eff2/eff3).Motor dengan efisiensi yang rendah juga akan menambahkehilangan daya pada konverter frekuensi, dan begitu pulasebaliknya.Jika frekuensi switching dinaikkan dari nominal, maka kehilangandaya akan naik secara signifikan.LCP dan konsumsi daya kartu kontrol khas juga disertakan. Opsiselanjutnya dan beban pelanggan dapat menambah hingga 30 W kekehilangan. (Sekalipun biasanya hanya ada tambahan 4 W untukkartu kontrol yang terbebani penuh atau opsi untuk slot A atau slotB, masing-masing).Sekalipun pengukuran dilakukan dengan perlengkapan mutakhir,beberapa ketidakakuratan pengukuran harus tetap diantisipasi

sebesar (±5%).

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

78 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 83: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

10.2 Data Teknis Umum

Pasokan-hantaran listrikPasokan/masukan Terminal L1, L2, L3Tegangan pasokan 200-240 V ±10%Tegangan pasokan 380-480 V/525-600 V ±10%Tegangan pasokan 525-690 V ±10%

Tegangan hantaran listrik rendah/perosokan (drop-out) hantaran listrik:Selama tegangan hantaran listrik rendah atau perosokan (drop-out) hantaran listrik, FC terus melanjutkan sampai tegangansirkuit antara drop sampai di bawah tingkat stop minimum, di bawah 15% pada konverter frekuensi yang mempunyaitegangan pasokan terukur yang paling terendah. Kenaikan daya dan torsi penuh tidak dapat dicapai pada tegangan listrik lebihrendah dari 10% di bawah pada konverter frekuensi yang mempunyai tegangan pasokan terukur yang paling terendah.

Frekuensi pasokan 50/60 Hz ±5%Ketidakseimbangan sementara maks. antara fasa-fasa hantaran listrik 3.0 % dari tegangan pasokan terukurFaktor Daya Sebenarnya (λ) ≥ 0.9 nominal pada beban terukurFaktor Daya Pergeseran (cos ϕ) hampir bersatu (> 0.98)Menghidupkan pasokan input L1, L2, L3 (daya naik) ≤ 7.5 kW maksimum 2 kali/menit.Switching pasokan masukan L1, L2, L3 (daya naik) 11-75 kW maksimum 1 kali/menit.Switching pasokan masukan L1, L2, L3 (daya naik) ≥ 90 kW maksimum 1 kali/2 menit.Lingkungan menurut EN60664-1 kategori III tegangan lebih/kadar polusi 2

Unit sesuai untuk digunakan pada sirkuit yang dapat menghantarkan tidak lebih dari 100.000 RMS Amper simetris, maksimum240/500/600/690 V.

Motor output (U, V, W)Tegangan keluaran 0-100% tegangan pasokanFrekuensi keluaran (1.1-90 kW) 0-590 HzFrekuensi keluaran (110-250 kW) 0-5901) HzSwitching pada keluaran Tak terbatasWaktu tanjakan 1-3600 detik

1) Bergantung pada tegangan dan daya

Karakteristik torsiTorsi awal (Torsi konstan) maksimum 110% untuk 60 d1)Torsi awal maksimum 135% sampai dengan 0.5 d1)

Torsi kelebihan beban (Torsi konstan) maksimum 110% untuk 60 d1)Torsi awal (Torsi variabel) maksimum 110% untuk 60 d1)Torsi beban berlebih (Torsi variabel) maksimum 110% untuk 60 dWaktu peningkatan torsi di VVCplus (tersendiri dari fsw) 10 md

1) Persentase berhubungan dengan torsi nominal.2) Waktu torsi tergantung pada aplikasi dan bebannya, sebagai peraturan umum, langkah torsi dari 0 sampai referensi adalah4-5x waktu peningkatan torsi.

Panjang dan penampang untuk kabel kontrol1)

Panjang kabel motor maks, disekat 150 mPanjang kabel motor maks, tidak disekat 300 mPenampang maksimum ke terminal kontrol, kawat kaku/ fleksibel tanpa selubung ujung kabel 1,5 mm2/16 AWGPenampang maksimum ke terminal kontrol, kawat fleksibel dengan selubung ujung kabel 1 mm2/18 AWGPenampang maksimum ke terminal kontrol, kawat fleksibel dengan selubung ujung kabel denganpenahan 0,5 mm2/20 AWGPenampang minimum ke terminal kontrol 0.25 mm2/24AWG

1)Untuk kabel daya, lihat tabel data elektrikal.

