Seri RZR-LU
Pendinginan Saja R-410A 50 Hz
RZR100/125/140LUY1(4)
Panduan
Servis
SiMT281515E
SiMT281515E
i Daftar Isi
Seri RZR-LU
Pendinginan
Saja R-410A 50
Hz
Referensi ED
Untuk item di bawah ini, lihat Data Teknik.
No. Item No. ED Halaman Keterangan
1 Spesifikasi EDMT281511 P. 12 - 23 2 Aksesoris EDMT281511 P. 79 - 80
1. Pendahuluan .............................................................................................. iv 1.1 Peringatan Keselamatan ....................................................................... iv
1.2 Ikon yang Digunakan............................................................................viii
Bagian 1 Informasi Umum ............................................................1
1. Nama Model Unit Indoor / Outdoor ........................................................... 2
2. Penampilan eksternal ................................................................................ 3
Bagian 2 Fungsi ............................................................................4
1. Fungsi ......................................................................................................... 5
Bagian 3 Remote Kontrol..............................................................6
1. Remote Kontrol Berkabel .......................................................................... 7 1.1 Model yang Berlaku ...............................................................................7
1.2 Nama dan Fungsi ...................................................................................8
1.3 Pengaturan MAIN/SUB saat Menggunakan 2 Remote Kontrol ...............12
1.4 Pengaturan No. Grup Kendali Terpusat ................................................13
1.5 Mode Servis .........................................................................................15
1.6 Mode Inspeksi ......................................................................................19
2. Remote Kontrol Nirkabel ......................................................................... 20 2.1 Model yang berlaku ..............................................................................20
2.2 Nama dan Fungsi .................................................................................20
2.3 Pengaturan MAIN/SUB dan Alamat ......................................................22
Bagian 4 Fungsi dan Kontrol ......................................................24
1. Fungsi Termistor dan Komponen Utama (Diagram Pemipaan)................................................................................ 25
2. Garis Besar Fungsi .................................................................................. 28
SiMT281515E
Daftar Isi ii
2.1 Unit Indoor ...........................................................................................28
2.2 Unit Outdoor ........................................................................................29
3. Diagram Alir Operasi ............................................................................... 30 3.1 Operasi Pendinginan/Kering (Cooling/Dry) ............................................30
4. Rincian Fungsi ......................................................................................... 31 4.1 Unit Indoor ...........................................................................................31
4.2 Unit Outdoor ........................................................................................36
Bagian 5 Operasi Uji Coba dan Pengaturan Bidang .................... 44
1. Operasi Uji Coba ...................................................................................... 45 1.1 Periksa sebelum Operasi Uji Coba .......................................................45
1.2 Pemeriksaan Operasi Uji Coba .............................................................45
2. Pengaturan Bidang dari Remote Kontrol ................................................ 46 2.1 Remote Kontrol Berkabel ......................................................................46
2.2 Remote Kontrol Nirkabel .......................................................................49
2.3 Nomor Kode dan Isi Pengaturan untuk Unit Indoor .................................50
2.4 Nomor Kode dan Isi Pengaturan untuk Unit Outdoor ..............................51
3. Pengaturan Bidang dari Adaptor Demand .............................................. 53 3.1 Fungsi i-Demand...................................................................................53
4. Pengaturan Bidang dari PCB Unit Outdoor ........................................... 54 4.1 Pengaturan dengan Tombol BS............................................................54
4.2 Mode 1 Pengaturan ..............................................................................54
4.3 Mode 2 Pengaturan..............................................................................55
4.4 Mode Monitor .......................................................................................57
4.5 Daftar Isi tentang Coba lagi dan Kesalahan ...........................................58
5 Operasi Darurat ........................................................................................ 60
Bagian 6 Diagnosis Servis .........................................................62
1. Inspeksi Pemeliharaan ............................................................................ 64 1.1 Gambaran Umum ................................................................................64
2. Pemecahan Masalah Berbasis Gejala ................................................... 66 2.1 Gambaran Umum .................................................................................66
2.2 Peralatan tidak Beroperasi ....................................................................67
2.3 Kipas Unit Indoor Beroperasi, tetapi Kompresor tidak Beroperasi ...........68
2.4 Operasi Pendinginan Mulai tetapi Berhenti Segera ................................69
2.5 Setelah Unit dimatikan, tidak dapat dihidupkan ulang untuk sementara ..70
2.6 Peralatan Beroperasi tetapi tidak memberikan Pendinginan ...................72
2.7 Peralatan Mengeluarkan Kabut Putih.....................................................73
2.8 Peralatan Menghasilkan suara keras atau Getaran ................................74
2.9 Peralatan Mengeluarkan Debu ..............................................................76
2.10 LCD Remote Kontrol Menampilkan "88" ...............................................76
3 Pemecahan Masalah berdasarkan Indikasi LED................................... 77 3.1 Pemecahan Masalah berdasarkan LED pada Unit Indoor .....................77
3.2 Pemecahan Masalah berdasarkan LED pada PCB Unit Outdoor ...........77
4 Pemecahan Masalah menggunakan Remote Kontrol ........................... 78 4.1 Penggantian Mode ................................................................................78
4.2 Prosedur diagnosis sendiri menggunakan Remote Kontrol .....................79
4.3 Deskripsi dan Kode Kesalahan ..............................................................83
4.4 Kode Kesalahan – Kode Sub .................................................................84
4.5 Gambaran Umum tentang Perangkat keselamatan Outdoor...................87
SiMT281515E
i Daftar Isi
4.6 Gambaran Umum tentang Perangkat keselamatan Indoor ....................87
5 Pemecahan Masalah berdasarkan Indikasi pada Remote Kontrol ...... 88
5.1 Ketidaknormalan PCB Unit Indoor .........................................................88
5.2 Ketidaknormalan Sistem Permukaan Air Saluran ...................................89
5.3 Kunci Motor Kipas Unit Indoor ..............................................................91
5.4 Ketidaknormalan Motor Kipas Unit Indoor ..............................................92
5.5 Ketidaknormalan PCB Kipas .................................................................94
5.6 Ketidaknormalan Sistem Saluran ..........................................................95
5.7 Ketidaknormalan Pengaturan Kapasitas ................................................96
5.8 Kesalahan Transmisi (antara PCB Unit Indoor dan PCB Kipas) .............97
5.9 Kesalahan Transmisi (antara PCB Unit Indoor dan PCB Kipas).............99
5.10 Ketidaknormalan Termistor .............................................................. 101
5.11 Kesalahan Kombinasi antara PCB Unit Indoor dan PCB Kipas ......... 102
5.12 Ketidaknormalan Termistor Remote Kontrol ...................................... 103
5.13 Ketidaknormalan PCB Unit Outdoor .................................................. 104
5.14 Ketidaknormalan Tekanan Tinggi
( Terdeteksi oleh Saklar Tekanan Tinggi) .......................................... 105
5.15 Kunci Motor Kompresor ................................................................... 107
5.16 Ketidaknormalan Motor Kipas Unit Outdoor ....................................... 108
5.17 Ketidaknormalan Katup Ekspansi Elektronik ...................................... 110
5.18 Ketidaknormalan Suhu Pipa Pembuangan ........................................ 112
5.19 Ketidaknormalan Sistem Saklar Tekanan Tinggi ................................ 113
5.20 Ketidaknormalan Termistor ............................................................... 114
5.21 Ketidaknormalan Sensor Tekanan .................................................... 115
5.22 Ketidaknormalan PCB Unit Outdoor .................................................. 116
5.23 Peningkatan Suhu Sirip Radiasi ........................................................ 118
5.24 Arus Berlebih Output DC (Sesaat)..................................................... 120
5.25 Termal Elektronik (Jeda waktu) ......................................................... 122
5.26 Pencegahan Stall (Jeda waktu) ........................................................ 124
5.27 Kesalahan Sistem Transmisi antar PCB Unit Outdoor....................... 126
5.28 Ketidakseimbangan Tegangan Catu Daya atau Fasa Terbuka ........... 127
5.29 Ketidaknormalan Termistor Sirip Radiasi ........................................... 128
5.30 Ketidaknormalan Pengaturan Kapasitas ............................................ 129
5.31 Kekurangan Refrigeran ..................................................................... 130
5.32 Ketidaknormalan Tegangan Catu Daya ............................................. 131
5.33 Kesalahan Transmisi antara Unit Indoor dan Unit Outdoor .................. 132
5.34 Kesalahan Transmisi antara Unit Indoor dan Remote Kontrol ............ 134
5.35 Kesalahan Transmisi antara Remote Kontrol MAIN dan
Remote Kontrol SUB ........................................................................ 135
5.36 Ketidaknormalan Saklar Pengaturan Bidang ..................................... 136
5.37 Kesalahan Pengaturan Alamat Terpusat ........................................... 137
5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor / Pemipaan dan
Ketidakcocokan Pengkabelan / Kekurangan Refrigeran ...................... 138
5.39 Pemeriksaan .................................................................................... 139
Bagian 7 Lampiran .................................................................... 149
1. Diagram Pengkabelan ........................................................................... 150 1.1 Unit Indoor .......................................................................................... 150
1.2 Unit Outdoor ....................................................................................... 151
Daftar Isi ii
SiMT281515E Pendahuluan
1. Pendahuluan
1.1 Peringatan Keselamatan Perhatian
dan
Peringatan
Pastikan untuk membaca peringatan keselamatan berikut sebelum melakukan pekerjaan perbaikan.
Item-Perhatian diklasifikasikan ke dalam “ Peringatan” dan “ Perhatian”. Item-
item “ Peringatan” sangat penting karena mereka dapat menyebabkan kematian
atau cedera serius jika tidak dipatuhi. Item-item “ Perhatian” juga dapat
menyebabkan kecelakaan serius dalam beberapa kondisi jika tidak dipatuhi. Oleh
karena itu, pastikan untuk mematuhi semua item perhatian keselamatan yang
dijelaskan di bawah ini.
Tentang Piktogram
Simbol ini menunjukkan item perhatian yang harus dilakukan.
Piktogram menunjukkan item-item yang harus diperhatikan.
Simbol ini menunjukkan tindakan yang dilarang. Item atau tindakan yang dilarang ditampilkan dalam ilustrasi atau dekat simbol.
Simbol ini menunjukkan tindakan, atau instruksi yang harus dilakukan.
Instruksi ditampilkan dalam ilustrasi atau dekat simbol.
Setelah pekerjaan perbaikan selesai, pastikan melakukan operasi uji coba untuk
memastikan bahwa peralatan beroperasi secara normal, dan menjelaskan kehati-
hatian pengoperasian produk kepada pelanggan.
1.1.1 Perhatian Mengenai Keselamatan Pekerja
Peringatan
Pastikan untuk mencabut steker kabel listrik dari stopkontak steker sebelum membongkar peralatan untuk perbaikan. Bekerja pada peralatan yang terhubung ke catu daya dapat menyebabkan sengatan listrik. Jika perlu mengalirkan listrik ke peralatan untuk melakukan perbaikan atau memeriksa sirkuit, jangan menyentuh bagian peralatan yang bermuatan listrik.
Jika gas refrigeran dibuang selama pekerjaan perbaikan, jangan sentuh gas refrigeran yang dibuang. Gas refrigeran dapat menyebabkan radang dingin.
Saat melepas pipa hisap atau pembuangan kompresor di bagian yang dilas, terlebih dahulu keluarkan gas refrigeran di tempat yang berventilasi baik. Jika ada gas yang tersisa di dalam kompresor, gas refrigeran atau minyak mesin refrigerasi akan keluar ketika pipa dilepaskan, dan dapat menyebabkan cedera.
Jika gas refrigeran bocor selama pekerjaan perbaikan, beri ventilasi di area tersebut. Gas refrigeran dapat menghasilkan gas beracun saat melakukan kontak dengan api.
Kapasitor step-up mengalirkan listrik tegangan tinggi ke komponen listrik dari unit outdoor. Pastikan untuk membuang kapasitor sepenuhnya sebelum melakukan pekerjaan perbaikan. Kapasitor yang bermuatan listrik dapat menyebabkan sengatan listrik.
Jangan menyalakan atau menghentikan operasi AC dengan mencolokkan atau mencabut steker kabel listrik. Mencolokkan atau mencabut steker kabel listrik untuk mengoperasikan peralatan dapat menyebabkan sengatan listrik atau kebakaran.
SiMT281515E Pendahuluan
v
Peringatan
Pastikan untuk mengenakan helm pengaman, sarung tangan, dan sabuk pengaman saat bekerja di tempat yang tinggi (lebih dari 2 m). Tindakan keselamatan yang tidak memadai dapat menyebabkan kecelakaan jatuh.
Dalam kasus model refrigeran R-410A, pastikan untuk menggunakan pipa, mur flare dan alat untuk penggunaan eksklusif refrigeran R-410A. Penggunaan bahan untuk model refrigeran R-22 dapat menyebabkan kecelakaan serius seperti kerusakan siklus refrigeran serta kegagalan peralatan.
Perhatian
Jangan memperbaiki komponen listrik dengan tangan basah. Bekerja pada peralatan dengan tangan basah dapat menyebabkan sengatan listrik.
Jangan membersihkan pendingin ruangan dengan memercikkan air. Mencuci unit dengan menggunakan air dapat menyebabkan sengatan listrik.
Pastikan untuk memberikan arde (pembumian) saat memperbaiki peralatan di tempat yang lembab atau basah, untuk menghindari sengatan listrik.
Pastikan untuk menonaktif(OFF)-kan saklar daya dan mencabut kabel listrik saat membersihkan peralatan. Kipas internal berputar pada kecepatan tinggi, dan menyebabkan cedera.
Pastikan untuk melakukan pekerjaan perbaikan dengan alat yang tepat.
Penggunaan alat-alat yang tidak sesuai dapat menyebabkan cedera.
Pastikan untuk memeriksa bahwa bagian siklus refrigerasi telah didinginkan dengan cukup sebelum melakukan pekerjaan perbaikan. Bekerja pada unit saat bagian siklus refrigerasi panas dapat menyebabkan luka bakar.
Gunakan alat las di tempat yang berventilasi baik. Penggunaan alat las di ruang tertutup dapat menyebabkan kekurangan oksigen.
Pendahuluan SiMT281515E
vi
1.1.2 Perhatian Mengenai Keselamatan Pengguna
Peringatan
Pastikan untuk menggunakan komponen yang tercantum dalam daftar komponen servis dari model yang berlaku dan alat yang tepat untuk melakukan pekerjaan perbaikan. Jangan pernah mencoba memodifikasi peralatan. Penggunaan komponen atau alat yang tidak sesuai dapat menyebabkan sengatan listrik, pembangkitan panas berlebihan atau kebakaran.
Jika kabel listrik dan kawat timah memiliki goresan atau memburuk, pastikan untuk menggantinya.
Kabel dan kawat yang rusak dapat menyebabkan sengatan listrik, pembangkitan panas berlebihan atau kebakaran.
Jangan menggunakan sambungan kabel listrik atau kabel perpanjangan, atau berbagi stopkontak yang sama dengan peralatan listrik lainnya, karena dapat menyebabkan sengatan listrik, pembangkitan panas berlebihan atau kebakaran.
Pastikan untuk menggunakan sirkuit listrik eksklusif untuk peralatan, dan mematuhi standar teknis lokal terkait dengan peralatan listrik, peraturan pengkabelan internal, dan panduan petunjuk untuk pemasangan ketika melakukan pekerjaan listrik. Kapasitas sirkuit listrik yang tidak memadai dan pekerjaan listrik yang tidak tepat dapat menyebabkan sengatan listrik atau kebakaran.
Pastikan untuk menggunakan kabel yang ditentukan untuk kabel antara Unit indoor dan outdoor. Buatlah sambungan aman dan rute kabel dengan benar sehingga tidak ada kekuatan yang menarik kabel di terminal sambungan. Sambungan yang tidak tepat dapat menyebabkan timbulnya panas berlebihan atau kebakaran.
Ketika melakukan pengkabelan antara unit indoor dan outdoor, pastikan bahwa penutup terminal tidak terangkat atau turun karena kabel. Jika penutup tidak terpasang dengan benar, bagian sambungan terminal dapat menyebabkan sengatan listrik, pembangkitan panas berlebihan atau kebakaran.
Jangan merusak atau memodifikasi kabel listrik. Kabel listrik yang rusak atau dimodifikasi dapat menyebabkan sengatan listrik atau kebakaran. Menempatkan benda-benda berat di atas kabel listrik, dan memanaskan atau menarik kabel listrik dapat merusak kabel.
Jangan mencampur udara atau gas selain refrigeran yang ditentukan (R-410A / R-22) di dalam sistem refrigeran. Jika udara memasuki sistem refrigeran, akan menghasilkan tekanan yang terlalu tinggi, menyebabkan kerusakan peralatan dan cedera.
Jika gas refrigeran bocor, pastikan menemukan titik bocor dan memperbaikinya sebelum mengisi refrigeran. Setelah pengisian refrigeran, pastikan tidak ada kebocoran refrigeran. Jika titik bocor tidak dapat ditemukan dan pekerjaan perbaikan harus dihentikan, pastikan untuk melakukan pump down dan menutup katup servis, untuk mencegah gas refrigeran bocor ke dalam ruangan. Gas refrigeran tidak berbahaya, tetapi dapat menghasilkan gas beracun saat melakukan kontak dengan nyala api, seperti kipas dan pemanas lainnya, tungku dan kompor.
Ketika memindahkan peralatan, pastikan bahwa tempat pemasangan baru memiliki kekuatan yang cukup untuk menahan berat peralatan tersebut. Jika tempat pemasangan tidak memiliki kekuatan yang memadai dan jika pekerjaan pemasangan tidak dilakukan dengan aman, peralatan bisa jatuh dan menyebabkan cedera.
SiMT281515E Pendahuluan
vii
Peringatan
Periksa untuk memastikan bahwa steker kabel listrik tidak kotor atau longgar, kemudian masukkan steker ke stopkontak dengan aman. Jika steker berdebu atau sambungannya longgar, dapat menyebabkan sengatan listrik atau kebakaran.
Pastikan untuk memasang produk secara benar dengan menggunakan rangka pemasangan standar yang disediakan.
Penggunaan rangka pemasangan yang tidak benar dan pemasangan yang tidak benar dapat menyebabkan peralatan jatuh, yang mengakibatkan cedera.
Untuk tipe kesatuan saja
Pastikan untuk memasang produk secara aman dalam rangka pemasangan yang dipasang di rangka jendela.
Jika unit tidak dipasang dengan aman, akan jatuh dan menyebabkan cedera.
Untuk tipe kesatuan saja
Saat mengganti baterai koin di remote kontrol, pastikan membuang baterai lama untuk mencegah anak-anak menelannya. Jika seorang anak menelan baterai koin, segera periksakan ke dokter.
Perhatian
Pemasangan pemutus kebocoran diperlukan dalam beberapa kasus tergantung pada kondisi tempat pemasangan, untuk mencegah sengatan listrik.
Jangan memasang peralatan di tempat yang ada kemungkinan terjadinya kebocoran gas mudah terbakar.
Jika gas mudah terbakar bocor dan berada di sekitar unit, dapat menyebabkan kebakaran.
Periksa untuk melihat apakah komponen-komponen dan kabel terpasang dan terhubung dengan benar, dan apakah sambungan di terminal telah disolder atau diatur dengan aman. Pemasangan dan sambungan yang tidak tepat dapat menyebabkan timbulnya panas berlebihan, kebakaran atau sengatan listrik.
Jika platform atau rangka pemasangan telah berkarat, menggantinya. Platform atau rangka pemasangan yang berkarat dapat menyebabkan unit jatuh, yang mengakibatkan cedera.
Periksa arde (pembumian), dan memperbaikinya jika peralatan dibumikan dengan tidak benar. Pembumian yang tidak tepat dapat menyebabkan sengatan listrik.
Pendahuluan SiMT281515E
viii
Perhatian
Pastikan untuk mengukur hambatan isolasi setelah perbaikan, dan pastikan bahwa
hambatannya sebesar 1 M atau lebih. Isolasi yang rusak dapat menyebabkan sengatan listrik
Pastikan untuk memeriksa saluran pembuangan unit indoor setelah perbaikan. Saluran pembuangan yang rusak dapat menyebabkan air masuk ke ruangan dan membasahi furnitur dan lantai.
Jangan memiringkan unit saat melepaskannya. Air di dalam unit bisa tumpah dan membasahi furnitur dan lantai.
Pastikan untuk memasang kemasan dan segel pada rangka pemasangan dengan benar. Jika kemasan dan segel tidak terpasang dengan baik, air dapat masuk ke dalam ruangan dan membasahi furnitur dan lantai.
Untuk tipe kesatuan saja
1.2 Ikon yang Digunakan Ikon digunakan untuk menarik perhatian pembaca untuk informasi spesifik. Arti dari setiap ikon dijelaskan
dalam tabel di bawah:
Ikon Tipe
Informasi Deskripsi
Catatan:
Catatan "Catatan" memberikan informasi yang tidak diperlukan, tetapi mungkin tetap berharga untuk pembaca, seperti tips dan trik.
Perhatian
Perhatian "Perhatian" digunakan ketika ada bahaya dimana pembaca, melalui manipulasi yang salah, dapat merusak peralatan, kehilangan data, mendapatkan hasil yang tak diinginkan atau harus memulai ulang (bagian dari) prosedur.
Peringatan
Peringatan "Peringatan" digunakan bila ada bahaya cedera pribadi.
Referensi "Referensi" memandu pembaca ke tempat-tempat lain di buku ini atau dalam panduan ini, di mana dia akan menemukan informasi tambahan tentang topik tertentu.
SiMT281515E
1 Informasi Umum
Bagian 1
Informasi Umum
1. Nama Model Unit Indoor / Outdoor ......................................................... 2
2. Penampilan eksternal ................................................................................ 3
SiMT281515E Nama Model Unit Indoor / Outdoor
Informasi Umum 2
1. Nama Model Unit Indoor / Outdoor
Unit Indoor Unit Outdoor Asupan Catu Daya
Tipe Nama Model Nama Model
Tipe Tekanan statis tinggi dan menengah sambungan Duct
FBQ100EVE(4) RZR100LUY1(4)
Unit Indoor: 1 fasa, 50 Hz, 220 - 240 V
Unit Outdoor : 3 fasa, 50 Hz, 380 - 415 V
FBQ125EVE(4) RZR125LUY1(4)
FBQ140EVE(4) RZR140LUY1(4)
FBQ60EVE(4) × 2 RZR125LUY1(4)
FBQ71EVE(4) × 2 RZR140LUY1(4)
3 Informasi Umum
SiMT281515E
( )
2. Penampilan eksternal Unit Indoor
FBQ-E
Remote kontrol berkabel
BRC1C61 BRC1D61 BRC1E62
Remote kontrol nirkabel
BRC4C66
unit penerima sinyal
Unit Outdoor
RZR100LUY1(4) RZR125LUY1(4) RZR140LUY1(4)
External Appearance SiMT281515E
Fungsi - Fungsi 4
Bagian 2
Fungsi-Fungsi
1. Fungsi-Fungsi ............................................................................................ 5
5 Fungsi-fungsi
SiMT281515E
1. Fungsi- Fungsi
Kategori Fungsi unit Indoor FBQ60-140EVE(4)
unit Outdoor RZQ100-140LUY1(4)
Kontrol inverter
Kenyamanan
Ayunan otomatis —
Pilihan pola ayunan —
Fungsi pencegahan aliran udara dingin (pemanasan) —
Aliran udara naik turun sendiri —
Kecepatan kipas dapat diganti (3 langkah)
Laju aliran udara otomatis (*3)
Mode kecepatan kipas tinggi —
Program “Dry”
Aplikasi plafon tinggi —
Dua sensor suhu yang dapat dipilih (*1)
Mulai panas (setelah pencairan bunga es) —
Pendinginan sepanjang tahun berlaku
Operasi kebisingan malam rendah (*2)
Remote Kontrol
Pengaturan ulang otomatis Setpoint (*5)
Pengaturan rentang Setpoint (*5)
Pengatur waktu jadwal mingguan (*3)
Pengatur waktu mati (off timer) (diprogram) (*5)
Pengatur waktu Nyala/mati (On/Off timer) (*6)
Kebersihan
Filter udara anti-bakteri (*4)
Filter udara tahan jamur —
Penampung saluran anti bakteri ion perak
Penampung saluran tahan jamur —
Kerja & penservisan
Mekanisme pompa saluran
Diisi daya sebelumnya hingga 30 m (*2)
Diisi daya sebelumnya hingga 10 m (*2) —
Filter tahan lama (*4)
Tanda Filter
Pencegahan pengotor plafon —
Deteksi tekanan gas rendah (*2)
Operasi darurat
Fungsi diagnosis sendiri
Fitur kendali
Memulai ulang otomatis
Penggantian pemanasan/pendinginan otomatis —
Kontrol dengan 2 remote kontrol
Kontrol grup dengan 1 remote kontrol
Kontrol perintah eksternal (*4)
Remote kontrol terpusat
Kendali interlock
Standar komunikasi DIII-NET
Pilihan
Filter efisiensi tinggi
Filter sangat tahan lama —
Perkakas asupan udara segar —
Lain-lain Penukar panas anti korosi (*2)
Catatan: : Tersedia
—: Tidak tersedia
*1: Berlaku jika remote kontrol berkabel digunakan
*2: Untuk unit outdoor
*3: Berlaku jika BRC1D61 atau BRC1E62 digunakan
*4: Pilihan
*5: Berlaku jika BRC1E62 digunakan
*6: Berlaku jika BRC1C61 digunakan
Fungsi-fungsi SiMT281515E
Remote Kontrol 6
Bagian 3
Remote Kontrol
1. Remote kontrol Berkabel ........................................................................... 7 1.1 Model yang berlaku ..............................................................................7
1.2 Nama dan Fungsi .................................................................................8
1.3 Pengaturan MAIN/SUB saat menggunakan 2 Remote Kontrol .............12
1.4 Pengaturan Nomor Grup Kontrol Terpusat ..........................................13
1.5 Mode Servis .......................................................................................15
1.6 Mode Inspeksi ....................................................................................19
2. Remote Kontrol Nirkabel ........................................................................ 20 2.1 Model yang Berlaku ............................................................................20
2.2 Nama dan Fungsi ...............................................................................20
2.3 Pengaturan MAIN/SUB dan Alamat ....................................................22
7 Remote Kontrol
SiMT281515E Remote Kontrol Berkabel
1. Remote kontrol berkabel
1.1 Model yang berlaku
Seri Model FBQ-E
Remote Kontrol BRC1C61
Remote kontrol berkabel dengan Pengatur Waktu Jadwal Mingguan
BRC1D61
Remote Kontrol Navigasi BRC1E62
Remote Kontrol 8
Remote Kontrol Berkabel SiMT281515E
C
1.2 Nama dan Fungsi 1.2.1 BRC1C61
4 2 1
14 13 15 16 20
1. Tombol ON/OFF
Tekan tombol ini dan sistem akan mulai. Tekan tombol ini
lagi dan sistem akan berhenti.
