pedoman trafo arus

Download Pedoman Trafo Arus

Post on 04-Jun-2018

233 views

Category:

Documents

3 download

Embed Size (px)

TRANSCRIPT

  • 8/14/2019 Pedoman Trafo Arus

    1/60

    PT PLN (Persero)

    TRANSFORMATOR ARUS (CT)

    Listrik untuk kehidupan yang lebih baik 1

    DAFTAR ISI

    DAFTAR ISI ........................................................................................................................................ 1I. PENDAHULUAN ................................................................................................................. 21.1. Pengertian Trafo Arus ......................................................................................................... 21.2. Fungsi Trafo Arus ................................................................................................................ 41.3. Jenis Trafo Arus .................................................................................................................. 61.4. Komponen Trafo Arus ....................................................................................................... 131.5. Failure Mode and Effect Analysis (FMEA) ........................................................................ 16

    1.5.1. Mendefinisikan sistem (peralatan) dan fungsinya .............................................. 161.5.2. Menentukan sub sistem dan fungsi tiap subsistem ........................................... 161.5.3. Menentukan functional failure tiap subsistem .................................................... 161.5.4. Menentukan failure mode tiap subsistem .......................................................... 171.5.5. FMEA CT ........................................................................................................... 17

    II. PEDOMAN PEMELIHARAAN .......................................................................................... 182.1. In Service Inspection ......................................................................................................... 18

    2.1.1. Dielectric ............................................................................................................ 182.1.2. Mechanical Structure ......................................................................................... 182.1.3. Pentanahan CT .................................................................................................. 19

    2.2. In Service Measurement ................................................................................................... 192.2.1. Thermovision ...................................................................................................... 19

    2.3. Shutdown Testing/Measurement....................................................................................... 202.3.1. Tahanan Isolasi .................................................................................................. 202.3.2. Tan Delta ............................................................................................................ 202.3.3. Pengujian Kualitas Minyak isolasi ...................................................................... 252.3.4. Pengujian Dissolved Gas Analysis (DGA) ......................................................... 272.3.5. Tahanan Pentahanan ........................................................................................ 27

    2.3.6. Ratio ................................................................................................................... 272.3.7. Pengujian Eksitasi atau Vknee .......................................................................... 29

    2.4. Shutdown Treatment ......................................................................................................... 30III. EVALUASI HASIL PEMELIHARAAN DAN REKOMENDASI ......................................... 313.1. In Service Inspection ......................................................................................................... 313.2. In Service Measurement ................................................................................................... 34

    3.2.1. Thermovisi klem dan konduktor ......................................................................... 343.2.2. Thermovisi Isolator dan Housing CT.................................................................. 35

    3.3. Shutdown Testing/ Measurement...................................................................................... 363.3.1. Tahanan Isolasi .................................................................................................. 363.3.2. Tan Delta ............................................................................................................ 373.3.3. Kualitas Minyak .................................................................................................. 403.3.4. DGA ................................................................................................................... 443.3.5. Tahanan Pentanahan ........................................................................................ 453.3.6. Ratio ................................................................................................................... 46

    3.4. Shutdown Inspection ......................................................................................................... 46IV. TABEL URAIAN KEGIATAN PEMELIHARAAN ............................................................. 47

  • 8/14/2019 Pedoman Trafo Arus

    2/60

    PT PLN (Persero)

    TRANSFORMATOR ARUS (CT)

    Listrik untuk kehidupan yang lebih baik 2

    I. PENDAHULUAN

    1.1. Pengertian Trafo Arus

    Trafo Arus (Current Transformator) yaitu peralatan yang digunakan untuk

    melakukan pengukuran besaran arus pada intalasi tenaga listrik disisi primer

    (TET, TT dan TM) yang berskala besar dengan melakukan transformasi dari

    besaran arus yang besar menjadi besaran arus yang kecil secara akurat dan teliti

    untuk keperluan pengukuran dan proteksi.

    Prinsip kerja trafo arus adalah sebagai berikut:

    Untuk trafo yang dihubung singkat : 2211 NINI =

    Untuk trafo pada kondisi tidak berbeban:

    2

    1

    2

    1

    N

    N

    E

    E=

    Dimana

    2

    1

    N

    Na = ,

    21 II > sehingga 21 NN < ,

    =1N jumlah lilitan primer, dan

    P1

    P2

    S2

    S1

    I2I1

    N1 N2

    Gambar 1.1. Rangkaian pada Trafo Arus

  • 8/14/2019 Pedoman Trafo Arus

    3/60

    PT PLN (Persero)

    TRANSFORMATOR ARUS (CT)

    Listrik untuk kehidupan yang lebih baik 3

    =2N jumlah lilitan sekunder.