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 79

10 10

Page 84: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Input digitalMasukan digital dapat diprogram 4 (6)1)

Nomor terminal 18, 19, 271), 291), 32, 33,Logika PNP atau NPNLevel tegangan 0-24 V DCTingkat tegangan, PNP logic'0' <5 V DCTingkat tegangan, PNP logic'1' >10 V DCVoltage level, logic '0' NPN2) >19 V DCTingkat tegangan, logic '1' NPN2) <14 V DCTegangan maksimum pada masukan 28 V DCKisaran frekuensi pulsa 0-110 kHz(Siklus aktif) Lebar pulsa minimum 4.5 msResistansi input, Ri sekitar 4 kΩ

Terminal 373, 4) Berhenti Aman (Terminal 37 merupakan logika PNP tetap)Level tegangan 0-24 V DCTingkat tegangan, PNP logic'0' <4 V DCTingkat tegangan, PNP logic'1' >20 V DCTegangan maksimum pada masukan 28 V DCArus masukan tipikal pada 24 V rms 50 mAArus masukan tipikal pada 20 V 60 mA rmsKapasitansi masukan 400 nF

Semua input digital secara galvanis diisolasikan dari tegangan catu (PELV) dan terminal tegangan tinggi lainnya.1) Terminal 27 dan 29 juga dapat diprogram sebagai ouput.2) Kecuali Terminal 37 input stop aman.3) Lihat untuk informasi lebih lanjut tentang terminal 37 dan Stop Aman.4) Pada saat menggunakan kontaktor dengan koil DC di dalamnya pada kombinasi Stop Aman, sangatlah penting untukmengembalikan arus dari koil pada saat menonaktifkannya. Hal ini dapat dilakukan dengan menggunakan diolda jalan bebas(atau, secara alternatif, 30 atau 50 V MOV untuk waktu respon yang lebih cepat) terhadap koil. Kontaktor tipikal dapat dibelidengan dioda ini.

Input analogJumlah masukan analog 2Nomor terminal 53, 54Modus Tegangan atau arusMemilih modus Saklar S201 dan saklar S202Modus tegangan Saklar S201/saklar S202 = OFF (U)Level tegangan -10 hingga +10 V (berskala)Resistansi input, Ri sekitar 10 kΩTegangan maks. ±20 VModus arus Saklar S201/saklar S202 = ON (I)Tingkat arus 0/4 hingga 20 mA (berskala)Resistansi input, Ri sekitar 200 ΩArus maks. 30 mAResolusi untuk masukan analog 10 bit (tanda +)Ketepatan masukan analog Kesalahan maks. 0,5% dari skala penuhLebar pita 20 Hz/100 Hz

Masukan analog diisolasi secara galvanis dari tegangan pasokan (PELV) dan terminal tegangan tinggi lainnya.

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

80 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 85: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Ilustrasi 10.1 Isolasi PELV

PulsaPulsa terprogram 2/1Pulsa nomor terminal 291), 332) / 333)

Frekuensi maks. pada terminal 29, 33 110 kHz (Gerakan dorong-tarik)Frekuensi maks. pada terminal 29, 33 5 kHz (kolektor terbuka)Frekuensi min. pada terminal 29, 33 4 HzLevel tegangan lihat 10.2.1 Masukan digitalTegangan maksimum pada masukan 28 V DCResistansi input, Ri kira-kira 4 kΩKetepatan masukan pulsa (0.1-1 kHz) Kesalahan maks: 0,1% dari skala penuhAkurasi input encoder (1-11 kHz) Kesalahan maks: 0.05 % dari skala penuh

Masukan encoder dan pulsa (terminal 29, 32, 33) secara galvanis diisolasikan dari tegangan pasokan (PELV) dan terminaltegangan tinggi.1) only2) Input pulsa adalah 29 dan 33

Output analogJumlah keluaran analog yang dapat diprogram 1Nomor terminal 42Kisaran arus pada keluaran analog 0/4-20 mABeban GND maks. – keluaran analog 500 ΩAkurasi pada keluaran analog Kesalahan maks: 0.5% dari skala penuhResolusi pada keluaran analog 12 bit

Keluaran analog secara galvanis diisolasikan dari tegangan pasokan (PELV) dan terminal tegangan tinggi lainnya.

Kartu kontrol, komunikasi serial RS-485Nomor terminal 68 (P,TX+, RX+), 69 (N,TX-, RX-)Nomor terminal 61 Pemakaian bersama untuk terminal 68 dan 69

Sirkuit komunikasi serial RS-485 secara fungsional terpisah dari sirkuit tengah lainnya dan diisolasi secara galvanis daritegangan pasokan (PELV).

Keluaran digitalKeluaran digital/pulsa yang dapat diprogram 2Nomor terminal 27, 29 1)

Tingkat tegangan pada keluaran digital/frekuensi 0-24 VArus output maks (benaman atau sumber) 40 mABeban maks. pada keluaran frekuensi 1 kΩBeban kapasitif maks. pada keluaran frekuensi 10 nFFrekuensi keluaran minimum pada keluaran frekuensi 0 HzFrekuensi keluaran maksimum pada keluaran frekuensi 32 kHzKetepatan dari keluaran frekuensi Kesalahan maks: 0,1 % dari skala penuhResolusi dari keluaran frekuensi 12 bit

1) Terminal 27 dan 29 juga dapat diprogram sebagai output.

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 81

10 10

Page 86: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Keluaran digital diisolasi secara galvanis dari tegangan pasokan (PELV) dan terminal tegangan tinggi lainnya.

Kartu kontrol, output DC 24 VNomor terminal 12, 13Tegangan keluaran 24 V +1, -3 VBeban maks. 200 mA

Pasokan DC 24 V secara galvanis diisolasikan dari tegangan pasokan (PELV) , tetapi memiliki potensi yang sama seperti inputdan output analog dan digital.