2. Lampu OPERATION (MERAH)
lampu ini menyala selama operasi.
3. TAMPILAN “ ” (DI BAWAH KENDALI
TERPUSAT)
Ketika muncul tampilan ini, sistem berada DI BAWAH
KENDALI TERPUSAT.
(Ini bukan spesifikasi standar)
4. Tampilan “ ” “ ” “ ” (MODE OPERASI)
Tampilan ini menunjukkan MODE OPERASI saat ini.
11. TAMPILAN TIDAK BERFUNGSI
Jika fungsi tertentu tidak tersedia, tekan tombol ini akan
menampilkan kata “NOT AVAILABLE” selama beberapa detik.
12. Tombol START/STOP MODE PENGATUR WAKTU
13. Tombol ON/OFF PENGATUR WAKTU
14. Tombol OPERASI UJI COBA/INSPEKSI
Tombol ini digunakan hanya oleh orang servis yang
memenuhi syarat untuk tujuan pemeliharaan.
Jangan menggunakannya dalam operasi normal.
15. Tombol WAKTU PEMROGRAMAN
Gunakan tombol ini untuk memprogram waktu “START dan/atau STOP”.
16. Tombol PENGATURAN SUHU
5. TAMPILAN “ TEST ” (OPERASI UJI COBA/INSPEKSI) Gunakan tombol ini untuk MENGATUR SUHU termostat.
Ketika TOMBOL OPERASI UJI COBA/INSPEKSI ditekan, tampilan menunjukkan mode sistem berada di dalam.
17.Tombol ATUR ULANG TANDA FILTER
6. TAMPILAN “
hr
” (WAKTU YANG DIPROGRAM)
hr
18.Tombol KONTROL KECEPATAN KIPAS
Tekan tombol ini untuk memilih kecepatan kipas, RENDAH atau TINGGI, tergantung pilihan anda.
Tampilan ini menunjukkan WAKTU YANG DIPROGRAM
sistem memulai atau berhenti.
7. TAMPILAN “ ” (SUHU YANG DIATUR)
Tampilan ini menunjukkan suhu yang diatur.
8. TAMPILAN “ L H
” (KECEPATAN KIPAS)
Tampilan ini menunjukkan kecepatan kipas: “RENDAH” atau “TINGGI”.
9. TAMPILAN “ ” (KISI-KISI ALIRAN UDARA)
10. TAMPILAN “ ” (WAKTU UNTUK MEMBERSIHKAN FILTER UDARA)
19. Tombol PEMILIH MODE OPERASI
Tekan tombol ini untuk memilih MODE OPERASI.
20. Tombol PENYESUAI ARAH ALIRAN UDARA
CATATAN
Untuk kepentingan penjelasan, semua indikasi ditampilkan
pada tampilan tersebut berbeda dengan situasi sebenarnya
saat berjalan.
C: 3P177429-9S
3
6
5 7
12
8 10
9 11
19
18
17
9 Remote Kontrol
SiMT281515E Remote Kontrol Berkabel
˚C
˚C ”
1.2.2 BRC1D61
1. Tombol ON/OFF ”
Tekan tombol ON/OFF untuk memulai atau menghentikan sistem.
2. Lampu Operasi ”
Lampu operasi menyala selama operasi atau berkedip jika terjadi kesalahan.
3. Ikon mode operasi ” “ ” ”
Ikon-ikon ini mengindikasikan mode operasi saat ini (FAN, DRY, COOLING).
4. Ikon mode ventilasi
“ ”“ ”“ ” Ikon-ikon ini mengindikasikan mode ventilasi saat ini (ventilator pembaruan panas saja) (AUTOMATIC, HEAT EXCHANGE, BYPASS).
5. Ikon ventilasi ”
Ikon ventilasi muncul jika ventilasi disesuaikan dengan tombol jumlah ventilasi (ventilator pembaruan panas saja). Secara bersamaan, jumlah ventilasi ditunjukkan dengan ikon kecepatan kipas (lihat 22).
6. Ikon pembersih udara ”
Ikon ini menunjukkan bahwa unit pembersih udara (pilihan) bersifat opsional.
7. Ikon leave home “ ”
Ikon leave home menunjukkan status fungsi leave home.
”
Ikon ini menunjukkan bahwa pengendali lain dengan prioritas lebih tinggi mengendalikan atau menonaktifkan instalasi Anda.
9. Ikon penggantian di bawah kontrol
terpusat “ ”
Ikon ini menunjukkan bahwa penggantian instalasi di bawah kontrol terpusat yang ditetapkan untuk unit indoor lain atau pemilih dingin /panas opsional yang terhubung ke unit outdoor (= remote kontrol utama).
10. Indikator hari dalam seminggu “MON TUE WED THU FRI SAT SUN”
Indikator hari dalam seminggu menunjukkan hari minggu saat ini (atau hari yang diatur ketika membaca atau memprogram pengatur waktu jadwal).
11. Tampilan jam “88:88”
Tampilan jam menunjukkan waktu saat ini (atau waktu tindakan ketika membaca atau memprogram pengatur waktu jadwal).
12. Suhu yang diatur maksimum “88 max”
Suhu yang diatur maksimum menunjukkan suhu yang diatur maksimum ketika dalam operasi batas.
13. Suhu yang diatur minimum “88 min
Suhu yang diatur minimum menunjukkan suhu yang diatur minimum ketika dalam operasi batas.
14. Ikon pengatur waktu jadwal ”
Ikon ini menunjukkan bahwa pengatur waktu jadwal diaktifkan.
C: 3P107422-3D
3 6 7 8 9 2 1
4 12 14 17
10 11
22
24
16 13 28
1518 19 20 21 5 32
23
25 34
26 35
36
27 29 30 31 33
8. Ikon kontrol eksternal control icon “
Menyala (ON) Leave home diaktifkan.
Berkedip Leave home aktif.
Mati (OFF) Leave home dinonaktifkan.
Remote Kontrol 10
Remote Kontrol Berkabel SiMT281515E
15. Ikon tindakan “1 2 3 4 5”
Ikon-ikon ini menunjukkan tindakan untuk setiap hari dari pengatur waktu jadwal.
16. Ikon non-aktif “OFF”
Ikon ini menunjukkan bahwa tindakan non-aktif(OFF) dipilih ketika memprogram pengatur waktu jadwal.
17. Inspeksi yang diperlukan ” dan ”
Ikon-ikon ini menunjukkan bahwa inspeksi diperlukan. Konsultasikan dengan installer Anda.
18. Tampilan suhu yang diatur “ ”
Ini menunjukkan suhu instalasi yang diatur saat ini (tidak ditampilkan dalam operasi LIMIT atau mode FAN atau DRY).
19. Pengaturan “SETTING”
Tidak digunakan, untuk tujuan servis saja.
20. Ikon arah aliran udara “ ”
Ikon ini menunjukkan arah aliran udara (hanya untuk instalasi dengan kisi-kisi aliran udara bermotor).
21. Tidak tersedia ”
“ ” ditampilkan kapanpun ketika pilihan tidak terpasang dialamatkan atau fungsi tidak tersedia.
22. Ikon kecepatan kipas “ ” ” ” ”
Ikon ini menunjukkan kecepatan kipas yang diatur.
23. Ikon waktu pembersihan filter udara “ ”
Ikon ini menunjukkan filter udara harus dibersihkan. Baca panduan tentang unit indoor.
24. Ikon waktu pembersihan Elemen “ ”
Ikon ini menunjukkan elemen harus dibersihkan (ventilator pembaruan panas saja).
25. Tombol mode ventilasi “ ”
Tombol mode ventilasi beroperasi pada ventilator pembaruan panas; lihat panduan ventilator pembaruan panas untuk lebih jelasnya
26. Tombol jumlah ventilasi “ ”
Tombol ini mengatur jumlah ventilasi; lihat panduan ventilator pembaruan panas untuk lebih jelasnya.
27. Tombol UJI COBA/INSPEKSI “ ”
Tidak digunakan, hanya untuk tujuan servis.
28. Tombol Pemrograman “ ”
Tombol ini adalah tombol multi tujuan. Tergantung pada manipulasi pengguna sebelumnya, tombol pemrograman dapat memiliki berbagai fungsi.
29. Tombol pengatur waktu jadwal ”“ ”
Tombol ini mengaktifkan atau menonaktifkan pengatur waktu jadwal.
30. Tombol penyesuai waktu “ ”“ ”
Tombol ini digunakan untuk menyesuaikan jam atau, ketika dalam mode pemrograman, untuk menyesuaikan waktu tindakan yang diprogram. Kedua tombol memiliki fungsi pengulang otomatis (auto-repeat).
31. Tombol penyesuai suhu “ ”“ ” Tombol ini digunakan untuk menyesuaikan setpoint
saat ini atau, ketika dalam mode pemrograman, untuk menyesuaikan suhu setpoint yang diprogram (step = 1˚C). Kedua tombol juga digunakan untuk menyesuaikan hari dalam seminggu.
32. Tombol min-max/ perubahan operasi “ ”
Tombol ini merupakan tombol multi tujuan. Tergantung pada manipulasi pengguna sebelumnya, tombol ini dapat memiliki fungsi sebagai berikut:
(1) Pilih mode operasi instalasi (FAN, DRY, COOLING)
(2) Beralih di antara suhu minimum dan suhu maksimum ketika dalam operasi batas
33. Tombol batas/ setpoint “ ” “ ”
Tombol ini mengganti mode antara setpoint, operasi batas atau OFF (mode pemrograman saja).
34. Tombol kecepatan kipas “ ” ”
Tombol ini mengganti antara L (rendah), H
(tinggi), HH (sangat tinggi), (otomatis).
35. Tombol penyesuai arah aliran udara “ ”
Tombol ini memungkinkan untuk menyesuaikan arah aliran udara.
36. Tombol pengatur ulang ikon waktu pembersihan
filter udara “ ”
Tombol ini digunakan untuk mengatur ulang ikon waktu pembersihan filter udara.
C: 3P107422-3D
11 Remote Kontrol
SiMT281515E Remote Kontrol Berkabel
1.2.3 BRC1E62
1 11
4 5 6 7
9
8
3
10
2
1. Tombol Pemilih Mode Digunakan untuk memilih mode operasi.
2. Tombol pengaturan aliran udara
Digunakan untuk menunjukkan laju aliran udara ( Volume Udara/ Kecepatan Kipas) / Layar arah aliran udara.
3. Tombol Menu/Enter • Digunakan untuk menunjukkan menu utama.
(Untuk rincian menu utama, lihat panduan operasi.) • Digunakan untuk memasukkan item pengaturan
yang dipilih.
4. Tombol naik " " • Digunakan untuk menaikkan suhu yang diatur. • Gunakan untuk menyorot item di atas pilihan saat
ini. (item yang disorot akan bergulir terus ketika tombol terus ditekan.)
• Digunakan untuk mengubah item yang dipilih.
5. Tombol Turun " " • Digunakan untuk menurunkan suhu yang diatur. • Gunakan untuk menyorot item di bawah pilihan saat
ini. (item yang disorot akan bergulir terus ketika tombol terus ditekan.)
• Digunakan untuk mengubah item yang dipilih.
6. Tombol Kanan " " • Digunakan untuk menyorot item berikutnya di
sisi kanan. • Isi Tampilan berubah ke layar berikutnya per
halaman.
7. Tombol kiri " " • Digunakan untuk menyorot item berikutnya di
sisi kiri. • Isi Tampilan berubah ke layar sebelumnya per
halaman. 8. Tombol ON/OFF • Tekan tombol ini dan sistem akan mulai. • Tekan tombol ini lagi dan sistem akan berhenti.
9. Lampu operasi (Hijau)
Lampu ini menyala selama operasi. lampu berkedip jika terjadi kesalahan.
10. Tombol pembatalan
• Digunakan untuk kembali ke layar sebelumnya. • Tekan dan tahan tombol ini selama 4 detik atau
lebih untuk menampilkan menu Pengaturan Servis.
11. LCD (dengan lampu latar)
cahaya latar akan menyala selama kurang lebih 30 detik dengan menekan setiap tombol operasi.
Remote Kontrol 12
Remote Kontrol Berkabel SiMT281515E
1.3 Pengaturan MAIN/SUB ketika menggunakan 2 Remote Kontrol
Situasi
Pengaturan MAIN/SUB diperlukan jika 1 unit indoor dikendalikan dengan 2 remote kontrol. Jika anda
menggunakan 2 remote kontrol (panel kontrol dan remote kontrol terpisah), Atur salah satu sebagai MAIN
dan lainnya sebagai SUB.
Pengaturan
Remote kontrol pengaturan pabrik ke MAIN, sehingga Anda hanya perlu mengubah salah satu remote
kontrol dari MAIN ke SUB. Untuk mengubah remote kontrol dari MAIN ke SUB, lakukan sebagai berikut:
1.3.1 BRC1C61/BRC1D61
Langkah Tindakan
1 Masukkan obeng pipih ke dalam ceruk antara bagian atas dan bawah remote kontrol, seperti yang ditunjukkan pada ilustrasi di bawah ini. Pelan-pelan bongkar bagian atas remote kontrol, kerjakan dari 2 posisi yang mungkin.
Bagian atas
remote kontrol
Bagian bawah remote
kontrol
2 Ubah saklar perubah MAIN/SUB pada PCB ke posisi “S”.
Saklar diatur ke posisi
M MAIN (pengaturan pabrik)
S
M
S Atur saklar ke posisi SUB.
1.3.2 BRC1E62 Penunjukkan Remote kontrol utama dan sub dapat ditukar. Perhatikan bahwa perubahan ini dengan
mematikan daya ( OFF) dan kemudian menyalakan (ON) lagi.
menu pengaturan
bidang
ditampilkan
Item 2
ditampilkan
.
Layar dasar
ditampilkan.
Tekan
tombol Cancel
sekali.
tekan dan tahan tombol Cancel selama 4 detik atau lebih
Pilih "Switch Main Sub Controller" dan tekan tombol
Menu/Enter.
Pilih "Main RC" atau
"Sub RC" dengan
menggunakan
tombol ▲/▼
(Up/Down), dan
kemudian tekan
tombol Menu/Enter.
Tekan tombol Menu/Enter.
Tekan tombol Cancel.
Item 2
ditampilkan
.
13 Remote Kontrol
SiMT281515E Remote Kontrol Berkabel
TEST
TEST
1.4 Pengaturan Nomor Grup Kendali Terpusat 1.4.1 BRC1C61/BRC1D61
Dalam rangka untuk melakukan remote kontrol terpusat dengan menggunakan remote kontrol pusat dan
pengendali ON/OFF terpadu, Pengaturan nomor Grup harus dibuat oleh grup dengan menggunakan
remote kontrol pengoperasian.
Lakukan pengaturan nomor Grup untuk remote kontrol terpusat dengan menggunakan remote kontrol pengoperasian.
1. Selama dalam mode normal, tekan dan tahan saklar “ ” selama 4 detik atau lebih untuk
mengatur sistem ke "Mode Pengaturan Bidang (Field Setting Mode)".
2. Pilih Nomor MODE “00” dengan tombol “ ”.
3. Gunakan tombol “ ” untuk memilih Nomor grup untuk setiap grup. (Nomor grup meningkat dalam urutan 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
4. Tekan “ ” atau “ ” untuk mengatur nomor grup yang dipilih. 5. Tekan “ ” untuk kembali ke MODE NORMAL.
BRC1C61
BRC1D61
Catatan :
Untuk nomor grup pengaturan ventilator pembaruan panas dan adaptor pengkabelan untuk pendingin ruangan lain, dll., Lihat panduan operasi.
CATATAN
Masukkan nomor grup dan tempat instalasi unit indoor ke dalam tabel instalasi yang terlampir. Pastikan
untuk menyimpan tabel instalasi ini bersama dengan panduan operasi untuk pemeliharaan.
4
NO. MODE NO. GRUP
MODE
PENGATUR
AN BIDANG
4
NO. MODE NO. GRUP
MODE
PENGATUR
AN BIDANG
Remote Kontrol 14
Remote Kontrol Berkabel SiMT281515E
1.4.2 BRC1E62 < Group No. Setting (Group)>
Layar dasar ditampilkan.
Menu Field
setting
ditampilkan
Item 2
ditampilkan
Item 2
ditampilkan.
Pilih "Group No. setting"
dan kemudian tekan Tombol Menu/Enter.
Tekan tombol
Cancel sekali.
Layar dasar ditampilkan.
Menu Field
setting
ditampilkan.
Item 2
ditampilkan.
Item 2 is
displayed.
Item 2 ditampilkan.
Pilih "Group No. setting"
dan kemudian tekan Tombol Menu/Enter.
Tekan tombol Cancel sekali.
Item 2
ditampilkan.
Tekan Tombol
Cancel sekali
Tekan dan tahan tombol Cancel selama 4 detik atau
lebih
Pilih "Group No. setting (Group)" dan kemudian tekan tombol Menu/Enter
Pilih Group No. yang diinginkan dengan menggunakan tombol (Up/Down) ▲/▼, dan kemudian tekan tombol Menu/Enter
Tekan tombol Menu/Enter
Tekan Tombol
Cancel sekali
Tekan dan tahan tombol Cancel selama 4 detik atau
lebih
Item 2 ditampilkan.
Tekan tombol
Menu/Enter
Pilih Group No. yang diinginkan dengan menggunakan tombol (Up/Down) ▲/▼, dan kemudian tekan tombol Menu/Enter
Tekan tombol
Cancel sekali
Pilih “Group No. setting (Unit)” dan kemudian
tekan tombol
Menu/Enter
Tekan Tombol
Cancel sekali
15 Remote Kontrol
SiMT281515E Remote Kontrol Berkabel
1.5 Mode Servis 1.5.1 BRC1C61/BRC1D61
(1) Menampilkan Data Servis
1. Masuk mode pengaturan bidang.
Tekan tombol operasi INSPECTION/TEST selama 4 detik atau lebih.
2. Masuk mode servis.
Setelah masuk mode pengaturan bidang, Tekan tombol operasi INSPECTION/TEST selama 4 detik atau
lebih.
3. Pilih No. mode
Atur No. mode yang diinginkan dengan tombol pengaturan suhu up/down.
4. Pilih No. unit
Pilih No. unit indoor yang diatur dengan tombol START/STOP mode waktu.
5. Pilih error history No. (nomor riwayat kesalahan) yang diinginkan atau thermistor data No. (nomor data
termistor) dengan tombol “ ” atau “ ”. 6. Tampilan setiap data (Lihat tabel tampilan di bawah ini)
7. Kembali ke mode operasi normal.
Tekan tombol operasi INSPECTION/TEST sekali.
No. Mode Fungsi Isi dan Metode Operasi Contoh Tampilan Remote Kontrol
40 Riwayat Kesalahan
Anda dapat mengubah riwayat ini dengan tombol up-down waktu pemrograman.
Past error
code
UNIT No. 1 40 CODE 2-C4 SETTING
Error history 1: Newest
3: Oldest "00" displayed for 4 and subsequent.
41 Tampilan Data Termistor
Pilih display thermistor dengan tombol up-down waktu pemrograman
Thermistor type
Temperature
UNIT No. 01 41 27 SETTING
Display thermistor 00: Termistor suhu kamar di remote
kontrol 01: Termistor udara hisap 02: Termistor penukar panas
No. Kode
Kedua
No. Kode
Pertama .
3 4
1 2 7 6
5 3
No. Unit No. Mode
Mode
Pengatura
n Bidang
Remote Kontrol 16
Remote Kontrol Berkabel SiMT281515E
UNIT No.
SETTING
(2) Pengaturan servis
1. Masuk mode pengaturan bidang.
Terus tekan tombol operasi INSPECTION/TEST setidaknya selama 4 detik.
2. Masuk mode pemeliharaan.
Setelah masuk mode pengaturan bidang, terus tekan tombol operasi INSPECTION/TEST setidaknya
selama 4 detik.
3. Pilih No. mode
Atur No. mode yang diinginkan dengan tombol pengatur suhu up/down. (Mode 43 hanya dapat
dilakukan untuk remote kontrol nirkabel)
4. Pilih No. unit
Pilih No. unit indoor yang diatur dengan tombol START/STOP MODE TIME.
(Pilih No. unit indoor dengan tombol up/down untuk remote kontrol nirkabel.)
5. Lakukan pengaturan yang diperlukan untuk setiap mode. (Mode 43 hanya dapat dilakukan untuk remote kontrol nirkabel)
• Dalam hal Mode 43
Tekan TOMBOL TIMER ON/OFF untuk menentukan Kipas Dinyalakan paksa (forced Fan ON).
• Dalam hal Mode 44
Atur “Kecepatan kipas (Fan speed)” dengan TOMBOL KONTROL KECEPATAN KIPAS dan “Arah
aliran udara (Airflow direction)” dengan TOMBOL PENYESUAI ARAH ALIRAN UDARA, kemudian
tekan TOMBOL TIMER ON/OFF untuk menentukannya.
• Dalam hal Mode 45
Pilih No. unit yang diubah dengan tombol “ ” atau “ ”, lalu tekan TOMBOL TIMER ON/OFF untuk
menentukannya.
6. Kembali ke mode operasi normal.
Tekan tombol operasi INSPECTION/TEST sekali.
No. Mode Fungsi Isi dan Metode Operasi Contoh Tampilan Remote Kontrol
43 Kipas Dinyalakan paksa
Menyalakan kipas untuk setiap unit secara individual.
44 Pengaturan
individual Mengatur kecepatan kipas dan arah aliran udara untuk setiap unit secara individual ketika menggunakan kendali grup.
Fan 1 : Low speed 3 : High 0: Upper
Airflow direction
UNIT No. 4: Lowest
CODE SETTING
Pengaturan dilakukan dengan menggunakan tombol “airflow direction adjust” dan “fan speed adjust”.
45 Perubahan No. Unit
Mengubah No. Unit
Mengatur No. unit setelah melakukan perubahan dengan tombol up-down waktu pemrograman.
NO. KODE
PERTAMA
NO. UNIT
NO. KODE
KEDUA
NO. MODE
3 4
MODE FIELD
SETTING
1 2 6
5 5 3
NO. MODE
MODE FIELD SETTING
4, 5
4, 5
NO. KODE KEDUA
NO. KODE PERTAMA
3
1, 2, 6
17 Remote Kontrol
SiMT281515E Remote Kontrol Berkabel
1.5.2 BRC1E62 Mengoperasikan remote kontrol memungkinkan data servis untuk diperoleh dan berbagai servis untuk diatur.
Pilih No. Unit yang
diinginkan dengan
menggunakan tombol
(Up/Down)▲/▼. Data yang
sesuai akan ditampilkan.
Menu Servis Item 2 Keterangan
1. Nama Model 1. Unit No. Pilih No. Unit yang anda ingin periksa.
2. Indoor unit 3. Outdoor unit
2. Jam operasi 1. Unit No. Pilih No. Unit yang anda ingin periksa.
2. Indoor unit operating time
Semua ini ditampilkan dalam jam.
3. Indoor unit fan operation time
4. Indoor unit energized time
5. Outdoor unit operating time
6. Outdoor unit fan 1 operation time
7. Outdoor unit fan 2 operation time
8. Outdoor comp. 1 operation time
9. Outdoor comp. 2 operation time
3. Status Unit Indoor 1/3 1. Unit No. Pilih No. Unit yang anda ingin periksa.
2. FAN Tap, kecepatan (rpm)
3. FLAP Berayun, tetap
4. Speed Kecepatan kipas (rpm)
5. EV Derajat katup ekspansi elektronik terbuka (pulsa)
6. MP ON/OFF pompa saluran
7. EH ON/OFF Pemanas listrik
8. Hu ON/OFF kelembaban udara
9. TbF ON/OFF kendali Anti-pembekuan
3. Status Unit Indoor 2/3 1. FLOAT 2. T1/T2
Layar dasar
ditampilkan.
Menu pengaturan
servis ditampilkan.
menu
Maintenance ditampilkan
.
Item 2
ditampilkan
.
Tekan tombol
Cancel
sekali.
Tekan dan tahan tombol Cancel selama 4 detik atau lebih.
Tekan tombol Cancel.
Tekan
tombol
Cancel
sekali.
Tekan dan tahan
tombol Cancel selama 4
detik atau lebih.
Pilih item yang diinginkan dari
menu Maintenance, dan kemudian
tekan tombol Menu/Enter .
Tekan tombol Cancel.
Remote Kontrol 18
Remote Kontrol Berkabel SiMT281515E
Menu Servis Item 2 Keterangan 3. Tampilan Status Indoor
3/3 1. Unit No. Pilih Unit No. yang ingin anda periksa.
2. Th1 Termistor udara hisap
3. Th2 Termistor penukar panas
4. Th3 —
5. Th4 Termistor udara buangan
6. Th5 —
7. Th6 —
4. Tampilan Status Unit Outdoor 1/2
1. Unit No. Pilih Unit No. yang ingin anda periksa.
2. FAN Step Kecepatan kipas
3. COMP Frekuensi catu daya kompresor (Hz)
4. EV1 Derajat katup ekspansi elektronik terbuka
5. SV1 ON/OFF katup Solenoid
4. Tampilan Status Unit Outdoor 2/2
1. Th1 Termistor udara Outdoor
2. Th2 Termistor penukar panas
3. Th3 Termistor pipa pembuangan
4. Th4 5. Th5 6. Th6
5. Pencairan paksa (Tidak tersedia)
1. Forced defrost ON Mengaktifkan operasi pembersihan bunga es paksa.
2. Forced defrost OFF Menonaktifkan operasi pembersihan bunga es paksa.
6. Tampilan kesalahan 1. Display Error ON Menampilkan kesalahan pada layar.
2. Display Error OFF Menampilkan tidak ada kesalahan maupun peringatan.
3. Display warning ON Menampilkan peringatan pada layar jika terjadi kesalahan.
4. Display warning OFF Tidak ada peringatan ditampilkan.
7. No. Unit Swap 1. Current Unit No. Sebuah unit No. dapat dialihkan ke yang lain.
2. Transfer Unit No.
8. Nilai Sensor yang dialamatkan
Unit No.: 0 - 15 Pilihthe Unit No. yang anda ingin periksa.
Code 00: 01: 02: 03: 04: 05: 06: 07: 08: 09:
Termistor remote kontrol (°C) Termistor udara hisap (°C) Termistor pipa cair penukar panas (°C) Termistor pipa gas penukar panas (°C) No. alamat unit Indoor No. alamat unit Outdoor No. alamat unit BS No. alamat zona kendali No. alamat jumlah pendinginan/pemanasan No. alamat Demand.
Data Data yang sesuai akan ditampilkan, berdasarkan No. Unit dan Kode yang dipilih.
19 Remote Kontrol
SiMT281515E Remote Kontrol Berkabel
Test operation
1.6 Mode Inspeksi 1.6.1 BRC1C61/BRC1D61
Tampilan Normal (Layar kosong)
Tekan tombol INSPECTION/TEST sekali.