    Rangkaian Ekivalen

    Tegangan induksi pada sisi sekunder adalah

    22 44,4 NfABE = Volt

    Tegangan jepit rangkaian sekunder adalah

    ( )bZZIE += 222 Volt

    instkawatb ZZZ += Volt

    Dalam aplikasinya harus dipenuhi21 UU >

    Dimana: =B kerapatan fluksi (tesla)

    =A luas penampang (m)

    =f frekuensi (Hz)

    =2N jumlah lilitan sekunder

    =1U tegangan sisi primer

    =2

    U tegangan sisi sekunder

    E2 I2U1 I2Zb= U2I0

    I1Z1 I2Z2

    Gambar 1.2. Rangkaian Ekivalen

  • 8/14/2019 Pedoman Trafo Arus

    4/60

    PT PLN (Persero)

    TRANSFORMATOR ARUS (CT)

    Listrik untuk kehidupan yang lebih baik 4

    =bZ impedansi/tahanan beban trafo arus

    =kawatZ impedansi/tahanan kawat dari terminasi CT ke instrumen

    =instZ impedansi/tahanan internal instrumen, misalnya relai

    proteksi atau peralatan meter.

    Diagram Fasor Arus dan Tegangan pada Trafo Arus (CT)

    1.2. Fungsi Trafo Arus

    Fungsi dari trafo arus adalah:

    - Mengkonversi besaran arus pada sistem tenaga listrik dari besaran primer

    menjadi besaran sekunder untuk keperluan pengukuran sistem metering dan

    proteksi

    - Mengisolasi rangkaian sekunder terhadap rangkaian primer, sebagai

    pengamanan terhadap manusia atau operator yang melakukan pengukuran.

    - Standarisasi besaran sekunder, untuk arus nominal 1 Amp dan 5 Amp

    Secara fungsi trafo arus dibedakan menjadi dua yaitu:

    a). Trafo arus pengukuran

    Im

    IO

    IOI1

    I2

    U2

    E

    U1I1Z1

    I2Z2

    Gambar 1.3. Diagram Fasor Arus dan Tegangan pada

  • 8/14/2019 Pedoman Trafo Arus

    5/60

    PT PLN (Persero)

    TRANSFORMATOR ARUS (CT)

    Listrik untuk kehidupan yang lebih baik 5

    o Trafo arus pengukuran untuk metering memiliki ketelitian tinggi pada

    daerah kerja (daerah pengenalnya) 5% - 120% arus nominalnya

    tergantung dari kelasnya dan tingkat kejenuhan yang relatif rendahdibandingkan trafo arus untuk proteksi.

    o Penggunaan trafo arus pengukuran untuk Amperemeter, Watt-meter,

    VARh-meter, dan cos jmeter.

    b). Trafo arus proteksi

    Trafo arus untuk proteksi, memiliki ketelitian tinggi pada saat terjadi

    gangguan dimana arus yang mengalir beberapa kali dari arus

    pengenalnya dan tingkat kejenuhan cukup tinggi.

    Penggunaan trafo arus proteksi untuk relai arus lebih (OCR dan GFR),

    relai beban lebih, relai diferensial, relai daya dan relai jarak.

    Perbedaan mendasar trafo arus pengukuran dan proteksi adalah pada

    titik saturasinya seperti pada kurva saturasi dibawah (Gambar 4).

    - Trafo arus untuk pengukuran dirancang supaya lebih cepat jenuh

    dibandingkan trafo arus proteksi sehingga konstruksinya mempunyai luas

    penampang inti yang lebih kecil (Gambar 5).

    pengukuran

    V

    I

    proteksi

    Gambar 1.4. Kurva kejenuhan CT untuk Pengukuran dan Proteksi

  • 8/14/2019 Pedoman Trafo Arus

    6/60

    PT PLN (Persero)

    TRANSFORMATOR ARUS (CT)

    Listrik untuk kehidupan yang lebih baik 6

    1.3. Jenis Trafo Arus

    Jenis trafo arus menurut tipe kont ruksi dan pasangannya.

    Tipe Konstruksi

    Tipe cincin (ring / window type) Gbr. 1a dan 1b.

    Tipe cor-coran cast