Output relaiKeluaran relai yang dapat diprogram semua kW: 2Nomor Terminal Relai 01 1-3 (putus), 1-2 (buat)Beban terminal maks. (AC-1)1) pada 1-3 (NC), 1-2 (NO) (Beban resistif) 240 V AC, 2 ABeban terminal maks. (AC-15)1) (Beban induktif @ cosφ 0.4) 240 V AC, 0.2 ABebn terminal maks. (DC-1)1) pada 1-2 (NO), 1-3 (NC) (Beban resistif) 60 V DC, 1 ABeban terminal maks. (DC-13)1) (Beban induktif) 24 V DC, 0.1 ARelai 02 ( saja) Nomor Terminal 4-6 (break), 4-5 (make)Beban terminal maks.(AC-1)1) pada 4-5 (NO) (Beban resistif)2)3) Kat. II kelebihan tegangan 400 V AC, 2 ABeban terminal maks.(AC-15)1) pada 4-5 (NO) (Beban induktif @ cosφ 0.4) 240 V AC, 0.2 ABeban terminal maks. (DC-1)1) pada 4-5 (NO) (Beban resistif) 80 V DC, 2 ABeban terminal maks. (DC-13)1) pada 4-5 (NO) (Beban induktif) 24 V DC, 0.1 ABeban terminal maks. (AC-1)1) pada 4-6 (NC) (Beban resistif) 240 V AC, 2 ABeban terminal maks. (AC-15)1) pada 4-6 (NC) (Beban induktif @ cosφ 0.4) 240 V AC, 0.2 ABeban terminal maks. (DC-1)1) pada 4-6 (NC) (Beban resistif) 50 V DC, 2 ABeban terminal maks. (DC-13)1) pada 4-6 (NC) (Beban induktif) 24 V DC, 0.1 ABeban terminal min. pada 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24 V DC 10 mA, 24 V AC 20 mALingkungan menurut EN 60664-1 kategori III tegangan lebih/kadar polusi 2

1) IEC 60947 bagian 4 dan 5Kontak relai secara galvanis diisolasikan dari sirkuit dengan isolasi penguatan (PELV).2) Kategori Kelebihan tegangan II3) Aplikasi UL 300 V AC 2A

Kartu kontrol, output DC 10 VNomor terminal 50Tegangan keluaran 10.5 V ±0.5 VBeban maks. 15 mA

Pasokan DC 10 V secara galvanis diisolasikan dari tegangan pasokan (PELV) dan terminal tegangan tinggi lainnya.

Karakteristik KontrolResolusi frekuensi keluaran pada 0-590 Hz ± 0.003 HzUlangi akurasi dari Anjak tepat/b'henti (terminal 18, 19) ≤± 0.1 mdWaktu tanggapan sistem (terminal 18, 19, 27, 29, 32, 33) ≤ 2 msJangkauan kontrol kecepatan (loop terbuka) 1:100 dari kecepatan sinkronJangkauan kontrol kecepatan (loop tertutup) 1:1000 dari kecepatan sinkronKetepatan kecepatan (loop terbuka) 30-4000 rpm: kesalahan ±8 rpmAkurasi kecepatan (loop tertutup), tergantung resolusi perangkat umpan balik 0-6000 rpm: kesalahan ±0.15 rpm

Semua karakteristik kontrol berdasarkan pada motor asinkron 4-kutub

LingkunganPenutup IP201)/Tipe 1, IP212)/Tipe 1, IP55/Tipe 12, IP66Uji getaran 1.0 gKelembaban relatif maks. 5% - 93% (IEC 721-3-3; Kelas 3K3 (tidak mengembun) sewaktu pengoperasianUji (IEC 60068-2-43) H2S lingkungan agresif kelas KdSuhu sekitar3) Maks. 50 °C (maksimum rata-rata 24-jam 45 °C)

1) Hanya untuk ≤ 3.7 kW (200-240 V), ≤ 7.5 kW (400-480 V)

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

82 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 87: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

2) Sebagai penutup kit untuk ≤ 3.7 kW (200-240 V), ≤ 7.5 kW (400-480 V)3) Penurunan untuk suhu sekitar yang tinggi, lihat kondisi khusus di Panduan Rancangan

Suhu minimum sekitar sewaktu pengoperasian skala penuh 0 °CSuhu minimum sekitar pada performa yang menurun - 10 °CSuhu selama penyimpanan/pengangkutan -25 to +65/70 °CKetinggian maksimum di atas permukaan laut tanpa penurunan 1000 m

Penurunan untuk ketinggian yang tinggi, lihat kondisi khusus dalam Panduan Perancangan

standar EMC, Emisi EN 61800-3, EN 61000-6-3/4, EN 55011

Standar EMC, KekebalanEN 61800-3, EN 61000-6-1/2,

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6

Lihat bagian mengenai kondisi khusus dalam Panduan Perancangan.

Performa kartu kontrolInterval pindai 1 ms

Kartu kontrol, USB komunikasi serialStandar USB 1.1 (Kecepatan Penuh)Colokan USB Colokan “device” USB jenis B

Koneksi ke PC dilakukan melalui kabel USB host/perangkat standar.Koneksi USB diisolasi secara galvanis dari tegangan pasokan (PELV) dan terminal tegangan tinggi lainnya.Koneksi USB tidak diisolasi secara galvanis dari pembumian pelindung. Gunakan hanya laptop terisolasi sebagi koneksi PC kekonektor USB pada konverter frekuensi.