(1) mode Inspeksi
Unit 0
Error code L 0 Inspection
Kode kesalahan berkedip jika terjadi kesalahan.
(2) Kode model unit Indoor
(3) Kode model unit Outdoor
Catatan:
Mode Inspeksi tidak tersedia untuk BRC1E62.
Unit 0
Error code L 0 Inspection
– – –
5 U 2
– – –
2 A A
Tampilan Model
5U2 FBQ-E
Tampilan Model
2AA RZR
(1) Mode Inspeksi
Tekan tombol INSPECTION/TEST sekali
(2) Tampilan kode model unit Indoor
Tekan tombol INSPECTION/TEST sekali
(3) Tampilan kode model unit outdoor
Tekan tombol INSPECTION/TEST sekali
Tekan tombol INSPECTION/TEST sekali
Mode operasi uji coba
Remote Kontrol 20
Remote Kontrol Nirkabel SiMT281515E
(20)
1)
2. Remote Kontrol Nirkabel
2.1 Model yang berlaku Seri Model FBQ-E
Remote Kontrol BRC4C66
2.2 Nama dan Fungsi
(1)
(3)
(6)
(4)
(2)
(5)
(7)
Penerima
(18)
(22)
(19)
(2
ON OFF (8)
H L
C
DOWN (10)
ON OFF UP
FAN H M L
C
TEMP TIME (11)
hr. UP
hr. (9) DOWN
FAN (13)
RESERVE CANCEL
hr. TI MER
TEST hr. MODE
SWING
TEST
TEST
(12)
(15)
(14)
(16)
(17)
21 Remote Kontrol
SiMT281515E Remote Kontrol Nirkabel
3P107422-8S
12 TOMBOL START/STOP MODE TIMER
13 TOMBOL RESERVE/CANCEL TIMER
14 TOMBOL PENYESUAI ARAH ALIRAN
UDARA
15
TOMBOL PEMILIH MODE OPERASI
Tekan tombol ini untuk memilih MODE
OPERASI. “ ” (COOL), “ ”
(FAN),“ ” (DRY).
16
TOMBOL ATUR ULANG TANDA FILTER
Lihat bagian MAINTENANCE dalam panduan operasi yang terlampir pada unit indoor.
17
TOMBOL OPERASI UJI COBA / INSPEKSI
Tombol ini digunakan hanya oleh orang
servis yang memenuhi syarat untuk tujuan pemeliharaan.
18
SAKLAR OPERASI DARURAT
Saklar ini siap digunakan jika remote kontrol tidak bekerja.
19
PENERIMA
Menerima sinyal dari remote kontrol.
20
LAMPU INDIKATOR OPERASI (merah)
Lampu ini tetap menyala selama pendingin ruangan berjalan. Lampu berkedip saat unit bermasalah.
21 LAMPU INDIKATOR TIMER (Hijau)
Lampu ini tetap menyala selama timer diatur.
22
LAMPU INDIKATOR WAKTU
PEMBERSIHAN FILTER UDARA (Merah)
Menyala ketika saatnya untuk membersihkan filter udara.
1
TAMPILAN “ ” (TRANSMISI SINYAL)
Menyala ketika sinyal sedang dikirim.
2
TAMPILAN ” “ ” “ ” (MODE
OPERASI)
Tampilan ini menunjukkan MODE OPERASI saat ini.
3
H M L
TAMPILAN “ ” (SUHU YANG DIATUR) C
Tampilan ini menunjukkan suhu
yang diatur.
4
TAMPILAN “ hr. hr. ”
(WAKTU YANG DIPROGRAM)
Tampilan ini menunjukkan WAKTU YANG
DIPROGRAM mengenai sistem mulai atau berhenti.
5 TAMPILAN “ ” (SIRIP ALIRAN UDARA)
6 TAMPILAN “ ” “ ” “ ”( KECEPATAN KIPAS)
Tampilan ini menunjukkan kecepatan kipas yang diatur.
7
TAMPILAN “ TEST” (OPERASI
INSPEKSI/ UJI COBA)
Jika TOMBOL OPERASI INSPECTION/TEST ditekan, tampilan
menunjukkan mode sistem berada di dalam. Jangan mengoperasikan tombol
ini selama penggunaan normal.
8
TOMBOL ON/OFF
Tekan tombol ini dan sistem akan mulai. Tekan tombol ini lagi dan
sistem akan berhenti.
9
TOMBOL KONTROL KECEPATAN KIPAS
Tekan tombol ini untuk memilih
kecepatan kipas, Rendah atau Sedang
atau Tinggi, tergantung pilihan anda.
10
TOMBOL PENGATURAN SUHU
Gunakan tombol ini untuk MENGATUR
SUHU.
11
TOMBOL TIMER PEMOGRAMAN /
PENYESUAIAN SUHU
Gunakan tombol ini untuk pengaturan suhu
dan memprogram waktu “START dan/atau STOP”. (Beroperasi dengan penutup depan
remote kontrol yang terbuka.)
Remote Kontrol 22
Remote Kontrol Nirkabel SiMT281515E
2.3 Pengaturan MAIN/SUB dan Alamat Pendahuluan
Untuk mengatur remote kontrol nirkabel, Anda harus mengatur alamat untuk:
Penerima remote kontrol nirkabel.
Remote kontrol nirkabel.
Mengatur Alamat untuk Penerima
Alamat untuk penerima remote kontrol nirkabel adalah pengaturan pabrik ke 1. Untuk mengubah pengaturan
ini, lakukan sebagai berikut:
Atur saklar (SS2) alamat nirkabel pada PCB sesuai dengan tabel di bawah ini.
No. Unit No. 1 No. 2 No. 3
Saklar (SS2) alamat nirkabel
1 2
3
1 2
3
1 2
3
Bila menggunakan kedua remote kontrol berkabel dan nirkabel untuk 1 unit indoor, remote kontrol berkabel
harus diatur ke MAIN. Oleh karena itu, atur saklar (SS1) MAIN/SUB penerima ke SUB.
MAIN/SUB MAIN SUB
saklar (SS1) MAIN/SUB
S
M
S
M
Mengatur Alamat untuk Remote Kontrol Nirkabel
Alamat untuk remote kontrol nirkabel adalah pengaturan pabrik ke 1. Untuk mengubah pengaturan ini,
lakukan sebagai berikut:
1. Tahan tombol “ ” dan tombol “ ”
setidaknya selama 4 detik untuk masuk ke mode Field
Setting.
(Ditunjukkan di bidang tampilan pada gambar di sebelah kanan.)
2. Tekan tombol “ ” dan pilih beberapa pengaturan (A/ b).
Setiap kali tombol ditekan saklar tampilan antara “A”
dan ”b”
3. Tekan tombol “ ” atau tombol “ ” untuk mengatur
alamat.
Alamat dapat diatur dari 1 sampai 6, namun atur alamat
ke 1 ~ 3 dan untuk alamat yang sama sebagai penerima
(penerima tidak bekerja dengan alamat 4 ~ 6.)
4. Tekan tombol “ ” untuk masuk ke pengaturan.
5. Tekan tombol “ ” setidaknya selama 1 detik
untuk menghentikan mode Field Setting dan kembali ke
tampilan normal.
OW
1 2 3 4 5 6
23 Remote Kontrol
SiMT281515E Remote Kontrol Nirkabel
Beberapa pengaturan A/b
Ketika unit indoor sedang beroperasi dengan kontrol eksternal (remote kontrol pusat, dll), terkadang tidak
merespon perintah pengaturan suhu dan ON/OFF dari remote kontrol ini. Periksa apa pengaturan yang
diinginkan oleh pelanggan dan lakukan beberapa pengaturan seperti yang ditunjukkan di bawah ini.
Remote Kontrol FBQ-E
Beberapa pengaturan Tampilan remote kontrol Untuk mengendalikan unit dan pendingin ruangan lainnya Untuk selain di sebelah kiri
A: Standar
Semua item ditampilkan.
Perintah selain ON / OFF dan pengaturan suhu diterima. (1 BUNYI BIP PANJANG atau 3 BUNYI BIP PENDEK dikeluarkan )
b: Multi Sistem Operasi tetap ditampilkan tak lama setelah eksekusi. Semua perintah diterima (2 BUNYI BIP PENDEK)
SiMT281515E
Fungsi dan Kontrol 24
Bagian 4
Fungsi dan Kontrol
1. Fungsi Komponen Utama dan termistor (Diagram Pemipaan)................................................................................ 25
2. Garis besar fungsi .................................................................................... 28 2.1 Unit Indoor ............................................................................................28
2.2 Unit Outdoor ..........................................................................................29
3. Diagram Alir Operasi................................................................................ 30 3.1 Operasi Kering / Pendinginan ................................................................30
4. Rincian Fungsi ......................................................................................... 31 4.1 Unit Indoor .............................................................................................31
4.2 Unit Outdoor ..........................................................................................36
SiMT281515E Remote Kontrol Nirkabel
S1PH
S1NPH
C1220T-O
perpipaan bidang 15.9
R10T
Fu
ng
si da
n K
en
dalil
(B) katup ekspansi
elektronik
Filter
Penukar panas Outdoor
R2T R3T
Penukar panas Indoor
R4T
R3T
Sensor tekanan
(5/16" flare)
Saklar
Tekanan(tinggi)
R5T
R1T
R1T
unit Indoor
perpipaan bidang 9.5
C1220T-O
Katup penghenti
(dengan port servis 5/16"
flare)
Aki
R2T
(A) Kompresor
unit Outdoor
Termistor R10T terletak dekat kotak komponen listrik.
C: 3D079463
Fu
ng
si K
om
po
nen
uta
ma
dan
Te
rmis
tor (D
iag
ram
Pe
mip
aa
n)
SiM
T2
81
51
5E
1.
Fu
ng
si K
om
po
nen
uta
ma
dan
Te
rmis
tor
(Dia
gra
m P
em
ipaa
n)
RZ
R1
00
LU
Y1
(4)
25
Port pengukur
S1PH
R2T
S1NPH
R10T
26
(B) Katup ekspansi elektrik
Filter
Penukar panas Outdoor
R2T R3T
Penukar panas Indoor
Sensor tekanan
port pengukur
(5/16" flare)
Saklar tekanan (tinggi)
R1T
unit Indoor
Perpipaan bidang 9.5
C1220T-O
Perpipaan bidang 15.9
C1220T-O
Katup penghenti
(dengan port servis 5/16"
flare)
Aki
(A) Kompresor
unit Outdoor
Termistor R10T terletak dekat kotak komponen listrik.
C: 3D079464
R5T
R3T
R1T
R4T
SiM
T2
81
51
5E
F
un
gs
i ko
mp
on
en
uta
ma
da
n T
erm
isto
r (Dia
gra
m P
em
ipa
an
)
R
ZR
12
5L
UY
1(4
) / RZ
R1
40
LU
Y1
(4)
Fu
ng
si d
an K
en
da
li
Fungsi Komponen Utama dan Termistor (Diagram Pemipaan) SiMT281515E
27 Fungsi dan Kontrol
Unit Outdoor
(A) Kompresor
Unit pengerak Inverter mengubah frekuensi operasi kompresor untuk mengendalikan kapasitas dan faktor lainnya.
(B) Katup Ekspansi Elektronik (Y1E)
Memberikan kontrol untuk menjaga kondisi operasi optimum untuk efisiensi tinggi.
R1T (Termistor Udara Outdoor)
• Digunakan untuk kontrol kecepatan kipas unit outdoor.
• Digunakan untuk kontrol perbedaan tekanan.
• Digunakan untuk keseluruhan kontrol perlindungan arus.
R2T (Termistor Pipa Pembuangan) • Digunakan untuk perlindungan suhu pipa pembuangan selama operasi kompresi.
R3T (Termistor Pipa Hisap)
• Digunakan untuk kontrol super panas hisap dengan katup ekspansi elektronik.
R4T (Termistor Pipa Cair)
• Digunakan untuk mendeteksi suhu pipa cair.
R5T (Termistor Penukar Panas Sedang) • Digunakan untuk perhitungan tekanan tinggi selama operasi pendinginan.
(Dihitung berdasarkan suhu yang terdeteksi dan karakteristik refrigeran R-410A)
R10T (Termistor sirip Radiasi) • Digunakan untuk kontrol kecepatan kipas unit outdoor. • Digunakan untuk kontrol suhu sirip radiasi. • Digunakan untuk kontrol perbedaan tekanan.
S1NPH (Sensor Tekanan Tinggi)
• Digunakan untuk mendeteksi tekanan tinggi.
S1PH (Saklar Tekanan Tinggi) • Saklar diaktifkan pada tekanan tinggi untuk menghentikan operasi kompresor.
Unit Indoor
R1T (Termistor Udara Hisap)
R2T (Termistor Pipa Cair Penukar Panas Indoor)
R3T (Termistor Penukar Panas Indoor)
SiMT281515E Garis besar fungsi
Fungsi dan Kontrol 28
2. Garis Besar Fungsi
2.1 Unit Indoor
(Tidak disediakan untuk remote kontrol nirkabel.)
Unit Indoor
Kontrol Termostat
Sensor hisap Motor Kipas
Fungsi pemantauan
Pompa saluran Sensor Penukar Panas
Program Kering
Operasi Kipas Tampilan LED
Kontrol Pompa saluran
Bel, LED
Saklar apung Fungsi Pencegahan
Beku
Kontrol Kipas Unit Indoor
Jumlah Putaran Kipas Fungsi Pencegahan Udara
Dingin
Fungsi Penjagaan Mode
Operasi
Fungsi Deteksi Kesalahan
Fungsi Pencegahan
Pengotor Plafon
Saklar Operasi
Darurat Fungsi mulai ulang otomatis
Remote Kontrol
dengan Kristal cair
Sensor Remote
Kontrol
(Input) (Output)
(Fungsi)
2 termostat yang digunakan,
termostat hisap dan remote kontrol.
unit nirkabel saja
Kontrol Fasa
Unit nirkabel saja
ON/OFF
Kecepatan kipas, dll. Kecepatan kipas , dll
29 Fungsi dan Kontrol
SiMT281515E Diagram Alir Operasi
2.2 Unit Outdoor
Unit Outdoor
Termistor Udara Outdoor Kontrol ON/OFF Kompresor Kompresor
Termistor Penukar Panas Fungsi Siaga 3 menit Motor Kipas
Termistor Pipa Pembuangan Kontrol Kipas Unit Outdoor Katup Ekspansi elektronik
Termistor Pipa Hisap Kipas Unit Outdoor Mulai Tampilan LED
Termistor Penukar Panas Sedang
Kontrol Pendinginan Sepanjang tahun
Termistor sirip Radiasi Kontrol Katup Ekspansi Elektronik
PS untuk Perlindungan Tekanan Tinggi Kontrol OFF Termostat Paksa
Sensor Tekanan Tinggi Operasi uji coba
Trafo Arus Fungsi Deteksi Kesalahan
Sinyal Unit Indoor Fungsi Operasi tiruan
Saklar Pengaturan
(Input) (Output)
Fungsi dan Kontrol 30
Function Outline SiMT281515E
Operasi Darurat
Cooling/Dry
Penilaian termostat ON
kontrol startup
Penilaian awal operasi
pemulihan minyak
Penilaian termostat OFF
Ruang kontrol termostat
Thermostat OFF dengan
pencegahan beku
Penilaian
operasi remote
kontrol OFF
Penilaian
siaga
Penilaian
penghentian yang
tidak normal
operasi pemulihan minyak operasi residu pump down
Penilaian akhir operasi
pemulihan minyak
Memulai ulang siaga
Penilaian Mode
operasi
Darurat
B
Kontrol Normal
Kontrol langkah kompresor
Kontrol katup PI ekspansi elektronik
Kontrol perlindungan tekanan tinggi
Kontrol suhu pipa pembuangan
Kontrol perlindungan arus Inverter
Kontrol perlindungan suhu sirip radiasi
Kontrol perlindungan arus keseluruhan
Kontrol pendinginan suhu udara outdoor rendah
Operasi tiruan
A B
A
3. Diagram Alir Operasi
3.1 Operasi Kering/Pendinginan
Catu Daya Aktif ( ON)
Inisialisasi katup ekspansi elektronik
Inisialisasi mikro-komputer
Kontrol operasi sebelum pemanasan
Penilaian operasi Remote kontrol
Pendinginan/Kering
Indikasi kode
kesalahan
31 Fungsi dan Kontrol
SiMT281515E Rincian Fungsi
T Differential 1.0 or 1.5ºC (4) Tr
3 Operasi kering
Termo. OFF
(Tro: Suhu udara kamar saat startup)
2
Operasi kering
4. Rincian Fungsi
4.1 Unit Indoor 4.1.1 Ruang Kontrol Termostat
Berdasarkan perbedaan antara suhu yang diatur dengan remote kontrol dan suhu kamar yang sebenarnya
terdeteksi (1), termostat dinyalakan atau dimatikan.
Catatan:
1. Termistor untuk mendeteksi suhu kamar adalah sebagai berikut sesuai dengan pengaturan bidang.
a. Pengaturan pabrik: Termistor udara hisap dalam unit indoor
b. Saat mulai termistor suhu kamar: Termistor suhu kamar dalam remote kontrol
(1) Dalam Operasi Normal
T: Suhu kamar terdeteksi - Suhu diatur oleh remote kontrol
Dalam pendinginan
(2) Dalam Program Operasi Kering
Tro: Suhu udara kamar yang terdeteksi saat operasi kering dimulai
Tr: Suhu termistor kamar (terdeteksi oleh termistor suhu kamar)
T: Suhu kamar terdeteksi (Tr) – Suhu udara kamar saat startup (Tro)
Suhu
Startup Operasi Kering
Termostat ON
Termostat OFF
Waktu T < -1.0 or 1.5ºC (4)
(3)
T 0
(2)
4. Nilai ini berubah sesuai dengan model.
Operasi Normal
(Termostat ON) Termostat OFF
• T -0.5ºC terus berlanjut selama 1 menit. • T -2ºC
T +0.5ºC
Operasi kering Termostat OFF
atau
Fungsi dan Kontrol 32
Rincian Fungsi SiMT281515E
4.1.2 Menggunakan Kondisi untuk Termistor Suhu Kamar dalam
Remote Kontrol Berlaku
Termistor suhu kamar dalam remote kontrol hanya tersedia dalam remote kontrol berkabel.
Metode Termistor suhu kamar dalam remote kontrol yang standarnya dinonaktifkan untuk unit SkyAir.
Penggunaan termistor suhu kamar dalam remote kontrol dapat diaktifkan dengan mengubah pengaturan
bidang 10(20)-2-02 sampai 10(20)-2-01.
Kondisi
Tabel di bawah ini berisi kondisi di mana termistor suhu kamar dalam remote kontrol tidak digunakan:
Kondisi Termistor suhu kamar dalam remote kontrol tidak digunakan jika...
1 Ketidaknormalan termistor suhu kamar dalam remote kontrol.
2 Kontrol Grup digunakan.
3 Kombinasi suhu udara hisap / suhu yang diatur di luar jangkauan. (Lihat grafik di bawah ini)
pendinginan
Diagram dibawah ini menunjukkan rentang operasi kombinasi suhu udara hisap / suhu yang diatur dalam
operasi pendinginan: ˚C
32 Suhu yang diatur (Ts)
30
28
26
TH1 = Ts - 3
TH1 = Ts - 1
TH1 = Ts + 1
TH1 = Ts + 3
A B C D E F 24
22
20
18
16
12 14 16 18 20 22 24 26 ˚C
28 30 32 34
Rentang dimana
Rentang dimana
Suhu udara hisap (TH1)
Diferensial
Contoh
termistor dalam remote kontrol dapat digunakan
termistor udara hisap dalam unit indoor dapat digunakan
Dengan asumsi suhu yang diatur adalah 24 ° C atau lebih, dan suhu udara hisap telah berubah dari
18°C menjadi 30°C (A --> F):
(Contoh ini juga mengasumsikan ada beberapa pendingin ruangan lain, sistem VRV MATI, dan suhu
berubah bahkan ketika termistor suhu kamar dalam remote kontrol MATI.) Termistor udara hisap
dalam unit indoor digunakan untuk suhu dari 18°C - 23°C (A --> C).
Termistor suhu kamar dalam remote kontrol digunakan untuk suhu dari 23°C - 27°C (C --> E).
Termistor udara hisap dalam unit indoor digunakan untuk suhu dari 27°C - 30°C (E --> F).
Dan dengan asumsi suhu udara hisap telah berubah dari 30°C menjadi 18°C (F --> A):
Termistor udara hisap dalam unit indoor digunakan untuk suhu dari 30°C menjadi 25°C (F --> D).
Termistor suhu kamar dalam remote kontrol digunakan untuk suhu dari 25°C menjadi 21°C (D --> B).
Termistor udara hisap dalam unit indoor digunakan untuk suhu dari 21°C menjadi 18°C (B --> A).
33 Fungsi dan Kontrol
SiMT281515E Rincian Fungsi
4.1.3 Fungsi Identifikasi Unit Outdoor Tujuan
Tujuan fungsi identifikasi unit outdoor adalah untuk mengaktifkan unit indoor secara otomatis menentukan
mode operasi apapun harus diatur dalam fungsi dari tipe unit outdoor yang terhubung.
Mode operasi
Mode operasi yang mungkin adalah:
Unit Outdoor Mode operasi
Pendinginan saja Fan Cooling Program dry
Input yang digunakan
Fungsi identifikasi unit outdoor menggunakan input sebagai berikut:
Input Koneksi pada PCB unit indoor
Koneksi pada PCB unit outdoor
PCB unit Indoor TC & RC —
PCB unit Outdoor — TC & RC
TC: Transmission circuit (sirkuit transmisi)
RC: Receiving circuit (sirkuit penerima)
Fungsi dan Kontrol 34
Rincian Fungsi SiMT281515E
4.1.4 Kontrol Kipas Unit Indoor Garis besar
Selama kompresor memulai dan menghentikan kontrol, kipas unit indoor akan menerima instruksi dari unit
outdoor untuk melindungi kompresor dari menerima cairan dan untuk menjamin kompresor halus memulai:
Kontrol kipas unit Indoor selama kompresor berhenti
Kontrol kipas unit Indoor sebelum kompresor memulai
Kontrol kipas unit Indoor saat kompresor memulai
Selama kompresor berhenti
Pengatur kipas unit Indoor
Pendinginan Indoor Termostat OFF Pengaturan Remote Kontrol
Remote kontrol OFF OFF
Program kering Termostat OFF OFF
Remote kontrol OFF OFF
Sebelum kompresor memulai
Pengatur kipas unit Indoor
Pendinginan Indoor Pengaturan Remote Kontrol
Program kering L
4.1.5 Kontrol Pompa Saluran Operasi Pendinginan, Operasi Kering
Tidak termasuk
yang disebutkan di
atas (1)
1. Ketika mengubah dari ON ke OFF, operasi residual dilakukan selama 5 menit.
4.1.6 Fungsi Pencegahan Pembekuan Tujuan
Untuk menghindari pembentukan es pada penukar panas unit indoor dalam mode pendinginan dan
kering, sistem otomatis memulai siklus pencegahan pembekuan ketika sejumlah kondisi tertentu terpenuhi.
Kondisi awal pencegahan pembekuan
Awal pencegahan pembekuan ditetapkan oleh unit indoor (pengaturan pabrik):
• Penukar panas Indoor –1°C selama 40 menit diakumulasikan
atau • Penukar panas Indoor < –3°C selama 1 menit terus menerus
• Kompresor berjalan selama minimal 8 menit sejak awal atau akhir operasi siklus pembekuan sebelumnya.
Kondisi penghentian pencegahan pembekuan
Penghentian pencegahan pembekuan ditetapkan oleh unit indoor (pengaturan pabrik):
Penukar panas Indoor > 7°C selama 10 menit terus-menerus
Pompa saluran OFF Pompa saluran ON
Operasi kering & pendinginan
Termostat ON
(: &
&
35 Fungsi dan Kontrol
SiMT281515E Rincian Fungsi
4.1.7 Memulai Ulang Otomatis Tujuan
Tujuan fungsi memulai ulang otomatis adalah secara otomatis melanjutkan mode operasi yang sama
seperti ketika unit beroperasi saat catu daya dipulihkan setelah kegagalan daya.
Jangan gunakan fungsi "Automatic Restart" setiap hari untuk memulai/menghentikan unit.
Kehati-hatian saat mematikan daya
Ketika anda harus mematikan catu daya untuk melakukan pemeliharaan, pertama-tama pastikan
untuk mematikan saklar ON/OFF remote kontrol.
Jika anda mematikan catu daya selama saklar ON/OFF remote kontrol masih menyala, "fungsi
memulai ulang otomatis (automatic restart function)" otomatis memulai kipas unit indoor segera dan
kipas unit outdoor memulai otomatis 3 menit setelah catu daya dihidupkan ulang.
Jangan memulai / menghentikan unit dengan mencabut catu daya. Hentikan unit dengan perintah
berhenti dari remote kontrol atau kontrol opsional sebelum melepaskan catu daya. Pastikan bahwa
kompresor dan kipas unit outdoor berhenti sebelum mencabut catu daya sehingga "Refrigerant
Recovery function" telah selesai dengan benar.
Ketika memulai ulang unit setelah daya terputus untuk jangka waktu lama, biarkan unit mati dengan catu
daya terhubung selama sekitar setengah jam.
Fungsi dan Kontrol 36
Rincian Fungsi SiMT281515E
4.2 Unit Outdoor 4.2.1 Memulai ulang Siaga
Untuk mencegah kompresor dari sering ON / OFF dan menyamakan tekanan saluran refrigeran, lakukan
penonaktifan termostat paksa selama 3 menit setelah kompresor berhenti. Selain itu, kipas unit outdoor
melakukan operasi residual selama jangka waktu tertentu untuk mempercepat pemerataan dan mencegah
refrigeran masuk di evaporator.
Termostat OFF Memulai ulang siaga selesai (Restart standby)
Kompresor
katup ekspansi elektronik
Kipas unit Outdoor
Berpindah ke “Stop” atau “Startup control” setelah penyelesaian “Restart standby”.
4.2.2 Kontrol startup Ketika kompresor memulai, frekuensi awal tetap selama jangka waktu tertentu pada frekuensi rendah untuk
mencegah kembalinya refrigeran.
Awal penyamaan
tekanan
Penyamaan
tekanan selesai
Kontrol Startup selesai
Kompresor
katup ekspansi elektronik
Kipas unit Outdoor
kipas unit Indoor (Termostat OFF)
(Remote kontrol OFF)
10~120 dtk.
ON
OFF
OFF
ON
OFF Operasi residual
For 3 min.
107 Hz
L
OFF(Ta pendinginan > 40˚C)
Atur kecepatan kipas
(pendingina n)
OFF
Kontrol penyamaan tekanan sebelum kompresor mulai kontrol Startup
480 pulsa 15 sec.
