work standar vapor extractor
TRANSCRIPT
-
7/31/2019 Work Standar Vapor Extractor
1/4
Standard
work
KPP
IISM PT KPP #1.2 100MW
Guidance
Tgl :2012.10.23 Rev. :0
Vapor Extractor OperationProcedure
Page:1/4
Purpose Of Work :
Summary work
Assortment Contents
Name and Place Of Work 1. Vapor Extractor Operation Procedure
Important Equipment
ImportantCheck
Quality1. Problem :2. Cause :
Environment
Safety
Safety ConsiderationA. BRK input electrical shock cautionB. Work clothes curling caution due to the rotor
2.Accident Case : Not Applicable
3.Near-Miss Case : Not Applicable
4.Fire Case : Not Applicable
5.Work Permit : Not Applicable
Preparation
ActionBeforeWork
APD Helmet, safety shoes, work gloves, ear plug.
EquipmentRequired
Walky talky, valve handle, detector noise & vibration,
By Achmad Gunawan
-
7/31/2019 Work Standar Vapor Extractor
2/4
Standard
work
KPP
IISM PT KPP #1.2 100MW
GuidanceRev. :0
Vapor Extractor OperationProcedure
Page:3/4
1. Main Oil Pump Operation (A: Control Room, B: Local)
Order Of Operations How To Work With Safety /Environment
(1) Oil quality (If necessary, operate the oilpurifier.)
(2) Lube oil tank temperature [TE-
MAV10CT001, TG-MAV10CT501] 10 C
(In case that oil temperature < 10 C,
start the main oil tank heater.)
(3) Oil level of main oil tank (If insufficient, fill
it up.) [LG-MAV10CL501, LT-MAV10CL001]Flow back oil level.
(4) Main oil tank drain valve [MAV10AA401,
402] Fully close
(5) Main oil tank sampling port valve
[MAV10AA601]Fully close (after
checking the quality of oil)
(6) Main oil tank inlet valve for oil portable
system [MAV10AA001]Fully close
(7) Main oil tank vapor extraction return line
valve [MAV10AA251]Fully close
(8) Control oil pump-
A,B[MAX21AP001,002]MANUAL,
STOP
(9) Mode selection.
MODE OPERATION ORDER STAND BY
AB MODE A B A
BA MODE B A B
BRK inputelectrical shockcaution
1.Control Room Start,A. Control Room Auto start
- In operation, Pump fault
- Main Oil Pump Pressure lower (4.6 barg)
B. Control Room Man start- Graphic in DCS
Choose Main Oil Pump- Choose Sub window Man Then Start
1)Check Before OP (B)
2) MOP start (A)
-
7/31/2019 Work Standar Vapor Extractor
3/4
Standard
work
KPP
IISM PT KPP #1.2 100MW
Guidance
Rev. :0
Vapor Extractor OperationProcedure
Page:3/4
1. Vibration Check2. Check Leakage
3. Main oil pump-A,B discharge Pressure(01/02 MAV21CP201,211) *4.6 BarGStand-by MOP & EOP start autmatically.(*: Setting value corresponds to4.2 BarGat T/G center.)
4. Main oil tank level (01/02 MAV10CL001)NOL +50 mm (H), NOL -50 mm (L).
- Confirm that there is no lube oilleakage. If any leakage is found out,repair it.
- Confirm that main oil tank drain valve isclosed.
- Fill the tank with lube oil up topermissible level.
Work clothes
curling cautiondue to the rotor
1.Control Room stopControl Room Auto stop (After Stand by start)
Control Room Man stop- Graphic di DCS
Choose Main Oil Pump- In Sub window, Choose Man stop
3)Check After MOPstart(Operation)
finish
4) MOP stop(A)
-
7/31/2019 Work Standar Vapor Extractor
4/4
Standard
work
KPP
IISM PT KPP #1.2 100MW
Guidance
Rev. :0
Vapor Extractor OperationProcedure
Page:4/4
Main Oil Pump Operation Flow