Perlindungan and Fitur

• Proteksi motor termal elektronik terhadap beban lebih.

• Pemantauan suhu heatsink dapat memastikan konverter frekuensi akan trip apabila suhu mencapai tingkatpradefinisi. Suhu yang terlampau tinggi tidak dapat disetel sampai suhu heatsink berada di bawah nilai yangditentukan pada tabel halaman berikut ini (Petunjuk - suhu tersebut dapat berubah untuk perbedaan ukuran daya,ukuran bingkai, penutup kelajuan, dll.).

• Konverter frekuensi terlindung dari hubung singkat pada terminal motor U, V, W.

• Jika fase listrik tidak ada, konverter frekuensi akan trip atau mengeluarkan peringatan (tergantung pada bebannya).

• Pemantauan tegangan sirkuit-lanjutan menjamin terjadinya trip konverter frekuensi jika tegangan sirkuit lanjutanterlalu rendah atau terlalu tinggi.

• Konverter frekuensi secara berkala memeriksa tingkat kritis dari suhu internal, arus beban, tegangan tinggi padarangkaian lanjutan dan kecepatan motor rendah. Sebagai tanggapan atas tingkat kritis, konverter frekuensi dapatmengatur frekuensi switching dan/ atau mengubah pola switching untuk memastikan performa konverterfrekuensi.

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 83

10 10

Page 88: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

10.3 Tabel sekering

10.3.1 Sekering Proteksi Sirkuit Bercabang

Untuk pemenuhan dengan standar elektrik IEC/EN 61800-5-1, sekering berikut disarankan.

Konverterfrekuensi

Ukuran sekering maksimum Tegangan Jenis

200-240 V - T2

1K1-1K5 16A1 200-240 jenis gG

2K2 25A1 200-240 jenis gG

3K0 25A1 200-240 jenis gG

3K7 35A1 200-240 jenis gG

5K5 50A1 200-240 jenis gG

7K5 63A1 200-240 jenis gG

11K 63A1 200-240 jenis gG

15K 80A1 200-240 jenis gG

18K5 125A1 200-240 jenis gG

22K 125A1 200-240 jenis gG

30K 160A1 200-240 jenis gG

37K 200A1 200-240 jenis aR

45K 250A1 200-240 jenis aR

380-480 V - T4

1K1-1K5 10A1 380-500 jenis gG

2K2-3K0 16A1 380-500 jenis gG

4K0-5K5 25A1 380-500 jenis gG

7K5 35A1 380-500 jenis gG

11K-15K 63A1 380-500 jenis gG

18K 63A1 380-500 jenis gG

22K 63A1 380-500 jenis gG

30K 80A1 380-500 jenis gG

37K 100A1 380-500 jenis gG

45K 125A1 380-500 jenis gG

55K 160A1 380-500 jenis gG

75K 250A1 380-500 jenis aR

90K 250A1 380-500 jenis aR

1) Sekering maks. - lihat peraturan negara setempat/internasional untuk memilih ukuran sekering yang dapat dipakai.

Tabel 10.12 Sekering EN50178, 200 V to 480 V

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

84 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 89: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Penutup DayaRekomendasi ukuransekering

Rekomendasi sekeringmaks.

Rekomendasi pemotongsirkuit

Tingkat tripmaks

Ukuran [kW] Danfoss [A]

A3

1.1 gG-6 gG-25 CTI25M 10-16 16

1.5 gG-6 gG-25 CTI25M 10-16 16

2.2 gG-6 gG-25 CTI25M 10-16 16

3 gG-10 gG-25 CTI25M 10-16 16

4 gG-10 gG-25 CTI25M 10-16 16

5.5 gG-16 gG-25 CTI25M 10-16 16

7.5 gG-16 gG-25 CTI25M 10-16 16

B2

11 gG-25 gG-63

15 gG-25 gG-63

18 gG-32

22 gG-32

C2

30 gG-40

37 gG-63 gG-80

45 gG-63 gG-100

55 gG-80 gG-125

75 gG-100 gG-160

C337 gG-100 gG-125

45 gG-125 gG-160

D

37 gG-125 gG-125

45 gG-160 gG-160

55-75 gG-200 gG-200

90 aR-250 aR-250

110 aR-315 aR-315

132-160 aR-350 aR-350

200 aR-400 aR-400

250 aR-500 aR-500

315 aR-550 aR-550

E355-400 aR-700 aR-700

500-560 aR-900 aR-900

F

630-900 aR-1600 aR-1600

1000 aR-2000 aR-2000

1200 aR-2500 aR-2500

Tabel 10.13 525-690 V, ukuran bingkai A, C, D, E dan F (sekering non-UL)

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 85

10 10

Page 90: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

10.3.2 UL dan Proteksi Sirkuit Bercabang Sekering

Untuk pemenuhan dengan standar elektrik UL dan cUL, sekering berikut atau subsitusi persetujuan UL/cUL diminta.Pengukuran/taraf/kelajuan sekering maksimum terdaftar.