65 pulsa
8 Step ON (Ta pendinginan 40˚C)
37 Fungsi dan Kontrol
SiMT281515E Rincian Fungsi
4.2.3 Kontrol Frekuensi Awal Kompresor inverter akan memulai dengan nilai frekuensi tetap terbatas selama jangka waktu tertentu untuk
mencegah cairan kembali ke kompresor, dan membatasi arus awal.
Umum Waktu kontrol startup normal adalah 2 ~ 3 menit. Waktu kontrol frekuensi awal dibatasi 10 menit.
Selama startup kompresor, perbedaan tekanan akan diperbesar dalam rangka untuk memiliki perbedaan
tekanan yang cukup untuk katup empat-cara beralih.
Grafik
Hz
107 Hz
Step 1
ON 1 2 ~ 3 Waktu (menit)
Kondisi akhir
Kontrol startup akan dihentikan ketika waktu awal maksimal 10 menit telah tercapai.
4.2.4 Kontrol Langkah Kompresor Setelah fungsi "kontrol frekuensi awal" telah dihentikan, frekuensi kompresor yang ideal akan ditentukan
oleh " Kontrol langkah kompresor ".
Umum Frekuensi operasi kompresor dikendalikan untuk menjaga suhu penguapan konstan dalam pendinginan.
Frekuensi dapat berubah setiap 20 detik. Perubahan frekuensi maksimum = 2 langkah / perubahan. (= Maks
6 langkah / menit)
Selama situasi tidak normal (misalnya perlindungan arus inverter) perubahan per langkah juga = 2 langkah /
perubahan, tetapi interval 20 detik mungkin akan diturunkan, sehingga perubahan mungkin lebih cepat.
Catatan:
Ketika fungsi kontrol lainnya diaktifkan (misalnya kontrol suhu pipa pembuangan), fungsi tersebut dapat
mengubah frekuensi kompresor dengan menggunakan input lain selain yang biasanya digunakan oleh
fungsi " kontrol langkah kompresor".
Kontrol Normal
Fungsi dan Kontrol 38
Rincian Fungsi SiMT281515E
Pendinginan
Dalam pendinginan, frekuensi operasi target
yang akan ditentukan oleh t indoor dan suhu
penguapan.
t dingin = Suhu yang diatur remote kontrol – Suhu
udara hisap Indoor.
Tergantung pada beban pendinginan, suhu
penguapan target (Te) akan menjadi nilai antara 2°C
Te 20°C.
Langkah frekuensi
Frekuensi operasi akan menjadi nilai yang dipilih dari
daftar dengan pengaturan frekuensi tetap yang
diprogram dalam memori unit:
4.2.5 Kontrol Kecepatan Kipas Unit Outdoor Kecepatan kipas unit outdoor akan dikendalikan dalam fungsi suhu udara outdoor yang sebenarnya,
tekanan kondensasi, perbedaan tekanan antara tekanan rendah dan tinggi dan rasio kompresi.
Untuk lebih jelasnya silahkan lihat " Kontrol Perbedaan Tekanan ".
Tabel Langkah Kipas
Langkah Pendinginan
M1F M2F
0 0 rpm 0 rpm
1 250 rpm 0 rpm
2 400 rpm 0 rpm
3 285 rpm 250 rpm
4 360 rpm 325 rpm
5 445 rpm 410 rpm
6 545 rpm 510 rpm
7 660 rpm 625 rpm
8 RZR100LUY1(4) 800 rpm 800 rpm
RZR125LUY1(4) 790 rpm 755 rpm
RZR140LUY1(4) 786 rpm 751 rpm
Catatan: Lihat "Kontrol Perbedaan Tekanan" di halaman 41.
No. Langkah
Frekuensi operasi Kompresor
3 41 Hz
4 44 Hz
5 48 Hz
6 52 Hz
7 55 Hz
8 58 Hz
9 69 Hz
10 72 Hz
11 78 Hz
12 84 Hz
13 90 Hz
14 94 Hz
15 98 Hz
16 102 Hz
17 107 Hz
18 112 Hz
19 117 Hz
20 123 Hz
21 131 Hz
22 139 Hz
23 147 Hz
24 155 Hz
25 164 Hz
26 174 Hz
39 Fungsi dan Kontrol
SiMT281515E Rincian Fungsi
4.2.6 Kontrol Perlindungan Tekanan tinggi Untuk mencegah tekanan tinggi yang tidak normal dalam sistem dan untuk alasan ini hindari perangkat
keselamatan tekanan tinggi, fungsi kontrol di bawah ini akan diaktifkan.
Diagram Alir
Karena tekanan batas hambatan bantalan menurun selama operasi lambat kompresor, batas bawah
frekuensi dibatasi.
[Dalam pendinginan]
Hp 3.04 MPa Batas bawah frekuensi kompresor
48 Hz Operasi Normal
Hp < 2.84 MPa Setelah 30 detik
Operasi Normal
Frekuensi operasi kompresor
–1 langkah/10 detik
Frekuensi operasi kompresor
+1 langkah / 1 menit
Frekuensi operasi
kompresor 123 Hz
Frekuensi operasi kompresor
+1 langkah /5 menit
Kompresor berhenti
Penghentian yang tidak normal (Indikasi E3)
Hp > 3.19 MPa Hp 3.94 MPa
Hp > 3.29 MPa Hp 3.04 MPa
Hp < 3.14 MPa
• HPS aktif atau
• Hp > 3.19 MPa selama 1 menit
Berhenti 15 kali atau kurang dalam 300 menit
atau
• HPS aktif • Berhenti 16 kali dalam 300 menit
Fungsi dan Kontrol 40
Rincian Fungsi SiMT281515E
Operasi Normal
Frekuensi batas atas kompresor
–1 langkah /20 detik
Frekuensi batas atas kompresor
+1 langkah/1 menit
Td 105 °C
Frekuensi batas atas kompresor
58 Hz
Kompresor berhenti
Penghentian tidak normal (indikasi F3)
4.2.7 Kontrol Suhu Pipa Pembuangan Garis besar
Frekuensi operasi kompresor akan dikendalikan untuk menghindari suhu kompresor tinggi yang tidak
normal (lihat juga kontrol katup ekspansi elektronik).
Td: Suhu pipa pembuangan (°C)
Td > 105 °C
• Td < 100 °C atau • Frekuensi batas atas
• & = Frekuensi maksimum • Td < 105 °C
• Td 110 °C
• & terus selama 5 menit atau • 300 detik
• Td < 100 °C
atau
• Td > 120 °C • & • Td 105 °C • 5 menit berlalu
• Td 115 °C terus atau selama 10 menit
• Td 135 °C
Berhenti 11 kali
dalam 200 menit
berhenti 10 kali atau kurang dalam 200 menit
[Kontrol derajat bukaan katup ekspansi elektronik]
Kontrol Normal
Batas bawah derajat bukaan katup ekspansi elektronik
+5 pulsa / Pendinginan selama 2 menit
Batas bawah derajat bukaan katup ekspansi elektronik
-5 pulsa / Pendinginan selama 2 menit
Batas bawah derajat bukaan katup ekspansi elektronik
+10 pulsa / Pendinginan selama 2 menit
Td 95˚C Td 80˚C
Td 90˚C
Td 100˚C
41 Fungsi dan Kontrol
SiMT281515E Rincian Fungsi
Operasi Normal Frekuensi kompresor –1 langkah/6 detik
Frekuensi kompresor +1 langkah/2 menit
Normal operation
Compressor frequency
–1 step/6 seconds
Compressor frequency
+1 step/2 minutes
Operasi Normal
Kipas unit Outdoor
+1 langkah/90 detik Pembatasan frekuensi operasi
kompresor (lihat berikut)
Kipas unit Outdoor
-1 langkah/90 detik
Kipas unit Outdoor
Langkah 1
Kipas unit Outdoor: Berhenti
Pembatasan
frekuensi
Suhu udara Outdoor < 20˚C
Suhu udara Outdoor 21˚C
4.2.8 Kontrol Perlindungan Arus Inverter Kontrol dengan Suhu Sirip Radiasi
Membatasi frekuensi batas atas operasi kompresor untuk mencegah kompresor dari tersandung (tripping)
karena suhu sirip radiasi.
Suhu sirip radiasi 86˚C
Frekuensi batas atas Inverter = Frekuensi Maksimum
Kontrol Perlindungan Arus Inverter
Suhu sirip radiasi 83˚C berlangsung selama 2 menit
Membatasi frekuensi operasi kompresor untuk mencegah kompresor dari tersandung(tripping) karena arus berlebih inverter.
Arus Inverter
> Arus turun
Frekuensi batas atas inverter
= Frekuensi maksimum
Untuk Semua
Model
Kondisi arus Inverter < Arus turun terus selama 2 menit
Suhu penukar panas unit Outdoor
(cairan) Suhu penukar panas unit
indoor&
Suhu penukar panas unit Outdoor (cairan) 25˚C
Suhu penukar panas unit Outdoor (cairan) Suhu penukar panas unit
indoor atau
Suhu penukar panas unit Outdoor (cairan) 25˚C
4.2.9 Kontrol Perbedaan Tekanan Untuk memastikan rasio kompresi (perbedaan tekanan antara tekanan tinggi dan rendah) pada kondisi suhu
udara outdoor rendah dalam mode pendinginan, kipas unit outdoor dan frekuensi kompresor target
mungkin bervariasi.
Ta: Suhu udara Outdoor
Tfin: Suhu sirip radiasi
Hp - Lp < 0.93MPa
atau
& Rasio kompresi < 2.1
Hp - Lp > 1.08MPa atau
Hp < 2.94MPa
atau Rasio kompresi > 2.4
Hp < 1.86MPa
Ta < 25˚C
Ta > 27˚C
& atau
Hp - Lp < 0.78MPa
Hp - Lp > 0.98MPa &
atau Rasio kompresi > 2.2 Rasio kompresi 1.8
Hp < 1.57MPa
Hp > 2.25MPa
Hp - Lp < 0.78MPa OR
Rasio kompresi < 1.8 &
Hp < 1.57MPa
Tfin < 66˚C
Hp - Lp > 0.88MPa &
atau Rasio kompresi > 2.0
Hp > 1.66MPa
Tfin 81˚C
Pembatasan frekuensi operasi kompresor
RZR100LUY1 (4) RZR125-140LUY1 (4)
Frekuensi batas atas 112 Hz 139 Hz
Frekuensi batas bawah 72 Hz
Arus turun
13 A Arus turun
11 A
Frekuensi kompresor
+ 1 langkah / 2 menit
Frekuensi kompresor - 1 langkah / 6 detik
Operasi normal
Fungsi dan Kontrol 42
Rincian Fungsi SiMT281515E
4.2.10 Kontrol Perlindungan Arus Keseluruhan Memonitor arus keseluruhan dan membatasi frekuensi operasi kompresor batas atas untuk mencegah
pemutus sirkuit dari melebihi kapasitas ternilai.
Arus unit Outdoor > Nilai arus batas atas
Operasi Normal Arus unit Outdoor Nilai arus batas atas
& frekuensi operasi kompresor batas atas = frekuensi maksimum
Arus unit Outdoor Nilai arus batas atas
Frekuensi operasi kompresor batas atas
–1 langkah /6 detik
Frekuensi operasi kompresor batas atas
+1 langkah /2 menit Arus unit Outdoor > Nilai
arus batas atas
Arus batas atas (A)
Ambil nilai-nilai berikut tergantung pada suhu udara outdoor.
Juga bervariasi tergantung pada model.
Arus keseluruhan (A)
13.5
10.0
8.5
3.0
25 28 43 50 Suhu udara outdoor (˚C)
4.2.11 Operasi Pump Down Setiap kali unit perlu dipindahkan atau dilepas, lakukan operasi pump down sebelum melepaskan pemipaan
bidang. Dengan melakukan operasi pump down, semua refrigeran akan terkumpul di unit outdoor.
Prosedur Kehati-hatian
1 Memulai " operasi kipas saja" dari remote
kontrol.
Pastikan bahwa kedua katup penghenti gas dan
cairan terbuka.
2 Tekan tombol (BS4) bawah pompa pada PCB
unit outdoor.
Kompresor dan kipas unit outdoor akan
mulai secara otomatis.
3 Setelah operasi berhenti (setelah 3 ~ 5 menit)
tutup katup penghenti cairan terlebih dahulu dan
kemudian katup penghenti gas.
4 Setelah " Operasi pump down " telah selesai ,
layar remote kontrol berkabel mungkin kosong
atau menunjukkan indikasi kesalahan "U4". Ini
tidak akan dapat memulai unit dari remote
kontrol tanpa mematikan catu daya terlebih
dahulu.
Pastikan katup penghenti terbuka sebelum
menyalakan kembali unit.
Perhatian
Menekan tombol (BS4) pump down pada PCB unit outdoor dapat menyebabkan kipas unit outdoor dan
indoor untuk mulai beroperasi secara otomatis.
Pastikan untuk membuka katup penghenti setelah pekerjaan pipa telah selesai. Pastikan untuk tidak
mengoperasikan unit dengan katup penghenti tertutup, atau kompresor dapat pecah.
43 Fungsi dan Kontrol
SiMT281515E Rincian Fungsi
4.2.12 Operasi Pemulihan Minyak Ketika kompresor beroperasi untuk jangka waktu tertentu pada frekuensi rendah, tingkat minyak di kompresor dapat menjadi rendah karena kembalinya minyak tidak selesai. Untuk mencegah kerusakan kompresor dan dalam kasus terburuk hindari kunci kompresor, operasi pemulihan minyak akan dilakukan.
Rincian Selama operasi pemulihan minyak, frekuensi operasi kompresor akan ditingkatkan selama jangka waktu 5
menit. Operasi pemulihan minyak hanya dijalankan dalam mode pendinginan.
4.2.13 Fungsi Operasi Tiruan Dalam kasus kesalahan termistor, operasi tiruan dilakukan dalam dua cara yang berbeda seperti yang ditunjukkan di bawah ini bahkan ketika kesalahan terdeteksi.
A. Operasi terus berlanjut selama kode kesalahan ditampilkan pada remote kontrol. Termistor yang dapat digunakan · Termistor udara Outdoor · Termistor udara hisap · Termistor penukar panas Indoor
B. Operasi terus berlanjut bahkan ketika kesalahan terdeteksi. Tampilan remote kontrol "Inspeksi / Test Run". Hanya jika tombol ditekan, kode kesalahan muncul. Termistor yang dapat digunakan · Termistor remote kontrol · Termistor sirip radiasi
Catatan:
Dalam kasus kesalahan termistor selain A dan B di atas, penghentian kesalahan dilakukan dan tidak ada operasi tiruan yang dilakukan.
Termistor yang dapat digunakan · Termistor pipa hisap · Termistor pipa pembuangan · Termistor penukar panas sedang
4.2.14 Kontrol Operasi Uji coba Tujuan
Saat mengoperasikan unit untuk pertama kalinya setelah instalasi, unit akan - tergantung pada mode operasi
yang dipilih – lakukan operasi uji coba terlebih dahulu.
Situasi 1
Pendinginan – Operasi pertama setelah instalasi dalam "mode pendinginan"
Termostat pendinginan aktif
Operasi pendinginan dalam "mode operasi uji coba" selama 3 menit
Operasi pendinginan Normal
Situasi 2
Pendinginan - Operasi pertama setelah instalasi dalam "mode operasi uji coba"
Operasi pendinginan dengan tombol operasi uji coba
Operasi pendinginan dalam "mode operasi uji coba" selama 3 menit
Operasi pendinginan dalam termostat dipaksa aktif.
Catatan:
Ketika berjalan dalam mode operasi uji coba, unit akan merasakan parameter instalasi di tempat (misalnya: kegagalan untuk membuka katup penghenti, ..) dan menunjukkan kode kesalahan yang berlaku jika diperlukan.
Jika remote kontrol menunjukkan "E3", "E4" atau "L8" sebagai kode kesalahan, ada kemungkinan bahwa baik katup penghenti tertutup atau outlet aliran udara terhambat.
Periksa sambungan kabel cabang unit tengah (kabel 1-2-3) jika kode kesalahan “U4” atau “UF”
ditampilkan pada remote kontrol. Jika kode kesalahan “U2” ditampilkan pada remote kontrol, periksa ketidakseimbangan tegangan. Jika kode kesalahan “L4” ditampilkan pada remote kontrol, ada kemungkinan bahwa bagian aliran
udara tertutup. Bila tidak ada tampilan kode kesalahan, operasi pendinginan terus berlanjut tanpa gangguan. (Namun,
kontrol ini sekali lagi dilakukan setelah refrigeran dipulihkan dengan menggunakan saklar pump down dan pada saat operasi pertama setelah penggantian PCB unit outdoor.)
SiMT281515E
Operasi Uji Coba dan Pengaturan Bidang 44
Bagian 5
Operasi Uji Coba dan
Pengaturan Bidang
1. Operasi Uji Coba ...................................................................................... 45 1.1 Periksa sebelum Operasi Uji Coba .......................................................45
1.2 Pemeriksaan Operasi Uji Coba .............................................................45
2. Pengaturan bidang dari Remote Kontrol ................................................ 46 2.1 Remote kontrol berkabel ......................................................................46
2.2 Remote Kontrol Nirkabel ......................................................................49
2.3 No. Kode dan Isi Pengaturan untuk Unit Indoor ....................................50
2.4 No. Kode dan Isi Pengaturan untuk Unit Outdoor ..................................51
3. Pengaturan bidang dari Adaptor Demand ............................................. 53 3.1 Fungsi i-Demand ..................................................................................53
4. Pengaturan bidang dari PCB Unit Outdoor ........................................... 54 4.1 Pengaturan dengan Tombol BS ............................................................54
4.2 Mode 1 Pengaturan ..............................................................................54
4.3 Mode 2 Pengaturan ..............................................................................55
4.4 Mode Monitor .......................................................................................57
4.5 Daftar Isi coba lagi dan Kesalahan .......................................................58
5. Operasi Darurat........................................................................................ 60
Operasi Uji Coba SiMT281515E
45 Operasi Uji Coba dan Pengaturan Bidang
1. Operasi Uji Coba
1.1 Periksa sebelum Operasi Uji Coba Sebelum melakukan operasi uji coba, lakukan sebagai berikut:
Langkah Tindakan
1 Pastikan tegangan pada sisi primer dari pemutus keselamatan adalah: (380 ~ 415 V) ± 10% untuk unit 3-fasa
2 Sepenuhnya buka katup penghenti cairan dan gas.
1.2 Pemeriksaan Operasi Uji Coba Untuk melakukan operasi uji coba, lakukan sebagai berikut:
Pastikan pengaturan suhu remote kontrol berada pada tingkat terendah dalam mode pendinginan
atau gunakan mode uji coba.
Periksa daftar periksa berikut:
pos pemeriksaan Perhatian atau peringatan
Apakah semua unit terpasang? Berbahaya untuk mengoperasikan selama badai Kemungkinan kerusakan untuk sambungan pipa
Apakah kabel arde dipasang sesuai dengan standar lokal yang berlaku?
Berbahaya jika terjadi kebocoran listrik
Apakah semua inlet dan outlet udara dari unit indoor dan outdoor terhalang?
Pendinginan Buruk
Apakah saluran mengalir dengan lancar? Kebocoran air
Apakah pemipaan cukup terisolasi panas? Kebocoran air
Apakah sambungan sudah diperiksa untuk kebocoran gas?
Pendinginan Buruk Penghentian
Apakah tegangan catu daya sesuai dengan spesifikasi pada pelat nama?
Operasi tidak benar
Apakah ukuran kabel seperti yang ditentukan dan sesuai dengan peraturan lokal?
Kerusakan kabel
Apakah sinyal remote kontrol diterima oleh unit? Tidak ada operasi
Operasi Uji Coba dan Pengaturan Bidang 46
Pengaturan bidang dari Remote Kontrol SiMT281515E
TEST
2. Pengaturan Bidang dari Remote Kontrol Fungsi individual unit indoor dapat diubah dari remote kontrol. Pada saat instalasi atau setelah pemeriksaan/
perbaikan servis, lakukan pengaturan bidang sesuai dengan uraian berikut.
Pengaturan tidak benar dapat menyebabkan kesalahan.
(Ketika aksesori opsional dipasang pada unit indoor, pengaturan untuk unit indoor mungkin diperlukan untuk
mengubahnya. Lihat informasi di buku pegangan pilihan.)
2.1 Remote kontrol berkabel 2.1.1 BRC1C61/BRC1D61
1. Ketika dalam mode normal, tekan tombol “ ” selama 4 detik atau lebih, dan FIELD SETTING MODE
dimasukkan.
2. Pilih MODE NO. yang diinginkan dengan tombol (2) “ ” . 3. Selama kontrol grup, saat pengaturan oleh setiap unit indoor (No. mode 20, 22 dan 23 telah dipilih),
tekan tombol (3) “ ” dan pilih INDOOR UNIT NO untuk diatur. (Operasi ini tidak perlu bila
pengaturan oleh grup.)
4. Tekan tombol atas (4) “ ” dan pilih FIRST CODE NO.
5. Tekan tombol bawah (5) “ ” dan pilih SECOND CODE NO.
6. Tekan tombol (6) “ ”sekali dan pengaturan sekarang adalah SET.
7. Tekan tombol (7) “ ” untuk kembali ke NORMAL MODE.
(Contoh)
Jika selama pengaturan grup dan waktu untuk membersihkan filter udara diatur ke FILTER
CONTAMINATION, HEAVY, SET MODE NO. menjadi “10” FIRST CODE NO. menjadi “0”, dan SECOND
CODE NO. menjadi “02”.
NO. KODE
KEDUA
NO. KODE
PERTAMA
3 4
1 7
6 5 2
NO. UNIT NO. MODE
MODE
PENGATUR
AN BIDANG
47 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Pengaturan bidang dari Remote Kontrol
2.1.2 BRC1E62
<Layar dasar>
(1)
<Layar menu Field setting >
(2)
<Layar Field setting >
1 Tekan tombol Cancel selama 4 detik atau lebih. Menu Field setting ditampilkan.
2 Pilih Field setting list di menu field
setting, dan tekan tombol Menu/Enter. layar Field setting list ditampilkan.
3 Sorot mode, dan pilih “Mode No.” yang
diinginkan dengan menggunakan tombol (Up/Down).
4 Dalam hal pengaturan per unit indoor selama kontrol grup (Ketika Mode No.
seperti 20 , 21 , 22 , 23 , 25 dipilih), sorot unit No. dan pilih “Indoor unit No.” untuk diatur dengan
menggunakan tombol
(Up/Down). (dalam hal pengaturan total grup, operasi ini tidak
diperlukan.)
dalam hal pengaturan individu per unit indoor, pengaturan saat ini ditampilkan. Dan, Second Code
No. “ - ” berarti tidak ada fungsi.
5 Sorot Second Code No. dari First Code
No. untuk diubah, dan pilih “Second Code No.” yang diinginkan dengan menggunakan tombol
Dalam hal pengaturan individu per unit
indoor
(3)
(4)
(5)
(3)
(5)
Dalam hal pengaturan total grup
First Code No.
(Up/Down). Beberapa pengaturan nomor mode yang identik tersedia.
Dalam hal pengaturan total grup, semua Second Code No. yang
dapat diatur ditampilkan seperti “ ”.
“ ” diubah ke Second Code No. untuk diatur. Dan, Second
Code No. “ - ” berarti tidak ada
fungsi.
Tekan tombol Menu/Enter
Tekan Tombol Menu/Enter
Second Code No.
Operasi Uji Coba dan Pengaturan Bidang 48
Pengaturan bidang dari Remote Kontrol SiMT281515E
< layar konfirmasi pengaturan>
(6)
(7)
6 Tekan tombol Menu/Enter. Layar konfirmasi pengaturan ditampilkan.
7 Pilih Yes dan tekan tombol
Menu/Enter. Rincian pengaturan
ditentukan dan kembali ke layar daftar pengaturan bidang.
8 Dalam hal beberapa perubahan pengaturan, ulangi “(3)” sampai “(7)”.
9 Setelah semua perubahan pengaturan selesai, tekan tombol Cancel dua kali.
10 Lampu latar keluar, dan “Connection under check Please wait for a moment” ditampilkan untuk inisialisasi.
Setelah inisialisasi, kembali ke layar dasar.
PERHATIAN
• Ketika aksesori opsional dipasang pada unit indoor, pengaturan unit indoor dapat diubah. Lihat panduan tentang aksesori opsional.
• Untuk rincian pengaturan bidang unit outdoor, lihat panduan instalasi yang
terlampir pada unit outdoor.
Tekan tombol Menu/Enter.
Konfirmasi pengaturan
49 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Pengaturan bidang dari Remote Kontrol
2.2 Remote Kontrol Nirkabel
No. Mode
mode pengaturan
bidang
Tombol UP
Tombol DOWN
Tombol RESERVE
No. kode pertama
Tombol MODE
No. kode kedua
Tombol INSPECTION/TEST
Pengaturan
Untuk mengatur pengaturan bidang, anda harus mengubah:
Mode No. (Nomor mode)
First code No. (Nomor kode pertama)
Second code No. (Nomor kode kedua)
Untuk mengubah pengaturan bidang, lakukan sebagai berikut:
Langkah Tindakan
1 Tahan tombol INSPECTION/TEST selama setidaknya 4 dt selama mode normal untuk masuk ke “Field setting mode”.
2 Tekan tombol MODE untuk memilih “Mode No.” yang diinginkan.
3 Tekan tombol UP untuk memilih “First code No.”.
4 Tekan tombol DOWN untuk memilih “Second code No.”.
5 Tekan tombol RESERVE untuk mengatur pengaturan saat ini.
6 Tekan tombol INSPECTION/TEST untuk kembali ke “Normal mode”.
Operasi Uji Coba dan Pengaturan Bidang 50
Pengaturan bidang dari Remote Kontrol SiMT281515E
2.3 No. Kode dan Isi Pengaturan untuk Unit Indoor Pengaturan bidang
Tabel di bawah ini berisi kemungkinan pengaturan bidang semua unit indoor. : Pengaturan pabrik
No. Mode
No. kode Pertama
Keterangan pengaturan No. Kode kedua
01 02 03 04
10 (20) 0 Kontaminasi filter berat /
ringan (Pengaturan
untuk waktu tampilan
untuk membersihkan
filter udara) (Atur waktu
tampilan untuk
membersihkan filter
udara sampai separuh
ketika ada kontaminasi
filter berat.)
Filter sangat tahan lama
Ringan Kira-kira 10,000 jam.
Berat Kira-kira 5,000 jam.
— —
Filter tahan lama
Kira-kira 2,500 jam.
Kira-kira 1,250 jam.
Filter standar
Kira-kira 200 jam.
Kira-kira 100 jam.
1 Tipe filter tahan lama Filter tahan lama
Filter sangat tahan lama
— —
2 Remote termistor dari remote kontrol
TH1 = remote kontrol
TH1 = Udara hisap
— —
3 Tampilan filter Tampilan Tidak ada tampilan — —
11 (21) 0 Sistem operasi serentak Sepasang Kembar Rangkap tiga Kembar ganda
1 Pengaturan Individu /terpadu Terpadu Individual — —
2 Keadaan kipas pada saat termostat Mati
Normal OFF — —
4 Kontrol mode operasi otomatis
Tersedia Larangan — —
7 penyesuaian aliran udara OFF Penyelesaian penyesuaian aliran udara
Awal penyesuaian aliran udarat
—
12 (22) 1 Pengaturan remote kontrol Penghentian paksa
Kontrol Start-stop
— —
5 Restart otomatis Dinonaktifkan Diaktifkan — —
6 Termostat pendinginan kecepatan kipas mati
Kecepatan LL Kecepatan yang diatur
— —
13 (23) 6 Tekanan statis eksternal Lihat tabel. (1)
15 (25) 1 Termostat kelebihan kelembaban mati
tidak dilengkapi
dilengkapi — —
3 Pilihan interlock alat pelembab pompa saluran
tidak dilengkapi
dilengkapi — —
5 Pilihan pengaturan bidang untuk pengaturan ventilasi individual dengan remote kontrol
tidak dilengkapi
dilengkapi — —
Catatan: 1.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
- - - - 50 Pa 60 Pa 70 Pa 80 Pa 90 Pa 100 Pa 110 Pa 120 Pa 130 Pa 140 Pa 150 Pa
51 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Pengaturan bidang dari Remote Kontrol
2.4 No. Kode dan Isi Pengaturan untuk Unit Outdoor Tabel di bawah ini berisi pengaturan remote kontrol.
: pengaturan pabrik
No. Mode
No.
Kode
Pertama
Keterangan Pengaturan
No. Kode Kedua
01 02 03 04 05 06
16 (26)
0 Operasi kebisingan malam rendah
Dinonaktifkan
Operasi kebisingan malam rendah
prioritas kapasitas
kebisingan
malam rendah
+ prioritas
kapasitas
— —
1 Waktu start dan stop Operasi kebisingan malam rendah otomatis
— — 22h00 ~ 06h00
22h00 ~ 08h00
20h00 ~ 08h00
—
2.4.1 Operasi kebisingan malam rendah Tujuan
Menurunkan suara pengoperasian unit outdoor.
Pengaturan
Operasi kebisingan malam rendah dapat diaktifkan dengan:
1. Kontrol otomatis (Dengan pengaturan bidang remote kontrol)
2. Aktivasi eksternal (dari PCB KRP58M opsional)
Operasi kebisingan malam rendah dengan Kontrol Otomatis
Operasi kebisingan malam rendah dapat diatur dengan pengaturan bidang dari remote kontrol berkabel:
: Pengaturan pabrik
No. Mode
No.
Kode
Pertama
Keterangan Pengaturan
No. Kode Kedua
01 02 03 04 05 06
16(26) 0 Operasi kebisingan malam rendah
nonaktif Operasi kebisingan malam rendah
Prioritas kapasitas
Operasi
kebisingan
malam
rendah +
prioritas
kapasitas
— —
1 Waktu start dan stop Operasi kebisingan malam rendah otomatis
— — 22h00 ~ 06h00
22h00 ~ 08h00
20h00 ~ 08h00
—
Metode Penentuan waktu Start dan Stop
Ketika mode pengaturan 16(26)-0-02, Operasi kebisingan malam rendah akan dilakukan dengan
menganggap waktu saat ini sesuai dengan suhu udara outdoor.
Mode otomatis akan dimulai ketika suhu udara outdoor adalah = rata-rata maks 10 hari terakhir -5 ° C dan
akan dilakukan selama 10 jam.
Suhu udara outdoor maksimum seharusnya terjadi pada saat 14: 00 h.
Karena keputusan waktu dibuat sesuai dengan suhu udara outdoor, penentuan waktu yang disebutkan di
atas adalah perkiraan saja.
Operasi Uji Coba dan Pengaturan Bidang 52
Pengaturan bidang dari Remote Kontrol SiMT281515E
Grafik
Pengaturan Prioritas Kapasitas
Ketika mode pengaturan 16(26)-0-04, operasi kebisingan malam rendah akan dihentikan ketika beban
pendinginan meningkat. Dalam hal ini, operasi akan kembali ke operasi normal. Unit akan kembali ke
operasi kebisingan malam rendah ketika beban pendinginan menurun lagi.
Grafik
Aktivasi eksternal dari PCB Opsional
Operasi kebisingan malam rendah juga dapat diaktifkan dari PCB (KRP58M51) opsional.
Konektor catu daya (pada
PCB X77A unit outdoor)
DS 1
1 2 3 4
X800M
ON
OFF
Konektor transmisi (pada
PCB X6A unit outdoor)
X801M
3 2 1 LNO P CO M
Output pada X801M = 12VDC, 12mA
Panjang kabel maksimum = 100 meter X801M
3 2 1 LNOP COM
Operasi kebisingan malam rendah akan dimulai ketika kontak pada LNOP-COM ditutup dan akan tetap aktif
selama kontak ditutup. Tidak ada pengaturan bidang pada unit outdoor atau dengan remote kontrol
diperlukan.
Operasi kebisingan malam rendah akan berakhir saat kontak dibuka kembali.
Penggunaan KRP58M51 memungkinkan penggunaan jam waktu eksternal.
Pengecualian
Operasi kebisingan malam rendah akan dibatalkan dalam kondisi berikut:
Operasi residual pump down
Kontrol Startup
Pemulihan Minyak
Suhu udara outdoor maksimum
+8 jam +10 jam
Garis tren menunjukkan fluktuasi suhu udara outdoor dalam 24 jam
X8
1A
X8
0A
Awal operasi
kebisingan
malam rendah
Akhir operasi
kebisingan
malam rendah
53 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Field Setting from Outdoor Unit PCB
2 1 LNOP
3. Pengaturan bidang dari Adaptor Demand
3.1 Fungsi i-Demand Tujuan
Menetapkan pembatasan terhadap konsumsi daya dari sistem. (Misalnya: kontrol persediaan,
batas konsumsi daya selama momen puncak,..)
Pengaturan
3 pengaturan demand yang berbeda dapat dipilih dengan menggunakan terminal X801M:
Demand 1 Menutup kontak antara COM dan kontak 1
Demand 2 Menutup kontak antara COM dan kontak 2
Demand 3 Menutup kontak antara COM dan kontak 3
Konektor transmisi
Konektor Catu Daya (pada
PCB X77A unit outdoor)
DS1
1 2 3 4
ON
OFF
(pada PCB X6A unit outdoor)
X800M
3 2 1 LNOP COM
X801M
Output pada X801M = 12VDC, 12mA
Panjang kabel maksimum = 100 meter
X801M
3 COM
Demand 1
Pembatasan konsumsi daya dalam fungsi pengaturan pada DS1:
PENGATURAN DS1
Konsumsi Daya Maksimum
1 2
OFF OFF
60%
ON OFF
70%
OFF ON
80%
ON ON
100%
Demand 2
Pembatasan konsumsi daya yang diatur menjadi 40%.
Demand 3
Termostat paksa Mati.
X8
1A
X80
A
Operasi Uji Coba dan Pengaturan Bidang 54
Field Setting from Demand Adaptor SiMT281515E
4. Pengaturan Bidang dari PCB Unit Outdoor 4.1 Pengaturan dengan Tombol BS
Dengan "Setting mode 1," "Setting mode 2" dan "Monitor mode," berbagai pengaturan dan data dapat diperiksa.
(1) Setting mode 1
Status awal (operasi normal) adalah "Setting mode 1." Mode ini menunjukkan status operasi -
"TEST(operasi uji coba)," "HWL (kesalahan)," "L.N.O.P(operasi kebisingan malam rendah)" atau
"DEMAND(operasi demand)."
(2) Setting mode 2
Setiap status operasi dapat dimodifikasi.
(3) Monitor mode
Mode ini menunjukkan "oil return operation," "outdoor unit class," "contents of retry," "contents of
error," "causes of drooping operation," dll.
dengan menggunakan tombol MODE, mode dapat diubah sebagai berikut.
Tekan dan tahan MODE (BS1) selama 5 detik (Normal) Tekan MODE (BS1) sekali
Setting mode 2
Setting mode 1
Monitor mode
MODE Tekan MODE MODE MODE
ON
H1P
(BS1) sekali.
H1P
OFF
H1P
berkedip
4.2 Mode 1 Pengaturan Dengan menggunakan mode ini, kondisi berikut dapat diperiksa:
• Kondisi operasi saat ini (operasi normal/uji coba /inspeksi jalur dan normal/ ada kesalahan)
• Kondisi operasi kebisingan rendah (Tingkat kebisingan normal/rendah 1, 2 dan 3)
• Kondisi operasi Demand (normal/Tingkat demand 1, 2 dan 3)
Kondisi di atas ini dapat diperiksa dengan melakukan langkah-langkah berikut: Prosedur untuk memeriksa item periksa
: ON : OFF : BERKEDIP
Selama "Setting mode 1," lampu
selalu mati.
Tampilan operasi uji coba
Dalam operasi normal
Dalam Operasi uji coba Dalam operasi pemeriksaan saluran
Tampilan Kesalahan Normal
Ada Kesalahan
Tampilan operasi kebisingan rendah Operasi Normal
Pengaturan tingkat kebisingan
rendah
Tampilan tingkat Demand
operasi Normal Tingkat 1 Demand
Tingkat 2 Demand Tingkat 3 Demand
Sistem secara normal diatur ke
"Setting mode 1".
Sebaiknya sistem diatur ke mode
lain selain itu, Tekan MODE
(BS1) untuk mengatur sistem ke
"Setting mode 1".
MODE TEST
H1P H2P
HWL
H3P
L.N.O.P
H4P H5P
DEMAND
H6P H7P
Periksa sistem untuk setiap kondisi melalui tampilan LED. (Lihat informasi
dalam tabel di sebelah kanan.)
55 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Pengaturan bidang dari PCB Unit Outdoor
Tekan dan tahan MODE (BS1) selama
5 detik dan atur ke “Setting mode 2”.
Tekan SET (BS2) dan atur tampilan LED ke item pengaturan yang
ditunjukkan dalam tabel di bawah ini.
Tekan RETURN (BS3) dan tentukan
item. (kondisi pengaturan saat ini
berkedip.)
Tekan SET (BS2) dan atur ke kondisi
pengaturan yang anda inginkan.
Tekan RETURN (BS3) dan tentukan
kondisinya.
< Pemilihan kondisi pengaturan >
<Pilihan item pengaturan>
Tekan RETURN (BS3) dan atur ke status awal dari “Setting mode 2”.
4.3 Mode 2 Pengaturan Dalam mode ini, pengaturan untuk item berikut bisa dilakukan dengan menggunakan tombol BS.
Jika Anda menjadi tidak yakin bagaimana
untuk melanjutkan, tekan MODE (BS1) dan kembali ke mode 1 pengaturan.
No.
Tampilan item pengaturan Tampilan kondisi pengaturan
Item pengaturan Tampilan LED
Kondisi pengaturan Tampilan LED
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
3
Operasi Demand 2
k h h h h k k 30% demand 40% demand (pengaturan pabrik) 50% demand
k h h h k h h
k h h h h k h
k h h h h h k
28 Mode pemulihan refrigeran
k h k k k h h OFF (pengaturan pabrik) ON
k h h h h h k
k h h h h k h
Jumlah dalam kolom “No.” merupakan jumlah waktu untuk menekan SET (BS2).
Pengaturan Operasi Demand 2
Dengan pengaturan ini, operasi kompresor dapat dikendalikan untuk mengurangi konsumsi daya.
(60% - 80% demand tersedia jika adaptor demand (aksesori opsional) digunakan.)
Item pengaturan Kondisi pengaturan Deskripsi
Operasi Demand 2
30% demand Beroperasi dengan 30% dari konsumsi daya ternilai.
40% demand (pengaturan pabrik) Beroperasi dengan 40% dari konsumsi daya ternilai.
50% demand Beroperasi dengan 50% dari konsumsi daya ternilai.
[prosedur kerja] h: NONAKTIF l: BERKEDIP k: AKTIF
Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan dan tahan MODE (BS1) dari "Setting mode 1" selama 5 detik atau lebih dan atur ke "Setting mode 2."
k h h h h h h
Tekan SET (BS2) 3 kali untuk mengatur tampilan LED seperti yang ditunjukkan dalam tabel sisi kanan.
k h h h h k k
Tekan RETURN (BS3) sekali. (pengaturan kini ditampilkan) k h h h h l h
Tekan SET (BS2) untuk mengatur tampilan LED seperti yang ditunjukkan dalam tabel sisi kanan.
30% dari konsumsi daya ternilai k h h h l h h
40% dari konsumsi daya ternilai k h h h h l h
50% dari konsumsi daya ternilai k h h h h h l
Tekan RETURN (BS3) sekali untuk membuat keputusan.
30% dari konsumsi daya ternilai k h h h k h h
40% dari konsumsi daya ternilai k h h h h k h
50% dari konsumsi daya ternilai k h h h h h k
Tekan RETURN (BS3) sekali lagi untuk eksekusi. (Tampilan LED dalam status awal dari "Setting mode 2".)
k h h h h h h
Tekan MODE (BS1) sekali untuk kembali ke Setting mode 1 (operasi normal). h h h h h h h
Operasi Uji Coba dan Pengaturan Bidang 56
Pengaturan bidang dari PCB Unit Outdoor SiMT281515E
Pengaturan Mode pemulihan Refrigeran
Ketika unit pemulihan refrigeran terhubung pada tempat untuk memulihkan refrigeran, sepenuhnya buka katup
ekspansi elektronik dari unit outdoor untuk membantu pemulihan.
[prosedur kerja]
(1) operasi penghentian.
(2) Nyalakan mode pemulihan refrigeran dengan melakukan prosedur berikut.
h: OFF l: Berkedip k: ON
Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan dan tahan MODE (BS1) dari "Setting mode 1" selama 5 detik atau lebih dan atur ke "Setting mode 2."
k h h h h h h
Tekan SET (BS2) 28 kali untuk mengatur tampilan LED seperti yang ditunjukkan pada tabel di sebelah kanan. (1)
k h k k k h h
Tekan RETURN (BS3) sekali. (Pengaturan Sekarang ditampilkan.) k h h h h h l
Tekan SET (BS2) sekali untuk mengatur tampilan LED seperti yang ditunjukkan pada tabel di sebelah kanan.
k h h h h l h
Tekan RETURN (BS3) sekali untuk membuat keputusan. k h h h h k h
Ketika RETURN (BS3) ditekan sekali lagi, katup ekspansi elektronik terbuka sepenuhnya.
k h h h h h h
(3) Hubungkan unit pemulihan refrigeran untuk melakukan pemulihan refrigeran.
(4) Setelah penyelesaian pemulihan refrigeran, matikan mode pemulihan refrigeran dengan melakukan
prosedur berikut atau mematikan daya unit outdoor.
Prosedur operasi H1P H2P H3P H4P H5P H6P H7P
Tekan SET (BS2) 28 kali untuk mengatur tampilan LED seperti yang ditunjukkan pada tabel di sebelah kanan. (1) k h k k k h h
Tekan RETURN (BS3) sekali. (Pengaturan Sekarang ditampilkan.) k h h h h l h
Tekan SET (BS2) sekali untuk mengatur tampilan LED seperti yang ditunjukkan pada tabel di sebelah kanan.
k h h h h h l
Tekan RETURN (BS3) sekali untuk membuat keputusan. k h h h h h k
Ketika RETURN (BS3) ditekan sekali lagi, katup ekspansi elektronik sepenuhnya menutup.
k h h h h h h
1. Jika Anda menjadi tidak yakin berapa kali Anda menekan tombol, tekan MODE (BS1) sekali
untuk kembali ke "Setting mode 1" dan mulai prosedur operasi lagi.
57 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Pengaturan bidang dari PCB Unit Outdoor
Tekan SET (BS2) dan atur tampilan LED ke item pengaturan.
Untuk masuk ke mode monitor,
tekan MODE (BS1) saat dalam
“Setting mode 1”.
Tekan RETURN (BS3) untuk menampilkan
data yang berbeda dari item pengaturan.
4.4 Mode Monitor Dalam mode ini, item berikut dapat diperiksa dengan menggunakan tombol BS.
< Pemilihan item pengaturan >
< Konfirmasi tentang isi
pengaturan >
Tekan RETURN (BS3) dan beralih ke status awal “Monitor mode”.
Tekan MODE (BS1) dan kembali ke
“Setting mode 1”.
Jumlah dalam kolom "No." merupakan jumlah berapa kali waktu
menekan SET (BS2).
Tampilan Data (1)
Isi tampilan Tampilan LED
H1P H2P H3P H4P H5P H6P H7P
Dalam operasi normal l h h h h h h
Dalam operasi kembalinya minyak
l h h h h h l
Tampilan Data (2) Data display (3)
Isi tampilan Tampilan LED
H1P H2P H3P H4P H5P H6P H7P
Pengaturan No. l h h h h h l
RZR100LUY1 (4) l h h l h h h
RZR125LUY1 (4) l h h l h h l
RZR140LUY1 (4) l h h l h l h
Isi tampilan Tampilan LED
H1P H2P H3P H4P H5P H6P H7P
Normal (tidak dalam operasi drooping)
l
h
h
h
h
h
l
Drooping tekanan rendah
l h h h h l h
Drooping tekanan tinggi
l h h h h l l
Drooping pipa pembuangan Inverter
l h h h l h h
Drooping arus Inverter
l h h h l h l
Drooping suhu sirip radiasi
l
h
h
h
l
l
h
Drooping Inverter l h h h l l l
Drooping arus keseluruhan
l h h l h h h
Drooping lainnya l h h l h h l
No.
item pengaturan
Tampilan LED
Tampilan Data
H 1 P
H 2 P
H 3 P
H 4 P
H 5 P
H 6 P
H 7 P
0 Indikasi operasi kembalinya minyak
l h h h h h h Lihat tampilan Data (1).
1 Indikasi kelas unit outdoor
l h h h h h k Lihat tampilan Data (2).
2 Isi coba lagi (terbaru)
l h h h h k h
Lihat "Error code display" pada halama selanjutnya.
3 Isi coba lagi (1 siklus sebelumnya)
l h h h h k k
4 Isi coba lagi (2 siklus sebelumnya)
l h h h k h h
5 Isi kesalahan (terbaru) l h h h k h k
6 Isi kesalahan (1 siklus sebelumnya)
l h h h k k h
7 Isi kesalahan (2 siklus sebelumnya)
l h h h k k k
10 Indikasi penyebab operasi drooping
l h h k h k h Lihat tampilan Data (3).
Operasi Uji Coba dan Pengaturan Bidang 58
Pengaturan bidang dari PCB Unit Outdoor SiMT281515E
4.5 Daftar isi tentang Coba lagi dan Kesalahan Lakukan langkah-langkah berikut untuk memeriksa isi coba lagi dan kesalahan..
k: ON h: OFF l: Berkedip
Kode kesalahan
Isi coba lagi atau kesalahan
1 2 3
H A P
H 1 P
H 2 P
H 3 P
H 4 P
H 5 P
H 6 P
H 7 P
H A P
H 1 P
H 2 P
H 3 P
H 4 P
H 5 P
H 6 P
H 7 P
H A P
H 1 P
H 2 P
H 3 P
H 4 P
H 5 P
H 6 P
H 7 P
C4 Ketidaknormalan termistor pipa cair penukar panas Indoor
l l k h h h l h l l k h h l h h l l k k h h h h
E1 Ketidaknormalan PCB unit Outdoor l l h k h h l l l l k h h h h l l l k k h h h h
E3 Ketidaknormalan tekanan tinggi (Terdeteksi dengan saklar tekanan tinggi)
l l k h h h l l l l k k h h h h
E5 Kunci motor kompresor l l k h h l h l l l k k h h h h
E7
Ketidaknormalan motor kipas unit Outdoor
Kunci motor DC 1 l l k h h l l l l l k k h h h l
Kunci motor DC 2 l l k k h h l h
Ketidaknormalan transmisi Inverter
l l k k h h l l
E9
Ketidaknormalan katup ekspansi elektronik
Konektor katup ekspansi elektronik terputus
l l k h l h h l l l k k h h h l
Kesalahan karena kondisi basah l l k k h h l h
F3
Ketidaknormalan suhu pipa pembuangan
Ketidaknormalan suhu pipa pembuangan
l l h k h l h l l l k h h h l l l l k k h h h l
Termistor pipa pembuangan terputus
l l k k h h l h
H3 Ketidaknormalan sistem saklar tekanan tinggi l l h k h l h h l l k h h h l l l l k k h h h h
H9 Ketidaknormalan termistor udara Outdoor l l k h l h h l l l k k h h h h
J1 Ketidaknormalan sensor tekanan l l h k h l l h l l k h h h h l l l k k h h h h
J3 Ketidaknormalan termistor pipa pembuangan l l k h h h l l l l k k h h h h
J5 Ketidaknormalan termistor pipa hisap l l k h h l h l l l k k h h h h
J6 Ketidaknormalan termistor pipa cair l l k h h l l h l l k k h h h h
J7 Ketidaknormalan termistor penukar panas sedang
l l k h h l l l l l k k h h h h
L1 Ketidaknormalan PCB unit Outdoor l l h k h l l l l l k h h h h l l l k k h h h h
L4 Suhu sirip radiasi naik l l k h h l h h l l k k h h h h
L5 Arus berlebih output DC (seketika) l l k h h l h l l l k k h h h h
L8 Termal Elektronik (Jeda waktu) l l k h l h h h l l k k h h h h
L9 Pencegahan Stall (Jeda waktu) l l k h l h h l l l k k h h h h
LC Kesalahan sistem transmisi antar PCB unit outdoor
l l k h l l h h l l k k h h h h
Untuk masuk ke "Monitor mode," tekan MODE
(BS1) ketika dalam "Setting mode 1."
Tekan SET (BS2) untuk mengatur tampilan LED
ke item coba lagi atau kesalahan.
Ketika RETURN (BS3) ditekan, tampilan LED
untuk RETURN 1 menyala.
Ketika SET (BS2) ditekan, tampilan LED untuk
RETURN 2 menyala.
Ketika SET (BS2) ditekan, tampilan LED untuk
RETURN 3 menyala.
<Tampilan RETURN 2>
< Pemilihan item coba lagi atau kesalahan > <Tampilan RETURN 3>
<Tampilan RETURN 1> Tekan RETURN (BS3) untuk mengembalikan sistem ke keadaan awal dari "Monitor mode."
Dengan menekan MODE (BS1) akan kembali ke "Setting mode 1."
59 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Pengaturan bidang dari PCB Unit Outdoor
k: ON h: OFF l: Berkedip
Kode kesalahan
Isi coba lagi atau kesalahan
1 2 3
H A P
H 1 P
H 2 P
H 3 P
H 4 P
H 5 P
H 6 P
H 7 P
H A P
H 1 P
H 2 P
H 3 P
H 4 P
H 5 P
H 6 P
H 7 P
H A P
H 1 P
H 2 P
H 3 P
H 4 P
H 5 P
H 6 P
H 7 P
P1 Ketidakseimbangan tegangan catu daya atau fasa terbuka
l l h k l h h h l l k h h h h l l l k k h h h h
P4 Ketidaknormalan termistor sirip radiasi l l k h h l h h l l k k h h h h
PJ Ketidaknormalan Pengaturan kapasitas l l k h l l h l l l k k h h h h
U0 kekurangan refrigeran
Peringatan kekurangan refrigeran l l h k l h h l l l k h h h h h l l k k h h h l
kekurangan refrigeran l l k k h h l h
U2
Ketidaknormalan Tegangan catu daya
Tegangan berlebih dan tegangan bawah Inverter
l l k h h h l h l l k k h h h l
Tegangan berlebih SP-PAM (1) l l k k h h l h
U4 Kesalahan transmisi antara unit indoor dan unit outdoor
l l k h h l h h l l k k h h h h
UA Ketidaknormalan saklar pengaturan bidang l l k h l h l h l l k k h h h h
UF Kesalahan transmisi antara unit indoor dan outdoor/ pemipaan dan ketidakcocokan kabel/ kekurangan refrigeran
l l k h l l l l l l k k h h h h
Catatan:
1. SP: Single Pulse (Pulsa tunggal)
PAM: PAM adalah bentuk modulasi sinyal yang mengontrol tegangan atau arus output.
Operasi Uji Coba dan Pengaturan Bidang 60
Emergency Operation SiMT281515E
5. Operasi Darurat Tabel di bawah ini menjelaskan tujuan mode operasi paksa.
Jika... Maka...
Remote kontrol rusak PCB unit Indoor rusak PCB unit Outdoor rusak
Mode operasi paksa dapat digunakan untuk menjalankan pendinginan. Dalam mode operasi paksa, kompresor dipaksa beroperasi sampai PCB unit indoor atau outdoor yang rusak kembali online.
Kondisi Startup
Anda dapat mengoperasikan sistem secara manual dengan mengubah saklar darurat pada PCB unit indoor dan outdoor dari "normal" ke "darurat". Ketika sistem operasi dalam "darurat" tidak bisa mengendalikan suhu kamar.
Kedua unit indoor dan outdoor harus diatur ke "darurat" selama daya MATI.
Kondisi Akhir
Anda dapat mengakhiri operasi darurat dengan mengubah saklar "darurat" kembali ke "normal" selama daya MATI.
Operasi darurat
Tabel di bawah menjelaskan apa yang akan terjadi ketika saklar diatur ke "darurat":
Mengubah saklar ke "darurat" untuk… Menyalakan…
unit Indoor Kipas unit Indoor Pompa saluran
unit Outdoor Kompresor Kipas unit Outdoor (s)
Cara mengatur Operasi darurat
Untuk mengatur operasi darurat, lakukan sebagai berikut:
Komponen aktif
Komponen Pendinginan paksa
Kompresor Aktif
Kipas unit Outdoor Kecepatan kipas H
Kipas unit Indoor Kecepatan kipas H
Pompa saluran Aktif
Langkah Tindakan
1 Matikan daya.
2 Menyalakan saklar (SS1) darurat pada PCB unit indoor.
Normal
Darurat
3 Menyalakan saklar darurat pada PCB unit outdoor.
Jangan mengubah pengaturan
pabrik.
Langkah Tindakan
4 Mengatur saklar darurat pada PCB unit outdoor untuk Pendinginan.
ON COOL
OFF HEAT
5 Menyalakan catu daya.
ON COOL ON ON
1
2
3
4
OFF HEAT OFF OFF
61 Operasi Uji Coba dan Pengaturan Bidang
SiMT281515E Operasi darurat
Informasi tambahan
Selama operasi darurat, jangan mencoba untuk mengoperasikan peralatan dari remote kontrol. Remote kontrol menunjukkan "88" selama operasi darurat aktif pada unit indoor.