Konverterfrekuensi

Bussmann Bussmann Bussmann SIBA Sekering LittelFerraz-

ShawmutFerraz-

Shawmut

200-240 V

[kW] Jenis RK1 Jenis J Jenis T Jenis RK1 Jenis RK1 Jenis CC Jenis RK1

1K1 KTN-R10 JKS-10 JJN-10 5017906-010 KLN-R10 ATM-R10 A2K-10R

1K5 KTN-R15 JKS-15 JJN-15 5017906-015 KLN-R15 ATM-R15 A2K-15R

2K2 KTN-R20 JKS-20 JJN-20 5012406-020 KLN-R20 ATM-R20 A2K-20R

3K0 KTN-R25 JKS-25 JJN-25 5012406-025 KLN-R25 ATM-R25 A2K-25R

3K7 KTN-R30 JKS-30 JJN-30 5012406-030 KLN-R30 ATM-R30 A2K-30R

5K5 KTN-R50 JKS-50 JJN-50 5012406-050 KLN-R50 - A2K-50R

7K5 KTN-R50 JKS-60 JJN-60 5012406-050 KLN-R60 - A2K-50R

11K KTN-R60 JKS-60 JJN-60 5014006-063 KLN-R60 A2K-60R A2K-60R

15K KTN-R80 JKS-80 JJN-80 5014006-080 KLN-R80 A2K-80R A2K-80R

18K5 KTN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R A2K-125R

22K KTN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R A2K-125R

30K FWX-150 - - 2028220-150 L25S-150 A25X-150 A25X-150

37K FWX-200 - - 2028220-200 L25S-200 A25X-200 A25X-200

45K FWX-250 - - 2028220-250 L25S-250 A25X-250 A25X-250

380-480 V, 525-600 V

[kW] Jenis RK1 Jenis J Jenis T Jenis RK1 Jenis RK1 Jenis CC Jenis RK1

1K1 KTS-R6 JKS-6 JJS-6 5017906-006 KLS-R6 ATM-R6 A6K-6R

1K5-2K2 KTS-R10 JKS-10 JJS-10 5017906-010 KLS-R10 ATM-R10 A6K-10R

3K0 KTS-R15 JKS-15 JJS-15 5017906-016 KLS-R16 ATM-R16 A6K-16R

4K0 KTS-R20 JKS-20 JJS-20 5017906-020 KLS-R20 ATM-R20 A6K-20R

5K5 KTS-R25 JKS-25 JJS-25 5017906-025 KLS-R25 ATM-R25 A6K-25R

7K5 KTS-R30 JKS-30 JJS-30 5012406-032 KLS-R30 ATM-R30 A6K-30R

11K KTS-R40 JKS-40 JJS-40 5014006-040 KLS-R40 - A6K-40R

15K KTS-R40 JKS-40 JJS-40 5014006-040 KLS-R40 - A6K-40R

18K KTS-R50 JKS-50 JJS-50 5014006-050 KLS-R50 - A6K-50R

22K KTS-R60 JKS-60 JJS-60 5014006-063 KLS-R60 - A6K-60R

30K KTS-R80 JKS-80 JJS-80 2028220-100 KLS-R80 - A6K-80R

37K KTS-R100 JKS-100 JJS-100 2028220-125 KLS-R100 A6K-100R

45K KTS-R125 JKS-150 JJS-150 2028220-125 KLS-R125 A6K-125R

55K KTS-R150 JKS-150 JJS-150 2028220-160 KLS-R150 A6K-150R

75K FWH-220 - - 2028220-200 L50S-225 A50-P225

90K FWH-250 - - 2028220-250 L50S-250 A50-P250

Tabel 10.14 sekering UL, 200-240 V dan 380-600 V

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

86 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 91: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Rekomendasi sekering maks.

Bussmann Bussmann Bussmann Bussmann Bussmann Bussmann

[kW] Jenis RK1 Jenis J Jenis T Jenis CC Jenis CC Jenis CC

1.1 KTS-R-5 JKS-5 JJS-6 FNQ-R-5 KTK-R-5 LP-CC-5

1.5-2.2 KTS-R10 JKS-10 JJS-10 FNQ-R-10 KTK-R-10 LP-CC-10

3 KTS-R-15 JKS-15 JJS-15 FNQ-R-15 KTK-R-15 LP-CC-15

4 KTS-R-20 JKS-20 JJS-20 FNQ-R-20 KTK-R-20 LP-CC-20

5.5 KTS-R25 JKS-25 JJS-25 FNQ-R-25 KTK-R-25 LP-CC-25

7.5 KTS-R-30 JKS-30 JJS-30 FNQ-R-30 KTK-R-30 LP-CC-30

11-15 KTS-R-35 JKS-35 JJS-35

18 KTS-R-45 JKS-45 JJS-45

22 KTS-R50 JKS-50 JJS-50

30 KTS-R-60 JKS-60 JJS-60

37 KTS-R-80 JKS-80 JJS-80

45 KTS-R-100 JKS-100 JJS-100

55 KTS-R125 JKS-125 JJS-125

75 KTS-R150 JKS-150 JJS-150

90 KTS-R175 JKS-175 JJS-175

Tabel 10.15 525-600 V, Ukuran Bingkai A, B, dan C

Rekomendasi sekering maks.