Jika perangkat keselamatan diaktifkan selama darurat, semua aktuator dimatikan. Dalam pendinginan, unit berjalan selama 20 menit dan kemudian berhenti selama 10 menit
untuk menghindari pembekuan kumparan indoor. Operasi darurat tidak dapat dilakukan ketika PCB itu sendiri rusak. Pastikan untuk mengatur saklar darurat di kedua unit outdoor dan indoor. Unit tidak akan mengatur suhu selama operasi darurat. Ubah posisi saklar darurat hanya ketika daya dimatikan.
SiMT281515E
Diagnosis Servis 62
Bagian 6
Diagnosis Servis
1. Inspeksi Pemeliharaan ............................................................................ 64 1.1 Gambaran umum .................................................................................64
2. Pemecahan masalah berdasarkan gejala .............................................. 66 2.1 Gambaran umum .................................................................................66
2.2 Peralatan tidak Beroperasi ...................................................................67
2.3 Kipas unit Indoor beroperasi, namun Kompresor tidak beroperasi .........68
2.4 Operasi pendinginan mulai tetapi berhenti segera .................................69
2.5 Setelah unit dimatikan, Tidak dapat dihidupkan ulang untuk sementara.70
2.6 Peralatan beroperasi namun tidak memberikan Pendinginan ................72
2.7 Peralatan Mengeluarkan Kabut Putih ....................................................73
2.8 Peralatan Menghasilkan suara keras atau Getaran ...............................74
2.9 Peralatan Mengeluarkan Debu .............................................................76
2.10 LCD Remote Kontrol Menampilkan "88" ..............................................76
3. Pemecahan masalah dengan indikasi LED ............................................ 77 3.1 Pemecahan masalah dengan LED pada Unit Indoor .............................77
3.2 Pemecahan masalah dengan LED pada PCB Unit Outdoor .................77
4. Pemecahan masalah Remote Kontrol ................................................... 78 4.1 Penggantian Mode ...............................................................................78
4.2 Prosedur diagnosis otomatis dengan Remote Kontrol ...........................79
4.3 Kode Kesalahan dan Deskripsi .............................................................83
4.4 Kode Kesalahan – Kode Sub ................................................................84
4.5 Gambaran umum Perangkat Keselamatan outdoor ...............................87
4.6 Gambaran umum Perangkat Keselamatan Indoor ................................87
5. Pemecahan masalah dengan indikasi pada Remote Kontrol ............... 88 5.1 Ketidaknormalan PCB unit Indoor .........................................................88
5.2 Ketidaknormalan Sistem Permukaan Air Saluran ..................................89
5.3 Kunci Motor Kipas Unit Indoor ..............................................................91
5.4 Ketidaknormalan Motor Kipas Unit Indoor ............................................92
5.5 Ketidaknormalan PCB Kipas ................................................................94
5.6 Ketidaknormalan Sistem Saluran ..........................................................95
5.7 Ketidaknormalan pengaturan kapasitas ................................................96
5.8 Kesalahan transmisi (antara PCB Unit Indoor dan PCB Kipas) ...............97
5.9 Kesalahan transmisi (antara PCB Unit Indoor dan PCB Kipas) ..............99
5.10 Ketidaknormalan Termistor ............................................................... 101
5.11 Kesalahan Kombinasi antara PCB Unit Indoor dan PCB Kipas .......... 102
5.12 Ketidaknormalan Termistor Remote Kontrol ..................................... 103
5.13 Ketidaknormalan PCB Unit Outdoor .................................................. 104
5.14 Ketidaknormalan Tekanan Tinggi
(Terdeteksi dengan Saklar Tekanan Tinggi) ...................................... 105
5.15 Kunci Motor Kompresor .................................................................... 107
5.16 Ketidaknormalan Motor Kipas Unit Outdoor ...................................... 108
5.17 Ketidaknormalan Katup Ekspansi elektronik...................................... 110
5.18 Ketidaknormalan Suhu Pipa Pembuangan ........................................ 112
5.19 Ketidaknormalan Sistem Saklar Tekanan Tinggi ............................... 113
5.20 Ketidaknormalan Termistor ............................................................... 114
SiMT281515E
63 Diagnosis Servis
5.21 Ketidaknormalan Sensor tekanan ..................................................... 115
5.22 Ketidaknormalan PCB Unit Outdoor .................................................. 116
5.23 Suhu Sirip Radiasi Naik .................................................................... 118
5.24 Arus berlebih Output DC (Seketika) .................................................. 120
5.25 Termal Elektronik (Jeda Waktu) ........................................................ 122
5.26 Pencegahan Stall (Jeda Waktu)........................................................ 124
5.27 Kesalahan Sistem Transmisi antara PCB Unit Outdoor ..................... 126
5.28 Ketidakseimbangan Tegangan Catu Daya atau Fasa Terbuka ......... 127
5.29 Ketidaknormalan Termistor Sirip Radiasi .......................................... 128
5.30 Ketidaknormalan Pengaturan Kapasitas ........................................... 129
5.31 Kekurangan Refrigeran .................................................................... 130
5.32 Ketidaknormalan Tegangan Catu Daya ............................................ 131
5.33 Kesalahan Transmisi antara Unit Indoor dan Unit Outdoor ................. 132
5.34 Kesalahan Transmisi antara Unit Indoor dan Remote Kontrol ............ 134
5.35 Kesalahan Transmisi antara Remote Kontrol MAIN dan
Remote Kontrol SUB ........................................................................ 135
5.36 Ketidaknormalan Saklar Pengaturan Bidang ..................................... 136
5.37 Kesalahan Pengaturan Alamat Terpusat ........................................... 137
5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor /
Pemipaan atau Ketidakcocokan pengkabelan / Kekurangan Refrigeran 138
5.39 Pemeriksaan .................................................................................... 139
Diagnosis Servis 64
Maintenance Inspection SiMT281515E
1. Inspeksi Pemeliharaan
1.1 Gambaran umum Ketika melakukan pemeliharaan, Anda setidaknya harus melakukan inspeksi berikut:
Unit Indoor
Adalah filter udara kotor?
Bagaimana tegangan dan arusnya?
Kabel Transmisi antara unit
indoor dan outdoor
Bagaimana kapasitas saklar?
Bagaimana ketebalan kabel?
Ke pemutus
khusus
Pipa Refrigeran
Pipa saluran unit Outdoor
Garis pandu untuk Kondisi Operasi Optimal
Pembumian
Garis pandu nilai operasi ketika beroperasi di bawah kondisi standar (pada frekuensi ternilai) dengan
menekan tombol operasi uji coba pada remote kontrol adalah seperti yang diberikan dalam tabel di bawah
ini.
Kipas unit indoor: pengatur H
Tekanan tinggi
Tekanan rendah
Suhu pipa pembuangan
Suhu udara hisap
Unit Indoor: Perbedaan suhu antara Udara Hisap dan Udara pembuangan
Unit Outdoor: Perbedaan suhu antara Udara Hisap dan Udara pembuangan
Pendinginan
2.6 MPa ~ 3.4 MPa
0.6 MPa ~ 1.0 MPa
60°C ~ 100°C –2°C ~ 10°C 8°C ~ 18°C 7°C ~ 12°C
Kondisi Standar
Indoor Outdoor
Operasi Pendinginan 27°C DB/19°C WB 35°C DB
Selama atau setelah pemeliharaan, ketika Catu Daya dihidupkan ulang, operasi memulai ulang otomatis
dengan “auto restart function.” Harap menjalankan peringatan yang sesuai.
65 Diagnosis Servis
SiMT281515E Inspeksi Pemeliharaan
Korelasi dari Status Operasi Pendingin Ruangan dan Tekanan / Arus yang mengalir
Apa yang terjadi jika dibandingkan dengan nilai normal yang dirangkum dalam tabel di bawah ini.
(Diukur selama 15 ~ 20 menit atau lebih setelah operasi dimulai.)
Pendinginan
Status Pendingin Ruangan Tekanan rendah Tekanan tinggi Arus yang mengalir
Pengotor filter udara Lebih rendah Lebih rendah Lebih rendah
Hubung singkat Udara Inlet/Outlet Unit Indoor
Lebih rendah Lebih rendah Lebih rendah
Pengotor Sirip Unit Outdoor Lebih tinggi Lebih tinggi Lebih tinggi
Hubung singkat Udara Inlet/Outlet Unit Outdoor
Lebih tinggi Lebih tinggi Lebih tinggi
Udara tercampur dalam Refrigeran Lebih tinggi Lebih tinggi Lebih tinggi
Air tercampur dalam Refrigeran Lebih rendah 1 Lebih rendah Lebih rendah
Kotoran tercampur dalam Refrigeran Lebih rendah 2 Lebih rendah Lebih rendah
Kekurangan Refrigeran (Gas) Lebih rendah Lebih rendah Lebih rendah
Kompresi tidak memadai Lebih tinggi 3 Lebih rendah Lebih rendah
Catatan:
1. Air dalam refrigeran membeku di dalam pipa kapiler atau katup ekspansi elektronik, dan pada dasarnya merupakan fenomena yang sama seperti pump down
2. Kotoran dalam refrigeran menyumbat filter dalam pipa, dan pada dasarnya merupakan fenomena yang sama seperti pump down.
3. Perbedaan tekanan antara tekanan tinggi dan rendah menjadi kecil.
Diagnosis Servis 66
Pemecahan masalah berdasarkan gejala SiMT281515E
2. Pemecahan masalah berdasarkan gejala
Gambaran Umum
Gejala Rincian Tindakan
1 Peralatan tidak beroperasi Lihat Halaman67
2 Kipas Unit Indoor beroperasi, namun kompresor tidak beroperasi.
Lihat Halaman 68
3 Operasi Pendinginan mulai tapi berhenti segera. Lihat Halaman 69
4 Setelah unit dimatikan, unit tidak bisa dimulai ulang untuk sementara waktu.
Lihat Halaman.70
5 Peralatan beroperasi tetapi tidak memberikan pendinginan.
Lihat Halaman 72
6 Peralatan mengeluarkan kabut putih Lihat Halaman 73
7 Peralatan menghasilkan suara keras atau getaran.
Lihat Halaman 74
8 Peralatan mengeluarkan debu. Lihat Halaman.76
9 LCD Remote kontrol menampilkan “88”. Lihat Halaman 76
10 Peralatan memancarkan bau. Bau rokok dan bau ruangan terakumulasi di dalam unit indoor dibuang/dikeluarkan bersama udara. Bagian dalam unit indoor harus dibersihkan.
11 Kipas unit Indoor beroperasi di pengatur “L” selama 1 menit dalam mode “program dry” bahkan ketika kompresor tidak beroperasi.
It is normal. The monitoring function forcibly operates the fan for 1 minute.
12 Pompa saluran beroperasi saat peralatan tidak beroperasi.
Hal ini normal. Pompa saluran terus beroperasi selama beberapa menit setelah peralatan dimatikan.
67 Diagnosis Servis
SiMT281515E Pemecahan masalah berbasis gejala
2.2 Peralatan tidak Beroperasi
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Sekring terbakar atau gangguan kontak dalam sirkuit operasi
Titik kontak atau saklar operasi rusak
Saklar Tekanan Tinggi Rusak
Saklar magnetik untuk motor kipas rusak
Aktivasi atau kegagalan relai arus lebih untuk motor kipas
Relai arus lebih untuk kompresor rusak
Termostat perlindungan kompresor rusak
Isolasi dalam sistem listrik tidak memadai
Titik kontak saklar magnetik untuk kompresor rusak
Kompresor rusak
Remote kontrol rusak atau baterai rendah (nirkabel)
Pengaturan alamat remote kontrol nirkabel tidak benar
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Nyalakan saklar listrik atau ganti sekring.
Tunggu sampai daya kembali.
Normal.
Memulai operasi setelah 3 menit (3-menit siaga).
Normal.
Memulai operasi setelah
3 menit (3-menit siaga).
Mendiagnosis berdasarkan kode kesalahan pada remote kontrol.
Mendiagnosis berdasarkan kode kesalahan pada remote kontrol.
Periksa sistem listrik. Komponen listrik rusak
Apakah saklar listrik MATI atau sekering saklar listrik
terbakar?
YA
YA
Apakah saklar operasi ditekan berulang kali?
YA
YA
Apakah lampu operasi pada LCD
remote kontrol
berkedip?
YA
Apakah lampu operasi pada bagian penerima unit indoor
berkedip?
YA
Tidak
Tidak
Tidak
Tidak
Tidak
Apakah ada kegagalan daya ?
Apakah termostat berubah dan diatur ulang lagi?
Tidak
Diagnosis Servis 68
Pemecahan masalah berdasarkan gejala SiMT281515E
Indoor unit
PCB
Outdoor unit PCB
Relay
· Kipas unit Indoor berjalan pada laju aliran udara yang diatur.
· Bila suhu udara hisap lebih tinggi dari suhu yang diatur
2.3 Kipas Unit Indoor Beroperasi, Namun Kompresor tidak beroperasi
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Sekring terbakar atau gangguan kontak dalam sirkuit operasi
Termistor rusak
PCB Unit indoor/outdoor rusak
Saklar magnetik rusak
Transistor daya rusak
Kompresor rusak
Pemecahan Masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
TIDAK
YA
Nyalakan saklar daya atau ganti sekring.
TIDAK
YA
Ganti kompresor.
TIDAK
YA
Ganti saklar magnetik atau
transistor daya.
YA
Ganti PCB.
TIDAK
Periksa termistor.
Termistor udara hisap Saklar
magnetik
COMP.
(3)
Output dari relai atau
mikro- komputer
(2) Output dari
saklar magnetik
atau sirkuit SW transistor
daya
(1) Output dari
saklar magnetik
atau U, V, W transistor
daya
Input
ke
PCB
Output
dari
PCB
Input
ke
PCB
Apakah saklar daya MATI atau sekring untuk saklar daya
terbakar?
(1)Apakah tegangan ternilai diterapkan pada terminal
kompresor?
(2) Apakah output tegangan ternilai dari saklar magnetik atau
transistor daya?
(3) Apakah output tegangan
ternilai dari PCB?
PCB unit Indoor PCB unit outdoor
69 Diagnosis Servis
SiMT281515E Pemecahan masalah berbasis gejala
2.4 Operasi Pendinginan Mulai namun Berhenti segera
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Isi berlebih refrigeran
Udara tercampur dalam sistem refrigeran
saklar tekanan rusak
saklar magnetik untuk motor kipas unit outdoor rusak
Relai tambahan untuk motor kipas unit outdoor rusak
Penukar panas unit outdoor kotor
Ada item pengganggu dalam aliran udara unit outdoor.
Kipas unit outdoor rusak
Filter udara unit indoor kotor
Penukar panas unit indoor kotor
Ada beberapa item pengganggu dalam aliran unit indoor.
Kipas unit indoor rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Diagnosis berdasarkan kode kesalahan pada remote kontrol
Diagnosis berdasarkan kode kesalahan pada remote kontrol
Motor kipas rusak. Periksa saklar magnetik dan saklar tambahan
untuk motor kipas.
Bersihkan filter.
Hilangkan item pengganggu.
Bersihkan penukar panas.
Setelah pengeringan vakum,
isi jumlah refrigeran yang
benar. Periksa saklar tekanan.
Kemungkinan penyebab sebagai berikut:
• Isi refrigeran berlebih
• Pencampuran udara dalam sistem refrigeran
• Saklar tekanan rusak
Apakah tipe remote
kontrol berkabel atau nirkabel?
Nirkabel
Berkabel Apakah lampu operasi remote kontrol berkedip?
TIDAK
YA
Apakah lampu operasi bagian
penerima sinyal unit
indoor berkedip?
TIDAK
YA
Apakah kipas berputar? YA
TIDAK
Apakah filter kotor?
TIDAK
YA
Apakah ada item yang mengganggu aliran udara?
TIDAK
YA
Apakah penukar panas kotor?
TIDAK
YA
Diagnosis Servis 70
Pemecahan masalah berdasarkan gejala SiMT281515E
2.5 Setelah Unit Dimatikan, Unit tidak dapat dihidupkan kembali untuk Sementara
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Relai arus berlebih (untuk kompresor)
Relai arus berlebih akan berpengaruh karena alasan berikut
• Tegangan catu daya lebih rendah
• Kelebihan tingkat tekanan tinggi
• Ukuran kabel daya tidak memadai
• Kompresor rusak
Termostat Perlindungan Kompresor
Termostat Perlindungan Kompresor akan berpengaruh karena alasan berikut
• Kompresi kompresor tidak memadai
• Refrigeran tidak sesuai
• Katup ekspansi elektronik rusak
• Sirkulasi refrigeran tidak memadai
71 Diagnosis Servis
SiMT281515E Pemecahan masalah berbasis gejala
Nyalakan saklar ON OFF operasi,
kemudian tunggu.
Does the unit start operation after 3 minutes?
NO
YES
Apakah sisi pembuangan dari
kompresor panas setelah unit
berhenti?
YA
Setelah pengeringan vakum, isi jumlah refrigeran yang benar. Kemudian, mulai
beroperasi lagi.
Defective compressor
Tegang Catu Daya dalam ±10 % dari
tegangan yang ditentukan
YA
NO
Apakah ukuran keseluruhan panjang kabel daya sesuai?
YA
NO
[Sirkuit refrigeran ]
Apakah ada perbedaan suhu antara inlet dan outlet katup ekspansi
elektronik?
YA
NO
Pemecahan masalah
Peratian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Normal.
Unit berada dalam mode siaga 3 menit.
Periksa kompresor.
Periksa penyebab mengapa relai arus berlebih (untuk kompresor) atau termostat perlindungan kompresor melakukan tindakan..
[Sistem listrik]
Hubungi Perusahaan Listrik.
Ganti kabel daya.
Ganti katup ekspansi elektronik.
Periksa kompresor.
Tidak (Tidak begitu panas)
Apakah unit mulai operasi setelah 3 menit?
YA
TIDAK
TIDAK
TIDAK
TIDAK
Kompresor Rusak
Diagnosis Servis 72
Pemecahan masalah berdasarkan gejala SiMT281515E
2.6 Peralatan beroperasi namun tidak memberikan pendinginan
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Pilihan model Tidak Benar
Kekurangan Refrigeran
Aliran udara dalam unit indoor tidak memadai
Peningkatan tekanan tinggi
Selain itu, kesalahan berikut mungkin dapat dibayangkan
• Kompresi kompresor tidak memadai
• Sirkulasi refrigeran tidak memadai
• Katup ekspansi elektronik rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau memutuskan konektor, atau kerusakan
bagian dapat terjadi.
Normal.
Instalasi unit tambahan harus dipertimbangkan.
Kekurangan refrigeran dapat menimbulkan gangguan.
Setelah pengeringan vakum, isi
jumlah refrigeran yang benar
Periksa setiap bagian. • filter udara tersumbat
• Penukar panas kotor • motor kipas rusak
(Lihat Pemecahan masalah “A6”.)
Periksa setiap item.
• Isi refrigeran berlebihan • Udara tercampur dalam sistem
refrigeran • Penukar panas kotor
• Hubungan pendek udara pembuangan
• Item pengganggu dalam aliran udara
• Motor kipas unit outdoor rusak (Lihat pemecahan masalah “E7”.)
Periksa setiap item.
• Kompresi kompresor tidak memadai
• Sirkulasi refrigeran tidak memadai
• Katup ekspansi elektronik rusak
Ukur suhu udara hisap dan udara pembuangan . Perbedaan suhu = Suhu udara hisap – Suhu udara
pembuangan
perbedaan suhu untuk pendinginan harus antara 8
dan 18C.
TIDAK
YA
Apakah ada embun beku di sekitar port inlet
penukar panas unit indoor atau
port outlet katup ekspansi elektronik?
YA Apakah arus operasi
kurang dari tingkat yang ditentukan?
YA
Apakah laju aliran udara
unit indoor menurun?
YA
Apakah tingkat tekanan tinggi lebih tinggi dari
tingkat normal?
YA
• Pilihan model salah
• Pengaruh matahari langsung
Apakah beban panas
meningkat setelah instalasi unit?
YA
TIDAK
TIDAK TIDAK
TIDAK
TIDAK
73 Diagnosis Servis
SiMT281515E Pemecahan masalah berbasis gejala
2.7 Peralatan Mengeluarkan Kabut Putih
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Tempat instalasi lembab
Tempat Instalasi kotor dan dengan kabut minyak pekat.
Penukar panas kotor
Filter udara tersumbat
Motor kipas rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Normal
TIDAK
Hilangkan sumber kondisi lembab.
Pembersihan penukar panas diperlukan.
Hilangkan sumber minyak,kabut
atau debu TIDAK
Bersihkan filter udara.
Periksa motor kipas.
(Lihat pemecahan masalah “A6”)
TIDAK
Normal
Apakah suhu kamar lebih tinggi dari nilai yang ditetapkan
dalam pendinginan? YA
Apakah penukar panas unit indoor kotor?
TIDAK
YA
Apakah lokasi berdebu atau
dengan kabut minyak pekat? YA
Apakah laju aliran udara terlalu kecil?
YA
Melanjutkan operasi unit.
Apakah kabut putih keluar dari unit?
TIDAK
YA
Diagnosis Servis 74
Pemecahan masalah berdasarkan gejala SiMT281515E
Apakah kebisingan menimbulkan getaran
pada seluruh plafon dan dinding?
TIDAK
Apakah kebisingan menimbulkan getaran pada bagian bantalan
Unit? TIDAK
Apakah pipa aman?
[sisi catu daya] YA
Apakah kipas bersentuhan dengan
bagian lain? TIDAK
Apakah pipa melakukan kontak dengan casing?
TIDAK
Apakah suara aliran kebisingan dari katup
pereduksi tekanan atau lubang kapiler?
TIDAK
A
2.8 Peralatan Menghasilkan suara keras atau Getaran
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Instalasi tidak benar
Kontak kipas, pipa, casing, dll.
Kebisingan aliran refrigeran
Kebisingan operasi peralatan saluran pembuangan
Kebisingan kontraksi komponen resin
Selain itu, kesalahan berikut mungkin dapat dibayangkan
• Isi refrigeran yang berlebih
• Percampuran udara
• Kebisingan sekilas dari refrigeran yang tidak memadai (Meredam kebisingan)
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
[ sisi pekerjaan instalasi]
YA Koreksi instalasi.
Penguatan untuk plafon atau dinding
YA Masukkan peredam kejut di bagian
bantalan, atau memperkuat bagian bantalan .
TIDAK Masukkan bahan bantalan untuk dukungan pipa seperti pelana.
YA Bongkar dan hilangkan kontak bagian
YA
Perbaiki pipa secara manual
atau ikat beban berat ke pipa.
YA
Normal.
75 Diagnosis Servis
SiMT281515E Pemecahan masalah berbasis gejala
Normal. Suara tersebut merupakan kebisingan aliran gas (refrigeran) di sisi dalam
unit pendingin ruangan.
Normal. Suara ini adalah suara
yang ditimbulkan pada saat aliran gas (refrigeran) berubah atau
berhenti.
Normal. Suara operasi perangkat pengeringan
Normal. Derit yang
ditimbulkan oleh penyusutan
bagian resin karena perubahan suhu.
Setelah pengeringan vakum,
isi jumlah yang benar dari
refrigeran.
• Isi refrigeran berlebihan
• Udara tercampur dalam sistem refrigeran
• Kebisingan aliran karena kekurangan
refrigeran. (suara shoo...)
A
Suara "shoo..." ringan terus menerus selama pendinginan
YA
Suara "shoo..." muncul hanya setelah
operasi mulai atau berhenti.
YA
TIDAK
Suara "shoo..."
muncul selama pendinginan setelah
operasi berhenti.
TIDAK
YA
Berderit setelah operasi berhenti
YA
TIDAK
TIDAK
Diagnosis Servis 76
Pemecahan masalah berdasarkan gejala SiMT281515E
2.9 Peralatan Mengeluarkan Debu
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Karpet
Rambut Hewan
Aplikasi (toko kain, ...)
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Debu yang terkumpul di bagian dalam unit indoor dikeluarkan. Pembersihan untuk bagian dalam unit indoor diperlukan.
Debu yang terkumpul di bagian dalam unit indoor dikeluarkan. Pembersihan untuk bagian dalam unit indoor diperlukan.
Pasang filter udara.
2.10 LCD Remote Kontrol Menampilkan "88"
Model yang
berlaku
Semua model seri SkyAir
Penyebab
seharusnya
Posisi SS1 pada PCB unit indoor pada posisi “Darurat”.
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Unit ini melakukan pemeriksaan untuk mengkonfirmasi bahwa remote kontrol normal. Indikasi
muncul sebentar.
Putar saklar ke "Normal," dan atur ulang catu daya.
Periksa unit berdasarkan pemecahan masalah dari LED
unit indoor dan LED unit outdoor.
Apakah gangguan muncul pada saat operasi dimulai lagi setelah jangka waktu operasi
yang lama? YA
Apakah dilengkapi filter udara? YA
Gangguan muncul hanya setelah
menyalakan catu daya.
TIDAK
YA
Apakah posisi SS1 pada PCB unit indoor pada posisi
"Darurat"?
YA
TIDAK
TIDAK
TIDAK
77 Diagnosis Servis
SiMT281515E Troubleshooting by Remote Controller
3. Pemecahan masalah dengan indikasi LED
3.1 Pemecahan masalah berdasarkan LED pada unit Indoor Pemecahan masalah dapat dilakukan berdasarkan LED (hijau) monitor servis. (Berkedip jika normal)
k: LED MENYALA / h: LED MATI / l: LED Berkedip / — : Tidak ada koneksi dengan pemecahan
masalah
Monitor Miro-komputer Normal
Isi / pemrosesan
HAP (LED-A)
l unit Indoor normal Pemecahan masalah unit Outdoor
l Kabel transmisi antara unit indoor dan outdoor tidak sesuai
Jika LED-A unit outdoor MATI, pemecahan masalah unit outdoor dilakukan. Jika LED-A unit outdoor berkedip, kabel PCB unit indoor atau outdoor rusak.
k PCB unit indoor rusak (4)
h Catu daya rusak atau PCB rusak atau kabel transmisi antara unit indoor dan outdoor rusak. (4)
Catatan: 1. Ketika tombol INSPECTION/TEST remote kontrol ditekan, tampilan INSPECTION berkedip
masuk mode INSPECTION.
2. Dalam mode INSPECTION, jika tombol ON/OFF ditekan dan ditahan selama 5 detik atau lebih,
tampilan riwayat kesalahan tersebut OFF. Dalam hal ini, setelah kode kesalahan berkedip 2
kali, tampilan kode berganti menjadi “00” (= Normal) dan No. unit berganti menjadi “0”. Mode
INSPECTION otomatis beralih ke mode normal (tampilan suhu yang diatur).
3. Operasi berhenti karena kesalahan tergantung pada model atau kondisi.
4. Memecahkan masalah dengan menonaktifkan catu daya selama minimal 5 detik, hidupkan lagi
catu daya, dan kemudian periksa kembali tampilan LED.
3.2 Pemecahan masalah berdasarkan LED pada PCB Unit Outdoor Diagnosis berikut dapat dilakukan dengan menyalakan saklar daya dan memeriksa indikasi LED pada PCB
(A1P) dari unit outdoor.
k: LED MENYALA / h: LED MATI / l: LED Berkrdip / — : Tidak ada hubunganya dengan pemecahan masalah
Deteksi LED
Deskripsi Mikro-komputer di
HAP operasi normal
(Hijau)
l Normal
k PCB unit outdoor rusak( 1)
h Ketidaknormalan catu daya, PCB unit outdoor rusak ( 2)
l Aktivasi perangkat perlindungan ( 3)
Catatan : 1. Matikan saklar daya, dan nyalakan lagi setelah 5 detik atau lebih. Periksa kondisi kesalahan,
dan lakukan diagnosis masalah.
2. Matikan saklar daya. Setelah 5 detik atau lebih, cabut kabel sambungan (2). Kemudian hidupkan
saklar daya. Jika HAP pada PCB unit outdoor berkedip sekitar 10 detik, PCB unit indoor yang
rusak.
3. Juga periksa untuk fasa terbuka.
Keterangan: Monitor deteksi kesalahan terus berlanjut untuk mengindikasi kesalahan yang muncul
sebelumnya sampai saklar daya dimatikan.
Pastikan untuk mematikan saklar daya setelah pemeriksaan.
Diagnosis Servis 78
Pemecahan masalah berdasarkan Indikasi LED SiMT281515E
Cancel
Cancel
Cancel
4. Pemecahan masalah dengan Remote Kontrol
4.1 PenggantianMode 4.1.1 BRC1C61/BRC1D61
Mode berikut dapat dipilih dengan menggunakan tombol INSPECTION / TEST pada remote control .
Tekan tombol INSPECTION/TEST selama
lebih dari 4 detik.
• Waktu tanda
filter • Arah aliran
udara • Lain-lain
Mode Pengaturan bidang
mode Servis
• Riwayat kode kesalahan
• Data suhu dari berbagai bagian
Pengaturan servis dapat dilakukan.
• Kipas dipaksa menyala • Pengaturan laju aliran udara/arah aliran udara
Tekan tombol INSPECTION/TEST
selama lebih dari 4 detik.
mode Normal
Tekan tombol
sekali.
Tekan tombol INSPECTION/TEST
sekali.
setelah 10 detik
Tekan tombol INSPECTION/TEST sekali
atau setelah 30 menit
Kode berikut dapat diperiksa. • Kode kesalahan
• Kode model Indoor • Kode model Outdoor
mode Inspeksi
Tekan tombol INSPECTION/TEST
sekali.
mode Operasi uji coba
Termostat secara paksa DIAKTIFKAN.
4.1.2 BRC1E62
<Layar dasar> • Penggantian mode operasi
• Kontrol kecepatan kipas
• Tampilan Menu
• Konfirmasi setiap pengaturan • Menyala
• Mati • Pembatalan
• Lampu operasi
Mode menu utama
Tekan
sekali.
Layar
<Menu Utama> • Arah aliran udara
• Permulaan cepat (quick start )
• Pilihan Penghematan Energi
• Jadwal
• pembersihan otomatis filter • Informasi pemeliharaan
• Konfigurasi
• Pengaturan arus
• Jam & Kalender • Bahasa
Tekan tombol Cancel
selama 4 detik atau lebih.
dasar Tekan Cancel
sekali.
<Pengaturan Servis>
• Operasi uji coba
Mode
Tekan tombol
Tekan
sekali.
selama
< Menu Pemeliharaan>
• Kontak pemeliharaan
• Pengaturan bidang • Setpoint Min. berbeda
service setting
4 detik atau lebih. Menu Maintenance
• Nama Model • Jam operasi
• Status unit Indoor
• Alamat AirNet unit Outdoor • Riwayat kesalahan
• Status unit Indoor
• Status unit Outdoor
• Kipas Paksa • Saklar Kontroller Main Sub
• Indikator Filter
• Uji pembersihan otomatis filter
• Brush/Filter Ind. • Menonaktifkan
pembersihan otomatis filter
• Status unit Outdoor • Tampilan kesalahan
• Menukar No. Unit
• Nilai Sensor yang dialamatkan
INSPECTION/TEST
Tekan tombol
Menu/Enter
sekali.
Pengaturan unit indoor dapat dilakukan Data servis dapat diperoleh
79 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Remote Kontrol
4.2 Prosedur diagnosis sendiri dengan Remote Kontrol 4.2.1 Remote kontrol berkabel — BRC1C61/BRC1D61
Jika operasi berhenti karena kesalahan, LED operasi remote kontrol berkedip, dan kode kesalahan
ditampilkan. (Bahkan jika operasi penghentian dilakukan, isi kesalahan ditampilkan saat mode pemeriksaan
dimasukkan.) Kode kesalahan memungkinkan Anda untuk menceritakan apa jenis kesalahan menyebabkan
operasi berhenti. Lihat P.83 untuk kode kesalahan dan isi kesalahan.
LED Operation
Catatan: 1. Dengan menekan tombol INSPECTION/TEST akan berkedip indikasi pemeriksaan.
2. Selama dalam mode servis, tekan tombol ON / OFF selama 5 detik atau lebih akan menghapus
indikasi riwayat kegagalan yang ditunjukkan di atas. Dalam hal ini, pada tampilan kode, kode
kesalahan akan berkedip dua kali dan kemudian berubah menjadi “00” (= Normal), No. Unit akan
berubah menjadi “0”, dan mode operasi otomatis akan beralih dari mode servis ke mode normal
(Menampilkan suhu yang diatur).
tombol ON/OFF
Tampilan unit indoor dimana kesalahan terdeteksi
tampilan pemeriksaan
kode kesalahan
Tombol INSPECTION/TEST
Diagnosis Servis 80
Pemecahan masalah dengan Remote Kontrol SiMT281515E
4.2.2 Remote kontrol berkabel — BRC1E62 Berikut ini akan ditampilkan pada layar ketika sebuah kesalahan (atau peringatan) terjadi selama
operasi. Periksa kode kesalahan dan ambil tindakan perbaikan yang ditentukan untuk model tertentu.
Layar
Lampu operasi
(1) Memeriksa kesalahan atau peringatan
Status operasi Tampilan
Dimatikan tidak normal
sistem berhenti beroperasi.
Lampu operasi(hijau) mulai berkedip. pesan "Error: Push Menu button" akan muncul dan berkedip pada bagian bawah layar
Peringatan
sistem terus beroperasi.
Lampu operasi(hijau) tetap menyala. Pesan "Warning: Push Menu button" akan muncul dan berkedip pada bagian bawah layar.
(2) Melakukan tindakan perbaikan
· Tekan tombol Menu/Enter untuk memeriksa kode kesalahan.
· Lakukan tindakan perbaikan khusus untuk model tersebut.
Kode kesalahan
Nama model
yang berlaku
FBQ100EVE
RZR100LUY1
81 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Remote Kontrol
4.2.3 Remote Kontrol Nirkabel Jika unit berhenti karena kesalahan, LED indikasi operasi pada bagian penerima sinyal berkedip. Kode
kesalahan dapat ditentukan dengan mengikuti prosedur yang diuraikan di bawah ini. (Kode kesalahan
ditampilkan ketika kesalahan operasi telah terjadi. Dalam kondisi normal, kode kesalahan dari masalah
terakhir ditampilkan.)
1 Tekan tombol INSPECTION/TEST untuk memilih “inspection”. Peralatan masuk
mode inspeksi. Indikasi “Unit” ditampilkan dan tampilan No. Unit menunjukkan indikasi “0” berkedip.
2 Atur No. Unit Tekan tombol UP atau DOWN dan ubah tampilan No. Unit sampai bel (1) dihasilkan dari unit indoor. 1. Jumlah bunyi bip
3 bunyi bip pendek: Melakukan semua operasi berikut. 1 bunyi bip panjang: Melakukan langkah 3 dan 4.
Melanjutkan operasi pada langkah 4 sampai bel tetap AKTIF. Bel terus menerus menunjukkan bahwa kode kesalahan dikonfirmasi.
Bunyi bip terus menerus: tidak ada kelainan.
3 Tekan tombol pemilih MODE. Indikasi “0” kiri (digit atas) kode kesalahan berkedip.
4 diagnosis digit atas kode kesalahan Tekan tombol UPatau DOWN dan ubah digit atas kode kesalahan sampai bel pencocokan kode kesalahan (2) dihasilkan.
Digit atas kode berubah seperti yang ditunjukkan di bawah ini jika tombol UP dan DOWN ditekan.
0 A C E H F J L P U 9 8 7 6 5 4 Tombol "UP" tombol "DOWN"
2 Jumlah bunyi bip Bunyi bip terus menerus: Kedua digit atas dan bawah dicocokkan. (Kode kesalahan dikonfirmasi)
2 bunyi bip pendek: Digit atas dicocokkan. 1 bunyi bip pendek Digit bawah dicocokkan.
5 Tekan tombol pemilih MODE. Indikasi “0” kanan (digit bawah) kode kesalahan berkedip.
6 diagnosis digit bawah kode kesalahan Tekan tombol UP atau DOWN dan ubah digit bawah kode kesalahan terus menerus sampai bel pencocokan kode kesalahan (2) dihasilkan. Digit bawah kode berubah seperti yang ditunjukkan di bawah ini jika tombol
UP dan DOWN ditekan.
0 1 2 3 4 5 6 7 8 9 A H C J E F Tombol "UP" Tombol "DOWN"
Diagnosis Servis 82
Pemecahan masalah dengan Remote Kontrol SiMT281515E
Normal status Enters inspection mode from normal status when the INSPECTION/TEST button is pressed.
1 Press INSPECTION/TEST button.
If no button is pressed for 1 minute, equipment returns to normal status.
5 Press MODE selector button.
Jika tidak ada tombol ditekan selama 1 menit, peralatan kembali ke status normal.
Jika tombol pemilih MODE ditekan atau tidak ada tombol ditekan selama 1 menit, peralatan kembali ke status.normal
3
Tekan
tombol
pemilih
MODE
.
Status normal Masuk mode operasi dari status normal jika tombol INSPECTION/TEST ditekan
1. Tekan tombol INSPECTION/TEST
Jika tidak ada tombol ditekan selama 1 menit, peralatan kembali ke status normal
Jika tidak ada tombol ditekan selama 1 menit, peralatan kembali ke status normal
5 Tekan tombol pemilih MODE
83 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Remote Kontrol
4.3 Kode Kesalahan dan Deskripsi
Tampilan Remote Kontrol
Isi Kesalahan
Halaman referensi
Unit Indoor A0 Perangkat perlindungan eksternal —
A1 Ketidaknormalan PCB unit indoor 88
A3 Ketidaknormalan sistem permukaan air saluran 89
A6 Kunci motor kipas unit indoor 91
Ketidaknormalan motor kipas unit indoor 92
A8 Ketidaknormalan PCB kipas 94
AF Ketidaknormalan sistem saluran 95
AJ Ketidaknormalan pengaturan Kapasitas 96
C1 Kesalahan transmis (antara PCB unit indoor dan PCB kipas) 97
C4 Ketidaknormalan termistor pipa cair penukar panas Indoor 101
C5 Ketidaknormalan termistor penukar panas Indoor 101
C6 Kesalahan kombinasi antara PCB unit indoor dan PCB kipas 102
C9 Ketidaknormalan termistor udara hisap 101
CJ Ketidaknormalan termistor Remote kontrol 103
Unit Outdoor
E1 Ketidaknormalan PCB unit Outdoor 104
E3 Ketidaknormalan Tekanan Tinggi (terdeteksi oleh saklar tekanan tinggi) 105
E5 Kunci motor kompresor 107
E7 Ketidaknormalan motor kipas unit Outdoor 108
E9 Ketidaknormalan katup ekspansi elektronik 110
F3 Ketidaknormalan suhu pipa pembuangan 112
H3 Ketidaknormalan sistem saklar tekanan tinggi 113
H9 Ketidaknormalan termistor udara Outdoor 114
J1 Ketidaknormalan sensor tekanan 115
J3 Ketidaknormalan termistor pipa pembuangan 114
J5 Ketidaknormalan termistor pipa hisap 114
J6 Ketidaknormalan termistor pipa cair 114
J7 Ketidaknormalan termistor penukar panas sedang 114
L1 Ketidaknormalan PCB unit Outdoor 116
L4 Suhu sirip radiasi naik 118
L5 Arus lebih output DC (seketika) 120
L8 Termal elektronik (jeda waktu) 122
L9 Pencegahan Stall (jeda waktu) 124
LC Kesalahan sistem transmisi antara PCB unit outdoor 126
P1 Ketidakseimbangan tegangan catu daya atau fasa terbuka 127
P4 Ketidaknormalan termistor sirip radiasi 128
PJ Ketidaknormalan pengaturan kapasitas 129
Sistem U0 Kekurangan refrigerant 130
U2 Ketidaknormalan tegangan catu daya 131
U4 Kesalahan transmisi antara unit indoor dan unit outdoor 132
U5 Kesalahan transmisi antara unit indoor dan remote kontrol 134
U8 Kesalahan transmisi antara remote kontrol MAIN dan remote kontrol SUB
135 UA Ketidaknormalan saklar pengaturan bidang 136
UC Kesalahan pengaturan alamat terpusat 137
UF Kesalahan transmisi antara unit indoor dan outdoor / pemipaan dan ketidakcocokan kabel / kekurangan refrigeran
138
Diagnosis Servis 84
Pemecahan masalah dengan Remote Kontrol SiMT281515E
4.4 Kode Kesalahan – kode Sub Jika kode kesalahan seperti yang ditunjukkan di bawah ini ditampilkan saat navigasi remote kontrol
(BRC1E62) sedang digunakan, buat rincian diagnosis atau diagnosis mengenai unit terkait dengan
mengacu pada daftar rincian kode kesalahan yang terlampir.
4.4.1 Unit Indoor
Kode Kesalahan
Pemecahan masalah
Deskripsi kesalahan Deskripsi diagnosis
A6 - 01 Motor kipas terkunci Arus motor kipas yang terkunci telah terdeteksi.
Putar kipas dengan tangan untuk memeriksa sambungan
Konektor .
A6 - 10 Kesalahan arus berlebih Kipas Arus berlebih motor kipas telah terdeteksi. Periksa sambungan konektor antara motor kipas dan PCB kipas. Jika sambungan normal, ganti motor kipas. Jika hal ini masih tidak bisa mengatasi kesalahan, ganti PCB kipas.
A6 - 11 Kesalahan deteksi posisi kipas Kesalahan dalam pendeteksian posisi motor kipas. Periksa sambungan konektor antara motor kipas dan PCB kipas. Jika sambungan normal, ganti motor kipas. Jika hal ini masih tidak bisa mengatasi kesalahan, ganti PCB kipas.
A8 - 01 Ketidaknormalan PCB kipas Kesalahan tegangan catu daya PCB kipas telah terdeteksi. Periksa apakah ada sambungan konektor longgar atau putus, atau sumber dari pembangkit kebisingan di dekatnya.
C1 - 01 Kesalahan transmisi Kesalahan transmisi telah terdeteksi antara PCB unit indoor dan PCB kipas. Periksa apakah ada sambungan konektor transmisi longgar atau putus.
C4 - 02 Ketidaknormalan sistem termistor Penukar panas Korsleting termistor telah terdeteksi. Periksa area
(korsleting) Sambungan apakah ada penyumbatan benda asing
C4 - 03 Ketidaknormalan sistem termistor Penukar panas (Sirkuit terbuka)
Pemutusan termistor telah terdeteksi. Periksa apakah ada sambungan konektor longgar atau putus.
C5 - 02 Ketidaknormalan sistem termistor Penukar panas Korsleting termistor telah terdeteksi. Periksa area
sedang (korsleting) Sambungan apakah ada penyumbatan benda asing
C5 - 03 Ketidaknormalan sistem termistor Penukar panas sedang (Sirkuit terbuka)
Pemutusan termistor telah terdeteksi. Periksa apakah ada sambungan konektor longgar atau putus.
C6 - 01 Kombinasi PCB unit indoor dan PCB kipas rusak Kombinasi PCB unit indoor dan PCB kipas rusak. Periksa apakah adaptor pengaturan kapasitas benar dan jenis PCB kipas benar.
C9 - 02 Ketidaknormalan sistem termistor udara hisap (short
Korsleting termistor telah terdeteksi. Periksa area
(korsleting) Sambungan apakah ada penyumbatan benda asing
C9 - 03 Ketidaknormalan sistem termistor udara hisap (Sirkuit terbuka)
Pemutusan termistor telah terdeteksi. Periksa apakah ada sambungan konektor longgar atau putus
85 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Remote Kontrol
4.4.2 Unit Outdoor
Kode Kesalahan
Pemecahan masalah
Deskripsi kesalahan Deskripsi diagnosis
E7 - 01 Kunci motor kipas Motor kipas telah menyebabkan rotasi tidak normal. Periksa sambungan konektor antara motor kipas dan PCB unit outdoor. Jika sambungan normal, ganti motor kipas. Jika hal ini masih tidak bisa mencegah kesalahan, ganti PCB unit outdoor.
L1 - 01 Kesalahan arus berlebih sesaat (selama dalam Lihat diagram alir “L1” dari setiap panduan dan lakukan
Operasi startup) diagnosis mengenai unit terkait berdasarkan kode kesalahan
L1 - 02 Yang ditunjukkan pada sisi kiri. Kesalahan sensor arus di PCB
L1 - 03 Kesalahan offset arus L1 - 04 Kesalahan IGBT (1) L1 - 05 Kesalahan pengaturan Jumper L1 - 06 Kesalahan tegangan berlebih SP/MP-PAM (2, 3) L8 - 01 Kesalahan termal elektronik 1 Beban arus berlebih selama 260 detik atau lebih
Kesalahan ini seharusnya akibat dari pengisian refrigeran
Yang berlebihan, kerusakan yang disebabkan bantalan
kompresor, tekanan terlalu tinggi, dll. periksa dan selidiki
Penyebabnya.
L8 - 02 Kesalahan termal elektronik 2 Arus beban berlebih dekat dengan arus terkunci yang dialirkan dalam termal selama lima detik. Kesalahan ini seharusnya akibat dari katup penghenti tertutup, kabel dalam motor kompresor terputus, dll. Periksa dan selidiki penyebabnya.
L8 - 03 Penurunan revolusi kompresor Beban kompresor telah meningkat setelah startup. Kesalahan ini seharusnya akibat dari kegagalan daya sesaat, kembalinya cairan, dll. periksa dan selidiki penyebabnya.
L8 - 04 Kesalahan deteksi petir Lonjakan yang disebabkan oleh petir
L8 - 05 Arus pembatas inverter Arus batas berlebih mengalir dalam inverter. Kesalahan ini seharusnya akibat dari kegagalan untuk membuka katup penghenti, pengisian refrigeran yang berlebihan, penyumbatan dalam filter unit indoor, noda dalam penukar panas unit indoor/outdoor dll.. periksa dan selidiki penyebabnya.
L9 - 01 Pencegahan Stall (kenaikan arus) Arus beban berlebih telah diterapkan untuk memulai
kompresor.
Kesalahan ini seharusnya akibat dari tekanan diferensial
Startup tinggi, kembalinya cairan, minyak kompresor
Berlebihan, minyak kompresor tidak normal, getaran
Poros kompresor, dll..
Periksa dan selidiki penyebabnya.
L9 - 02 Pencegahan Stall (kesalahan startup) Kompresor belum menyelesaikan operasi startup. Kesalahan ini seharusnya akibat dari tekanan diferensial startup tinggi, kembalinya cairan, minyak kompresor berlebihan, minyak kompresor tidak normal, getaran poros kompresor, sirkuit deteksi posisi rusak, dll.. Periksa dan selidiki penyebabnya.
PJ - 01 Pengaturan kapasitas tidak dilakukan Ini adalah PCB unit outdoor untuk perbaikan, tetapi tidak capacity Memiliki adaptor pengaturan yang terhubung. Sambungkan correct capacity adaptor pengaturan ke PCB.
PJ - 04 Pengaturan kapasitas rusak Kesalahan ini hasil dari ketidakcocokan sinyal antara kontroler di PCB dan inverter. Periksa apakah jenis PCB sesuai dan adaptor pengaturan kapasitas sesuai terhubung.
U0 - 02 Kekurangan Refrigeran - unit Outdoor (Faktor 0) Kesalahan ini akibat dari kekurangan refrigeran. Lihat
Diagram alir pemecahan masalah “U0” dan lakukan
Diagnosis dan kemudian ambil tindakan pencegahan.
U0 - 03 Kekurangan Refrigeran - unit Outdoor (Faktor 1) Kesalahan ini akibat dari kekurangan refrigeran yang disebabkan oleh kebocoran gas. Isi refrigeran hingga jumlah refrigeran normal.
U0 - 04 Kekurangan Refrigeran - unit Outdoor (Faktor 2) Kesalahan ini akibat dari penyumbatan yang disebabkan sesuatu dalam
sistem pemipaan refrigeran. Periksa kegagalan untuk membuka katup
penghenti dan penyumbatan dalam sistem refrigeran.
Catatan: 1. IGBT: IGBT adalah perangkat semikonduktor daya terutama digunakan sebagai saklar
elektronik.
2. SP: Single Pulse (Pulsa tunggal) 3. MP: Multi Pulse (Beberapa pulsa)
Diagnosis Servis 86
Pemecahan masalah dengan Remote Kontrol SiMT281515E
Pemecahan masalah
Deskripsi kesalahan Deskripsi diagnosis
U2 - 01 Kesalahan tegangan catu daya Kesalahan ini seharusnya akibat dari tegangan catu daya
kurang atau berlebih, atau sensor tegangan di PCB rusak
U2 - 02 Fasa catu daya terbuka Periksa setiap fasa catu daya terbuka.
U2 - 03 Kesalahan muatan kapasitor sirkuit utama Ada arus sirkuit yang tidak normal mengalir di PCB. Jika sambungan kabel terkait dengan PCB normal, ganti PCB unit outdoor.
U2 - 04 Kesalahan tegangan berlebih SP/MP - PAM Ada kesalahan tegangan berlebih (fasa tunggal). Jika sambungan kabel terkait dengan PCB normal, ganti PCB unit outdoor.
UA - 01 Nomor unit indoor yang terhubung tidak sesuai Kesalahan ini akan ditampilkan jika jumlah unit indoor
yang diatur secara lokal berbeda dari jumlah unit indoor yang terdeteksi.
UA - 02 Beberapa unit induk terdeteksi Ada sejumlah unit indoor dengan remote kontrol yang terhubung. Hubungkan remote kontrol hanya ke salah satu unit indoor.
UA - 03 Unit indoor yang terhubung berlebih Kesalahan ini akan ditampilkan jika lima atau lebih unit indoor terhubung.
UA - 05 Kesalahan transmisi Indoor-Outdoor antara slave 1 dan unit outdoor
Ada kesalahan dalam transmisi antara unit outdoor dan unit indoor slave 1. Periksa sambungan jumper antara unit indoor slave (dengan tanpa remote kontrol yang terhubung) dan unit outdoor.
UA - 07 Kesalahan transmisi Indoor-Outdoor antara slave 2 dan unit outdoor
Ada kesalahan dalam transmisi antara unit outdoor dan unit indoor slave 2. Periksa sambungan jumper antara unit indoor slave (dengan tanpa remote kontrol yang terhubung) dan unit outdoor.
UA - 09 Kesalahan transmisi Indoor-Outdoor antara slave 3 dan unit outdoor
Ada kesalahan dalam transmisi antara unit outdoor dan unit indoor slave 3. Periksa sambungan jumper antara unit indoor slave (dengan tanpa remote kontrol yang terhubung) dan unit outdoor.
UF
UF
-
-
01
02
Pengkabelan tidak sesuai Ada kesalahan dalam sambungan kabel untuk transmisi antara unit indoor dan outdoor (dinilai dengan unit indoor). periksa sambungan jumper 1, 2, dan 3 antara unit indoor dan outdoor.
Pemipaan terhubung sebaliknya Ada kesalahan dalam mode operasi dan suhu deteksi pemipaan refrigeran. Periksa pipa refrigeran yang terhubung sebaliknya, kekurangan refrigerant, dll.
kode kesalahan
87 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Remote Kontrol
4.5 Gambaran Umum Perangkat Keselamatan Outdoor
Model Saklar tekanan tinggi
Sekring Terbuka Tertutup
RZR-LUY1(4) 4.0 + 0
– 0.15
MPa 3.0 ± 0.15 MPa A1P
6.3 A / 250 V (F1U, F2U, F3U, F4U)
31.5 A / 500 V (F5U, F6U)
A2P
5.0 A / 250 V (F1U)
4.6 Gambaran Umum Perangkat Keselamatan Indoor
Model Sekring PCB Motor kipas Sekring Termal
Sekring PCB (pengerak kipas)
FBQ-E 3.15 A / 250 V (F1U) 6.3 A / 250 V (F4U) Tidak tersedia 5.0 A / 250 V (F2U)
Diagnosis Servis 88
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
5. Pemecahan masalah dengan Indikasi pada
Remote Kontrol
5.1 Ketidaknormalan PCB Unit Indoor
Kode Kesalahan A1
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Periksa data dari E²PROM.
Kondisi
putusan
kesalahan
Kesalahan yang dihasilkan ketika data dari E²PROM tidak diterima dengan benar.
E²PROM (Electrically Erasable Programmable Read Only Memory): Sebuah chip memori
yang menyimpan konten tanpa daya. Memori dapat dihapus, baik di dalam komputer
atau di luar dan biasanya membutuhkan lebih banyak tegangan untuk penghapusan dari
tegangan +5 volt yang umum digunakan dalam rangkaian logika. E²PROM berfungsi
seperti RAM yang tidak mudah hilang, tetapi untuk menulis ke E²PROM lebih lambat
daripada menulis ke RAM.
Penyebab
seharusnya
PCB unit indoor rusak
Faktor Eksternal (Kebisingan, dll)
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Ganti PCB unit indoor.
Kesalahan dapat disebabkan oleh faktor eksternal, bukan
bagian yang rusak.
Cari penyebabnya dan perbaiki situasinya.
Matikan daya dan hidupkan lagi untuk
memulai ulang.
diatur ulang normal? Tidak
YA
89 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
5.2 Ketidaknormalan Sistem Permukaan Air Saluran
Kode Kesalahan A3
Model yang
berlaku Semua model indoor
Metode deteksi
kesalahan
Dengan deteksi saklar apung OFF
Kondisi
putusan
kesalahan
Kesalahan dihasilkan ketika permukaan air mencapai batas atas dan ketika saklar apung OFF
Penyebab
seharusnya
Pompa saluran rusak
Pekerjaan pipa saluran tidak tepat
Penyumbatan pipa saluran
Saklar apung rusak
PCB Unit indoor rusak
Konektor korsleting X15A rusak
Diagnosis Servis 90
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Sambungan konektor hubung pendek
Ganti konektor hubung pendek.
Ganti PCB unit indoor.
Hubungkan pompa saluran.
Keridaknormalan sistem saluran
Hubungkan saklar apung.