SIBA Sekering Littel Ferraz-Shawmut Ferraz-Shawmut

[kW] Jenis RK1 Jenis RK1 Jenis RK1 Jenis J

0.37-1.1 5017906-005 KLSR005 A6K-5R HSJ6

1.5-2.2 5017906-010 KLSR010 A6K-10R HSJ10

3 5017906-016 KLSR015 A6K-15R HSJ15

4 5017906-020 KLSR020 A6K-20R HSJ20

5.5 5017906-025 KLSR25 A6K-25R HSJ25

7.5 5017906-030 KLSR030 A6K-30R HSJ30

11-15 5014006-040 KLSR035 A6K-35R HSJ35

18 5014006-050 KLSR045 A6K-45R HSJ45

22 5014006-050 KLS-R50 A6K-50R HSJ50

30 5014006-063 KLSR060 A6K-60R HSJ60

37 5014006-080 KLSR075 A6K-80R HSJ80

45 5014006-100 KLSR100 A6K-100R HSJ100

55 2028220-125 KLS-125 A6K-125R HSJ125

75 2028220-150 KLS-150 A6K-150R HSJ150

90 2028220-200 KLS-175 A6K-175R HSJ175

Tabel 10.16 525-600 V, Ukuran Bingkai A, B, dan C

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 87

10 10

Page 92: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Rekomendasi sekering maks.

[kW]Pre sekeringmaks.

BussmannE52273RK1/JDDZ

BussmannE4273 J/JDDZ

BussmannE4273 T/JDDZ

SIBA E180276RK1/JDDZ

LittelFuseE81895RK1/JDDZ

Ferraz-ShawmutE163267/E2137RK1/JDDZ

Ferraz-ShawmutE2137 J/HSJ

11 30 A KTS-R-30 JKS-30 JKJS-30 5017906-030 KLS-R-030 A6K-30-R HST-30

15-18.5 45 A KTS-R-45 JKS-45 JJS-45 5014006-050 KLS-R-045 A6K-45-R HST-45

22 60 A KTS-R-60 JKS-60 JJS-60 5014006-063 KLS-R-060 A6K-60-R HST-60

30 80 A KTS-R-80 JKS-80 JJS-80 5014006-080 KLS-R-075 A6K-80-R HST-80

37 90 A KTS-R-90 JKS-90 JJS-90 5014006-100 KLS-R-090 A6K-90-R HST-90

45 100 A KTS-R-100 JKS-100 JJS-100 5014006-100 KLS-R-100 A6K-100-R HST-100

55 125 A KTS-R-125 JKS-125 JJS-125 2028220-125 KLS-150 A6K-125-R HST-125

75 150 A KTS-R-150 JKS-150 JJS-150 2028220-150 KLS-175 A6K-150-R HST-150

* Pemenuhan UL hanya 525-600V

Tabel 10.17 525-690 V, Ukuran Bingkai B dan C

10.3.3 Sekering Pengganti untuk 240 V

Sekering orisinal Pabrik Sekering pengganti

KTN Bussmann KTS

FWX Bussmann FWH

KLNR SEKERING LITTEL KLSR

L50S SEKERING LITTEL L50S

A2KR FERRAZ SHAWMUT A6KR

A25X FERRAZ SHAWMUT A50X

Tabel 10.18 Sekering Pengganti

10.4 Sambungan Torsi Pengencangan

Daya (kW) Torsi (Nm)

Penu-tup

200-240 V 380-480/500 V 525-600 V 525-690 VSumber

listrikMotor

SambunganDC

RemPembu

mianRelai

A2 1.1-2.2 1.1-4.0 1.8 1.8 1.8 1.8 3 0.6

A3 3.0-3.7 5.5-7.5 1.1-7.5 1.1-7.5 1.8 1.8 1.8 1.8 3 0.6

A4 1.1-2.2 1.1-4.0 1.8 1.8 1.8 1.8 3 0.6

A5 1.1-3.7 1.1-7.5 1.1-7.5 1.8 1.8 1.8 1.8 3 0.6

B1 5.5-11 11-18 11-18 1.8 1.8 1.5 1.5 3 0.6

B2 15 22-30 22-30 11-30 4.5 4.5 3.7 3.7 3 0.6

B3 5.5 -11 11-18 11-18 1.8 1.8 1.8 1.8 3 0.6

B4 15-18 22-37 22-37 11-37 4.5 4.5 4.5 4.5 3 0.6

C1 18-30 37-55 37-55 10 10 10 10 3 0.6

C2 37-45 75-90 75-90 37-90 14/241) 14/241) 14 14 3 0.6

C3 45-55 45-55 45-55 10 10 10 10 3 0.6

C4 37-55 75-90 75-90 14/24 1) 14/24 1) 14 14 3 0.6

Tabel 10.19 Pengencangan Terminal

1) Untuk dimensi kabel yang berbeda x/y, di mana x ≤ 95 mm2 dan y ≥ 95 mm2.

Spesifikasi VLT® Petunjuk Operasional Drive HVAC

88 MG11AI9B - VLT® merek dagang terdaftar Danfoss

1010

Page 93: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

Indeks

AA53............................................................................................................. 20

A54............................................................................................................. 20

Adaptasi Motor Otomatis........................................................... 31, 52

Alarm......................................................................................................... 55

AMAAMA............................................................................................... 59, 62Dengan T27 Tersambung............................................................. 48Tanpa T27 Yang Tersambung..................................................... 48

Arde........................................................................ 12, 13, 14, 16, 26, 27

ArusBeban Penuh................................................................................. 8, 26Berlebih............................................................................................... 52DC...................................................................................................... 7, 52Input..................................................................................................... 16Motor................................................................................. 7, 30, 62, 34Output........................................................................................... 52, 59RMS.......................................................................................................... 7Yang Terukur..................................................................................... 59

AutoAuto...................................................................................................... 35Aktif................................................................................................ 35, 52

AWG........................................................................................................... 68

BBatas

Arus....................................................................................................... 31Suhu...................................................................................................... 27Torsi....................................................................................................... 31

Berdampingan......................................................................................... 9

Bergantung-daya.................................................................................. 68

CContoh

Aplikasi................................................................................................. 48Program............................................................................................... 37Program Terminal............................................................................ 39

DDaftar Kode Alarm/Peringatan........................................................ 58

DataMotor........................................................................ 29, 31, 59, 62, 31Teknis................................................................................................... 79

DayaInput.............................................................. 12, 16, 26, 27, 55, 65, 7Motor.................................................................... 10, 0 , 12, 62, 34

Definisi Peringatan Dan Alarm........................................................ 56

DeltaArde....................................................................................................... 16Mengambang.................................................................................... 16

Digital Input............................................................................................ 59

Download Data Dari LCP................................................................... 36

EEMC............................................................................................................ 27

FFaktor Daya................................................................................. 7, 13, 27

Filte RFI..................................................................................................... 16

FrekuensiMotor.................................................................................................... 34Switching............................................................................................ 52

Fungsi Trip.............................................................................................. 12

GGelombang AC.................................................................................... 7, 6

HHand

Hand..................................................................................................... 35Aktif....................................................................................................... 35

HantaranListrik................................................................................................. 0Listrik AC.............................................................................. 7, 6, 10, 16Listrik Isolasi....................................................................................... 16

Harmonis.................................................................................................... 7

Hentian Aman........................................................................................ 21

IIEC 61800-3............................................................................................. 16

InisialisasiInisialisasi............................................................................................ 36Manual................................................................................................. 36

InputAC...................................................................................................... 7, 16Analog........................................................................................... 17, 58Digital.............................................................................. 17, 20, 52, 39Terputus.............................................................................................. 16

Instalasi....................................................................... 6, 8, 12, 18, 27, 28

Interlock Eksternal......................................................................... 20, 39

Isolasi Kebisingan.......................................................................... 12, 27

JJalankan

Izin......................................................................................................... 52Perintah............................................................................................... 32

Jarak Ruang............................................................................................... 9

Jenis Peringatan Dan Alarm............................................................. 55

Indeks VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 89

Page 94: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

KKabel

Arde......................................................................................... 12, 13, 27Kontrol................................................................................ 12, 0 , 12Motor................................................................ 8, 12, 0 , 13, 27, 31Pelindung...................................................................... 8, 12, 0 , 27Pelindung Penggunaan Arde...................................................... 13Pembumian........................................................................................ 27

KartuKontrol................................................................................................. 58Kontrol, USB Komunikasi Serial................................................... 83

Kebisingan Elektrik............................................................................... 13

Kebocoran Arus..................................................................................... 26

Kecepatan Moto.................................................................................... 28

Kehilangan Fase.................................................................................... 58

Kelebihan Tegangan.................................................................... 31, 52

Keluaran Motor...................................................................................... 79

Ketidakseimbangan Tegangan....................................................... 58

Komunikasi Serial.......................................... 6, 10, 17, 19, 35, 52, 55

KoneksiArde....................................................................................................... 27Pembumian........................................................................................ 27

KontrolKabel.............................................................................................. 19, 27Lokal........................................................................................ 33, 35, 52Terminal........................................................................................ 18, 29

Konverte Frekuensi Multipel............................................................ 13

KonverterFrekuensi............................................................................................. 17Frekuensi Diagram Blok................................................................... 6Frekuensi Multipel........................................................................... 12

LLevel Tegangan..................................................................................... 79

Link DC..................................................................................................... 58

LogAlarm.................................................................................................... 34Masalah................................................................................................ 34

LoopTerbuka......................................................................................... 20, 37Tertutup............................................................................................... 20

MMemutuskan Saklar............................................................................. 26

Mengembalikan Pengaturan Standar........................................... 36

MenuCepat............................................................................... 34, 37, 40, 34Utama............................................................................................ 37, 34

ModeLokal...................................................................................................... 31Status.................................................................................................... 52Tidur...................................................................................................... 52

Modus Auto............................................................................................ 34

Mulai Lokal.............................................................................................. 31

Multipel Motor....................................................................................... 26

OOperasi Lokal.......................................................................................... 33

Opsi Komunikasi................................................................................... 61

OutputAnalog.................................................................................................. 17Relai....................................................................................................... 18

PPanel Kontrol Lokal.............................................................................. 33

Pasokan Tegangan........................................................................ 17, 61

Pelat Belakang.......................................................................................... 9

PELV.................................................................................................... 17, 51

Pemasangan........................................................................................... 27

PembumianPembumian........................................................................................ 27(Arde).................................................................................................... 27

Pemecahan Masalah....................................................................... 6, 65

Pemeriksaan Keselamatan................................................................ 26

Pemotorng Sirkuit................................................................................ 27

Pemrograman........................................................................................ 37

Penambahan Waktu............................................................................ 31

PengaturanPengaturan.................................................................................. 32, 34Parameter........................................................................................... 35

Pengencangan Terminal.................................................................... 88

Pengereman.................................................................................... 60, 52

Pengesahan.............................................................................................. iii

Pengontol Eksternal............................................................................... 6

PengujianFungisonal.......................................................................................... 26Fungsional..................................................................................... 6, 31Kontrol-lokal...................................................................................... 31

Pengukuran Arus..................................................................................... 8

Penurunan................................................................................................. 8

Peralatan Optional............................................................. 14, 20, 28, 6

PerintahEksternal......................................................................................... 7, 52Kontrol Jauh......................................................................................... 6

PerlindunganKelebihan Beban.......................................................................... 8, 12Motor.................................................................................................... 12Transien.................................................................................................. 7

PermulaanPermulaan................................................................. 6, 36, 37, 26, 65Sistem................................................................................................... 32

Persyaratan Jarak Ruang...................................................................... 8

Indeks VLT® Petunjuk Operasional Drive HVAC

90 MG11AI9B - VLT® merek dagang terdaftar Danfoss

Page 95: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

ProgramProgram....................................................... 6, 31, 34, 40, 47, 58, 33Remote................................................................................................ 47Terminal.............................................................................................. 20

Programg................................................................................................. 35

Programm............................................................................................... 20

Proteksi Motor....................................................................................... 83

Putaran Arde.......................................................................................... 19

Putus Saklar............................................................................................ 28

RRCD............................................................................................................ 13

ReferensiReferensi.......................................................................... iii, 48, 52, 34Kecepatan..................................................... 20, 32, 38, 48, 0 , 52Kontrol Jauh....................................................................................... 52

Reset................................................................ 33, 36, 52, 55, 59, 63, 35

Reset-auto............................................................................................... 33

Rotasi Motor.................................................................................... 31, 34

RS-485....................................................................................................... 21

Ruang Kosong Pendinginan............................................................. 27

SSalinan Pengaturan Parameter........................................................ 35

Saluran................................................................................. 0 , 27, 0

SambunganArde....................................................................................................... 12Daya...................................................................................................... 12

Sebelum Mulai....................................................................................... 26

SekeringSekering............................................................ 12, 27, 61, 65, 84, 86EN50178, 200 V To 480 V............................................................... 84UL........................................................................................................... 86

Setpoin..................................................................................................... 52

Simbol........................................................................................................ iii

SinyalAnalog.................................................................................................. 58Input.............................................................................................. 20, 38Kontrol................................................................................... 37, 38, 52Output.................................................................................................. 40

Sirkuit Pendek........................................................................................ 60

SistemKontrol.................................................................................................... 6Monitoring.......................................................................................... 55

Spesifikasi....................................................................................... 6, 9, 68

StatusMotor...................................................................................................... 6Pesan.................................................................................................... 52

Stop Perintah......................................................................................... 52

Struktur Menu.......................................................................... 35, 40, 41

TTampilan Peringatan Dan Alarm..................................................... 55

TanganTangan................................................................................................. 31Aktif....................................................................................................... 31

TeganganEksternal.............................................................................................. 38Hantaran Listrik.......................................................................... 34, 35Induced................................................................................................ 12Input.............................................................................................. 28, 55Pasokan........................................................................................ 17, 26Sumber Listrik................................................................................... 52

Terminal53............................................................................................. 20, 37, 3854........................................................................................................... 20Input......................................................................... 10, 16, 20, 26, 58Kontrol............................................................................ 10, 35, 52, 39Output........................................................................................... 10, 26

Thermistor........................................................................................ 17, 51

TombolMenu.............................................................................................. 33, 34Navigasi................................................................... 28, 37, 52, 33, 35Operasi................................................................................................. 35

TripTrip........................................................................................................ 55Terkunci............................................................................................... 55

UUkuran Kabel................................................................................... 12, 13

UmpanBalik........................................................................... 20, 27, 61, 52, 63Balik Sistem........................................................................................... 6

Unit............................................................................................................... 9

Upload Data Ke LCP............................................................................. 36

WWaktu

Ramp Atas........................................................................................... 31Ramp Bawah...................................................................................... 31

Wiring Kontrol Thermistor................................................................ 17

YYang

Aman....................................................................................................... 9Optimal.................................................................................................. 8

Indeks VLT® Petunjuk Operasional Drive HVAC

MG11AI9B - VLT® merek dagang terdaftar Danfoss 91

Page 96: VLT® HVAC Drive FC 102 1.1-90 kW Oper. Ifiles.danfoss.com/download/Drives/MG11AI9b.pdf · 2.4.5.3 Wiring untuk Kontrol Terminal 18 2.4.5.4 Gunakan Kabel Kontrol Layar 19 ... 52 7.1

www.danfoss.com/drives

*MG11AI9B*130R0083 MG11AI9B Rev. 2013-01-25