Ganti saklar apung.
Ganti PCB unit indoor.
Ganti pompa saluran.
Ganti PCB unit indoor.
Lepas saklar apung dan hubung
singkat, kemudian mulai ulang operasi.
Atur ke “emergency” dan periksa tegangan konektor dimana pompa saluran terhubung.
Apakah mekanisme pompa saluran terhubung?
TIDAK Apakah konektor hubung singkat terhubung ke PCB
unit indoor?
TIDAK
YA YA
Periksa kontinuitas konektor hubung singkat. Apakah ada kontinuitas?
YA
TIDAK
Apakah pompa saluran terhubung ke PCB unit indoor?
TIDAK
YA
Apakah pompa saluran
bekerja setelah memulai
ulang operasi?
YA Apakah ketidaknormalan
permukaan air saluran tinggi?
YA
A pak ah s akl ar apung terhubung
ke P CB unit indoor?
TIDAK
YA
Kesalahan ditampilkan lagi
TIDAK
YA
220 (±10%) VAC? YA
TIDAK TIDAK
TIDAK
91 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
5.3 Kunci Motor Kipas Unit Indoor
Kode Kesalahan A6
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Kesalahan dalam putaran kipas terdeteksi oleh sinyal dari motor kipas.
Kondisi
Putusan
Kesalahan
Kesalahan dihasilkan ketika rotasi kipas tidak meningkat.
Penyebab
seharusnya
Kipas tidak berputar karena tersumbat benda asing.
Sambungan harness motor kipas putus, korsleting atau longar
Sambungan konektor antara PCB unit indoor dan PCB kipas longgar
Kunci motor kipas (faktor eksternal atau terkait motor)
Motor kipas rusak (kegagalan pemutusan atau isolasi)
Kesalahan sinyal dari motor kipas (sirkuit rusak)
PCB unit indoor rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Hilangkan benda asing tersebut.
hubungkan dengan benar.
Ganti motor kipas.
Ganti PCB unit indoor.
Ganti motor kipas.
CHECK 4 Lihat Halaman 143.
Matikan catu daya dan tunggu
selama 10 menit.
Periksa CHECK 4 untuk
konektor motor kipas
Apakah ada benda asing di sekitar kipas?
YA
Apakah konektor kipas terhubung ke PCB unit
indoor dengan benar? TIDAK
YA
Apakah kipas dapat diputar dengan mudah menggunakan tangan setelah melepaskan konektor motor kipas dari PCB unit indoor?
TIDAK
YA
Apakah setiap hambatan antara pin sama dengan atau lebih tinggi dari standar nilai?
TIDAK
YA
TIDAK
Diagnosis Servis 92
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
5.4 Ketidaknormalan Motor Kipas Unit Indoor
Kode Kesalahan A6
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Dideteksi dengan nilai arus yang mengalir melalui PCB kipas
Dideteksi dengan rotasi kipas saat motor kipas diindikasikan berputar
Dideteksi dengan sinyal lokasi dari motor kipas
Dideteksi dengan nilai arus yang mengalir melalui PCB kipas saat motor kipas dijalankan
Kondisi
Putusan
Kesalahan
Jika aliran arus berlebih.
Jika rotasi kipas tetap kurang dari jumlah tertentu selama enam detik.
Kesalahan lokasi rotor kipas terus berlanjut selama 5 detik atau lebih.
Penyebab
seharusnya
Tersumbat benda asing
Pemutusan konektor motor kipas
Pemutusan konektor antara PCB unit indoor dan PCB kipas
PCB kipas rusak
Motor kipas rusak
93 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
Matikan catu daya dan tunggu
selama 10 menit.
Ada benda asing disekitar kipas.
TIDAK
Konektor motor kipas terputus dari PCB kipas.
TIDAK
The connector between the indoor unit PCB and the fan PCB is
disconnected.
Tidak ada kontinuitas di sekring pada PCB kipas.
Matikan catu daya dan tunggu
selama 10 menit.
Lampu HAP pada PCB(A1P) unit indoor
berkedip sementara lampu HAP pada PCB (A2P) kipas
tidak berkedip.
YA
Setiap hambatan antara pin sama dengan atau lebih rendah dari 1.
YES
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
YA
Hilangkan benda asing tersebut.
YA
Hubungkan konektor dengan benar.
YA Hubungkan konektor dengan benar.
YA Ganti PCB kipas.
TIDAK
Nyalakan catu daya selama konektor
motor kipas tidak terhubung.
Ganti motor kipas.
Ganti PCB kipas.
Ganti PCB kipas.
Jika ketidaknormalan "A6" masih terjadi lagi.
Ganti motor kipas.
Ganti motor kipas.
CHECK 4 Lihat Halaman 143.
Matikan catu daya dan tunggu selama 10 menit.
Periksa CHECK 4 untuk
konektor motor kipas
Konektor antara PCB unit indoor dan PCB kipas tidak terhubung
TIDAK
TIDAK
YA
Diagnosis Servis 94
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
5.5 Ketidaknormalan PCB Kipas
Kode Kesalahan A8
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Mikro-komputer memeriksa kondisi tegangan PCB kipas.
Kondisi
Putusan
Kesalahan
Ketika tegangan berlebih atau penurunan tegangan terdeteksi pada PCB kipas.
Penyebab
seharusnya
Sambungan konektor catu daya rusak
PCB unit indoor rusak
PCB kipas rusak
Faktor eksternal seperti kebisingan
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Hubungkan dengan benar.
Hubungkan dengan benar.
Ganti harness.
Hilangkan faktor eksternal.
Normal.
Periksa PCB unit indoor dan
PCB kipas.
Apakah konektor X3A pada PCB unit indoor terhubung dengan benar?
YA
Apakah konektor X70A pada PCB kipas terhubung dengan benar?
YA
Apakah sambungan harness X3A dan X70A tidak terhubung?
YA
Apakah ada faktor eksternal seperti kebisingan?
YA
TIDAK
Matikan catu daya dan kemudian nyalakan lagi.
Masukan unit ke dalam operasi dengan remote kontrol.
Kesalahan ditampilkan lagi.
YA
TIDAK
TIDAK
TIDAK
TIDAK
95 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
5.6 Ketidaknormalan Sistem Saluran
Kode Kesalahan AF
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Kebocoran air terdeteksi berdasarkan operasi saklar ON/OFF apung selama kompresor tidak
beroperasi.
Kondisi
Putusan
Kesalahan
Saklar apung berubah dari ON ke OFF selama kompresor OFF.
Penyebab
seharusnya
Kesalahan instalasi pipa saluran
Saklar apung rusak
PCB unit indoor rusak
Sambungan konektor rusak
Pompa saluran rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar listrik sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Saklar apung
Kemungkinan kegagalan saklar apung. Periksa untuk melihat apakah ketinggian saluran atas dan panjang pipa horizontal melebihi spesifikasi.
Sistem pembuangan air saluran tersumbat. Pompa saluran tersumbat. Saklar apung rusak.
Pompa saluran
Ganti PCB unit indoor. Periksa untuk melihat apakah ketinggian saluran atas dan panjang pipa horizontal melebihi spesifikasi.
Periksa konektor X15A jumper.
Periksa Pompa saluran dan pipa saluran.
Periksa sistem pembuangan. Periksa untuk melihat apakah ketinggian saluran atas dan panjang pipa horizontal melebihi spesifikasi.
Pengatur dalam sistem pembuangan air tidak normal
Ganti PCB unit indoor.
Apakah saklar apung dan pipa
saluran normal?
TIDAK
YA
Apakah sistem
pembuangan air normal?
TIDAK
YA
Apakah pompa
saluran terpasang?
YA
TIDAK
Apakah pompa saluran normal?
YA
TIDAK
Apakah jumlah air saluran beredar terlalu banyak setelah operasi penghentian pompa?
YA
Apakah aliran air saluran
ke belakang selama tidak
ada operasi?
YA
TIDAK TIDAK
TIDAK
Diagnosis Servis 96
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
5.7 Ketidaknormalan Pengaturan Kapasitas
Kode Kesalahan AJ
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Kapasitas ditentukan sesuai dengan hambatan adaptor pengaturan kapasitas dan memori
dalam memori IC pada PCB unit indoor, dan apakah nilai normal atau tidak normal ditentukan.
Kondisi
Putusan
Kesalahan
Ketika kode kapasitas tidak disimpan ke PCB, dan adaptor pengaturan kapasitas tidak
tersambung.
Ketika kapasitas tersebut tidak ada untuk itu unit ditetapkan.
Penyebab
seharusnya
Sambungan adaptor pengaturan kapasitas rusak
PCB unit indoor rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Ganti PCB unit indoor.
Ganti PCB unit indoor.
Pasang adaptor pengaturan kapasitas.
PCB unit indoor diganti dengan PCB
alternatif.
YA
Adaptor
pengaturan kapasitas harus terpasang saat
mengganti PCB.
YA
TIDAK
TIDAK
97 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
5.7 Kesalahan Transmisi (antara PCB Unit Indoor dan PCB Kipas)
Kode Kesalahan C1
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Periksa kondisi transmisi antara PCB (A1P) Unit indoor dan PCB (A2P) kipas dengan
menggunakan mikro-komputer.
Kondisi
Putusan
Kesalahan
Jika transmisi normal tidak dilakukan selama jangka waktu tertentu.
Penyebab
seharusnya
Sambungan konektor antara PCB (A1P) unit indoor dan PCB (A2P) kipas rusak
PCB (A1P) indoor unit rusak
PCB (A2P) kipas rusak
Faktor eksternal, seperti pemadaman sementara
Diagnosis Servis 98
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Pemecahan masalah
Perhatian
Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Hubungkan konektor secara akurat.
Ganti PCB (A1P) unit indoor.
Ganti PCB (A2P) kipas.
Hubungkan dan lanjutkan operasi tersebut (Hal ini dimungkinkan
memiliki penyebab, seperti
pemadaman sesaat).
Catatan: 1. Tarik keluar dan masukkan konektor sekali dan pastikan benar-benar terhubung.
2. Metode untuk memeriksa bagian transmisi PCB unit indoor.
Matikan daya dan lepas konektor X70A dari PCB (A1P) unit indoor
Hubung singkat X70A.
Setelah menghidupkan daya, periksa angka di bawah ini berdasarkan pengaturan
bidang dari remote kontrol. (Konfirmasi: No. kode kedua saat kondisi No. kode pertama
21 pada No. mode 41)
Penentuan 01: Normal
Selain 01: Kesalahan transmisi pada PCB unit indoor
Setelah konfirmasi, matikan daya, lepaskan hubung singkat dan hubungkan X70A
kembali ke kondisi aslinya.
Konfirmasi kondisi transmisi pada PCB unit indoor menggunakan Mode
pengaturan bidang. (2)
Hubungkan konektor X70A
dan nyalakan daya lagi.
Apakah konektor antara PCB (A1P) unit indoor dan PCB (A2P)
kipas secara akurat terhubung? (1)
YA
Dalam mode pengaturan bidang di atas, No. kode
kedua adalah "01".
YA
Kesalahan ditampilkan lagi.
YA
TIDAK
TIDAK
TIDAK
99 Diagnosis Servis
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
5.9 Kesalahan transmisi (antara PCB Unit Indoor dan PCB Kipas)
Kode Kesalahan C1-01
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Periksa kondisi transmisi antara PCB unit indoor dan PCB kipas dengan menggunakan mikro-
komputer.
Kondisi
Putusan
Kesalahan
Kesalahan diputuskan ketika transmisi antara PCB unit indoor dan PCB kipas telah hilang
selama 15 detik dan kode kesalahan akan ditampilkan pada remote kontrol 60 detik
kemudian.
Penyebab
seharusnya
Sambungan konektor transmisi antara PCB unit indoor dan PCB kipas rusak
PCB unit indoor rusak
PCB kipas rusak
Faktor eksternal seperti kebisingan
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 100
Pemecahan masalah
Perhatian astikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Hubungkan dengan benar.
Hubungkan dengan benar.
Hubungkan dengan benar.
Ganti harness.
Hilangkan faktor eksternal.
Normal.
Periksa PCB unit indoor dan PCB kipas.
Apakah konektor X70A pada PCB unit indoor terhubung dengan benar?
YA
Apakah konektor X3A pada PCB kipas
terhubung dengan benar?
YA
Apakah konektor X10A
pada PCB kipas terhubung dengan
benar?
YA
Apakah harness tidak terhubung?
YA
Apakah ada faktor eksternal seperti
kebisingan selain kegagalan?
TIDAK
Matikan catu daya dan kemudian
hidupkan lagi.
Masukan unit ke dalam operasi dengan remote kontrol.
YA
Kesalahan ditampilkan lagi.
YA
TIDAK
TIDAK
TIDAK
TIDAK
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
101 Service Diagnosis
5.10 Ketidaknormalan Termistor
Kode Kesalahan C4, C5, C9
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Kesalahan dideteksi dengan suhu yang terdeteksi oleh termistor.
Kondisi
Putusan
Kesalahan
Ketika termistor menjadi terputus atau korsleting saat unit sedang berjalan.
Penyebab
seharusnya
Sambungan konektor rusak
Termistor rusak
PCB unit indoor rusak
Kabel putus atau tidak tersambung
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Perbaiki sambungan.
Ganti Termistor yang
rusak.
Perbaiki kontak.
Ganti PCB unit outdoor.
C4: Termistor (R2T) pipa cair penukar panas Indoor
C5: Termistor (R3T) penukar panas Indoor C9: Termistor (R1T) udara hisap
CHECK 1 Lihat Halaman 139, 140.
Periksa sambungan konektor.
Periksa hambatan termistor.
Periksa kontak antara termistor dan
PCB.
Apakah tersambung dengan benar? TIDAK
YA
CHECK 1 apakah normal?
YA
TIDAK
apakah kontak OK? TIDAK
YA
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 102
5.11 Kesalahan kombinasi antara PCB Unit Indoor dan PCB Kipas
Kode Kesalahan C6
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Melakukan deteksi jalur terbuka dengan PCB kipas dengan menggunakan PCB (A1P) unit indoor.
Kondisi
Putusan
Kesalahan
Ketika data komunikasi PCB kipas ditentukan sebagai data yang salah.
Penyebab
seharusnya
PCB kipas rusak
Sambungan adaptor pengaturan kapasitas rusak
Pengaturan bidang rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Ganti dengan PCB (A2P) kipas yang benar.
Setelah membangun transmisi untuk indoor dan outdoor,
lakukan diagnosis operasi sekali
lagi.
Pasang adaptor pengaturan kapasitas yang benar.
Catatan: 1. Tipe PCB kipas.
Setelah membangun transmisi untuk indoor dan outdoor,
lakukan diagnosis operasi sekali
lagi.
Model yang berlaku Tipe PCB kipas
FBQ60/71EVE(4) PC14006-13(A)
FBQ100/125/140EVE(4) PC14006-14(A)
Apakah tipe PCB
(A2P) kipas benar? (1) TIDAK
YA
Apakah PCB (A1P) unit indoor diganti dengan PCB alternatif?
TIDAK
YA
Apakah adaptor pengaturan kapasitas yang benar
terpasang saat menempatkannya dengan
PCB alternatif?
TIDAK
YA
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
103 Service Diagnosis
5.12 Ketidaknormalan Termistor Remote Kontrol
Kode Kesalahan CJ
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Bahkan kesalahan dideteksi, sistem ini tersedia untuk operasi melalui sensor suhu hisap
indoor.
Kesalahan dideteksi pada suhu yang terdeteksi oleh sensor suhu udara dari remote kontrol.
¥ sistem terus beroperasi sementara kode kesalahan ditampilkan.
Kondisi
Putusan
Kesalahan
Ketika termistor suhu udara remote kontrol tidak terhubung atau terputus aliran dalam
operasi.
Penyebab
seharusnya
Termistor remote kontrol rusak
PCB remote kontrol rusak
Faktor eksternal seperti kebisingan
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Ganti remote kontrol.
Faktor eksternal seperti kebisingan yang diduga.
Catatan: 1. Riwayat kode kesalahan dihapus dengan menekan dan menahan tombol On / Off
selama lima detik atau lebih di mode Pemeliharaan remote kontrol.
Hapus riwayat kode kesalahan
remote kontrol (1).
Kesalahan ditampilkan lagi. YA
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 104
5.13 Ketidaknormalan PCB Unit Outdoor
Kode Kesalahan E1
Model yang
berlaku
Metode Deteksi
Kesalahan
Kondisi
Putusan
Kesalahan
RZR
Mikro-komputer memeriksa apakah E2PROM normal.
Ketika kesalahan E2PROM saat menghidupkan catu daya
Penyebab
seharusnya
PCB unit outdoor rusak
Motor kipas rusak
Faktor eksternal (Kebisingan, dll.)
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Masalah dapat disebabkan oleh faktor eksternal (kebisingan, dll.) selain kesalahan.
Ganti PCB (A1P) unit outdoor.
Periksa motor kipas.
Matikan catu daya sekali dan
kemudian hidupkan ulang
Matikan catu daya, lepas konektor motor kipas dan kemudian hidupkan
catu daya lagi.
YA
Kesalahan ditampilkan lagi. YA
TIDAK
TIDAK
Apakah pengaturan
ulang memungkinkan?
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
105 Service Diagnosis
5.14 Ketidaknormalan Tekanan Tinggi (Dideteksi dengan saklar Tekanan Tinggi)
Kode Kesalahan E3
Model yang
berlaku
RZR
Metode Dteksi
Kesalahan
Sirkuit perangkat perlindungan memeriksa kontinuitas dalam saklar tekanan tinggi.
Kondisi
Putusan
Kesalahan
Saklar tekanan tinggi digerakkan pada 4,0 MPa.
Penyebab
seharusnya
Saklar tekanan tinggi rusak
Pemutusan dalam harness saklar tekanan tinggi
Sambungan konektor saklar tekanan tinggi rusak
Penukar panas unit outdoor kotor
Motor kipas unit outdoor rusak
Kelebihan isi refrigeran
Katup penghenti tidak terbuka
PCB unit outdoor rusak
Pengaturan
Saklar Tekanan
Tinggi
Tabel di bawah ini berisi nilai saklar tekanan tinggi
Model Saklar tekanan tinggi
RZR Terbuka Tertutup
4.0 +0
MPa –0.15 3.0 ± 0.15 MPa
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 106
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Buka katup penghenti.
Hubungkan dengan benar.
Ganti saklar tekanan tinggi dengan tanpa kontinuitas.
Perbaiki tekanan tinggi tersebut.
Ganti saklar tekanan tinggi.
Ganti PCB (A1P) unit outdoor.
CHECK 2 Lihat halaman 141.
Periksa kondisi instalasi.
Matikan catu daya. Tunggu 10 menit setelah kompresor berhenti beroperasi,
kemudian periksa hal-hal berikut
Atur remote kontrol dan hidupkan
lagi.
Apakah katup penghenti terbuka?
YA
TIDAK
Apakah kontrol dan perlindungan saklar tekanan
tinggi terhubung ke PCB Unit outdoor?
TIDAK
YA
Apakah ada kontinuitas dalam kontrol dan
perlindungan saklar tekanan tinggi?
TIDAK
YA
CHECK 2 YA
Apakah kode “H3” ditampilkan?
YA
TIDAK
Apakah ketidaknormalan tekanan tinggi tinggi?
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
107 Service Diagnosis
5.15 Kunci Motor Kompresor
Kode Kesalahan E5
Model yang
berlaku
RZR
Metode deteksi
Kesalahan
Mendeteksi kunci motor saat kompresor dinyalakan.
Kondisi
Putusan
Kesalahan
Jika rotor motor tidak berotasi saat kompresor dinyalakan.
Penyebab
Seharusnya
Kunci kompresor
Awal tekanan diferensial tinggi (2,6 MPa atau lebih)
Pengkabelan UVW tidak benar
PCB unit outdoor rusak
Katup penghenti tidak terbuka
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Buka katup penghenti.
Hubungkan pengkabelan dengan benar.
Perbaiki penyebabnya.
Ganti kompresor.
Ganti PCB unit outdoor.
Ganti kompresor.
Periksa kondisi instalasi.
Apakah katup penghenti terbuka?
YA
TIDAK
Apakah pengkabelan
UVW normal? YA
TIDAK
Apakah tekanan lebih tinggi dari 2.6
MPa pada
permulaan?
YA
Periksa dan lihat apakah kompresor
dihubung singkat atau
dilakukan pembumian.
YA
Apakah tekanan rendah atau tinggi berbeda meski sesaat saat menyalakan
ulang kompresor?
YA
TIDAK
TIDAK
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 108
5.16 Ketidaknormalan Motor Kipas Unit Outdoor
Kode Kesalahan E7
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Ketidaknormalan sistem motor kipas dideteksi sesuai dengan kecepatan kipas yang dideteksi
oleh IC Hall ketika motor kipas berjalan.
Kondisi
Putusan
Kesalahan
Ketika kipas berjalan dengan kecepatan kurang dari salah satu yang ditentukan selama 15
detik atau lebih saat kondisi perjalanan motor kipas terpenuhi
Ketika konektor pendeteksian kecepatan kipas tidak terhubung
Ketika kesalahan dihasilkan 4 kali, sistem dimatikan.
Penyebab
Seharusnya
Motor kipas rusak
Konektor harness antara motor kipas dan PCB yang tersisa, konektornya terputus
atau rusak
Kipas tidak berjalan karena benda asing tersangkut
PCB unit outdoor rusak
Ledakan sekring
Faktor eksternal (Kebisingan, dll.)
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
109 Service Diagnosis
Hilangkan benda asing tersebut.
Lepas konektor motor kipas.
Ganti motor kipas.
Periksa CHECK 4 untuk konektor
motor kipas.
Colokkan konektor motor kipas dengan
benar dan kemudian hidupkan Daya lagi
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Apakah konektor
motor kipas terhubung dengan benar ke PCB
unit outdoor?
TIDAK
Hubungkan dengan benar konektor tersebut.
YA
Apakah ada TIDAK benda asing disekitar
kipas?
YA
Apakah kipas dapat TIDAK
berputar dengan mudah saat diputar dengan tangan?
YA
Apakah nilai hambatan
motor kipas normal?
TIDAK
Ganti motor kipas.
YA
Apakah sekring dengan kontinuitas?
TIDAK Ganti sekring.
YA
Kesalahan ditampilkan lagi. YA
Ganti PCB(A2P) unit outdoor.
CHECK 4
TIDAK
Lihat Halaman 143.
Tidak ada masalah dengan unit.
Faktor eksternal (kebisingan,
dll) selain kegagalan unit
mungkin menjadi penyebab kesalahan tersebut.
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 110
Matikan catu daya sekali dan
kemudian hidupkan lagi.
Apakah kode kesalahan "E9" terulang?
YA
Apakah konektor katup ekspansi elektronik
terhubung dengan benar
ke PCB unit outdoor? (X21A)
YA
Apakah hambatan kumparan katup ekspansi
elektronik normal?
CHECK 11
YA
A
5.17 ketidaknormalan Katup Ekspansi elektronik
Kode Kesalahan E9
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Mendeteksi kesalahan berdasarkan pemeriksaan kontinuitas dari katup ekspansi elektronik.
Mendeteksi kesalahan dengan derajat super panas pipa hisap, derajat super panas pipa
pembuangan dan derajat bukaan katup ekspansi elektronik.
Kondisi
Putusan
Kesalahan
Tidak ada catu daya umum ketika daya diaktifkan
Ketika kondisi berikut ditetapkan
Derajat super panas pipa hisap 4°C derajat
super panas pipa pembuangan 5°C
Derajat bukaan katup ekspansi elektronik derajat bukaan Minimum
Penyebab
Seharusnya
Katup ekspansi elektronik rusak
Katup solenoid rusak
Pemutusan harness katup ekspansi elektronik
Sambungan konektor katup ekspansi elektronik rusak
Setiap termistor rusak
Setiap bantalan termistor rusak
Sensor tekanan rusak
PCB unit outdoor rusak
Operasi basah
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
TIDAK Hubungkan dengan benar.
TIDAK
Ganti kumparan katup ekspansi elektronik.
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
111 Service Diagnosis
Jalankan ulang operasi.
Error is displayed again. YES
A
Apakah masing-masing termistor (pipa hisap, pipa pembuangan,
penukar panas sedang, dan termistor pipa cair) terpasang
dengan benar?
YA
CHECK 1
Apakah karakteristik masing-
masing termistor normal?
TIDAK
Pasang termistor dengan benar .
TIDAK Ganti termistor yang tidak normal.
YA
Sebenarnya, berada dalam operasi basah.
Lihat CHECK 8 untuk menghilangkan
penyebab dari operasi basah.
PCB (A1P)unit outdoor.
Diyakini bahwa faktor (kebisingan, dll,) selain
kegagalan menyebabkan kesalahan.
CHECK 1
CHECK 8
Lihat Hal. 139, 140.
Lihal Hal. 146.
CHECK 11 Lihat Hal.147.
TIDAK
Kesalahan ditampilkan
lagi
YA
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 112
5.18 Ketidaknormalan Suhu pipa Pembuangan
Kode Kesalahan F3
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Ketidaknormalan terdeteksi sesuai dengan suhu yang dideteksi oleh termistor pipa pembuangan.
Kondisi
Putusan
Keslahan
Ketika suhu pipa pembuangan naik ke tingkat tinggi yang tidak normal
Ketika suhu pipa pembuangan naik tiba-tiba
Ketika suhu pipa pembuangan tidak naik setelah operasi dimulai
Penyebab
Seharusnya
Termistor pipa pembuangan rusak
Sambungan termistor pipa pembuangan rusak
Jumlah refrigeran tidak memadai
Kompresor rusak
Pemutusan termistor pipa pembuangan
PCB unit outdoor rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Ketidaknormalan dalam sistem refrigeran seperti kekurangan
refrigeran, kompresor rusak, dll Lakukan inspeksi.
Hubungkan dengan benar, dan operasikan unit lagi.
Pasang termistor, dan operasikan unit lagi.
Catatan:
1. Suhu berbeda tergantung tipe model.
Ganti termistor pipa pembuangan.
Ganti PCB (A1P) unit outdoor
Model Suhu
RZR 115°C
CHECK 1 Lihat Hal. 139, 140.
Apakah suhu pipa pembuangan tinggi?
(1)
TIDAK
YA
Apakah termistor pipa pembuangan dengan benar terhubung ke PCB (A1P)?
TIDAK
YA
Apakah termistor pipa
pembuangan dipasang
ke pipa pembuangan? TIDAK
YA
CHECK 1 Apakah karakteristik
termistor pipa pembuangan
normal?
TIDAK
YA
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
113 Service Diagnosis
Tunggu 10 menit setelah unit berhenti beroperasi, kemudian periksa hal-hal
berikut.
Apakah perlindungan konektor (1) saklar tekanan tinggi dengan benar terhubung ke PCB unit outdoor?
NO
YES
Apakah ada kontinuitas di setiap perlindungan
saklar tekanan tinggi? NO
YES
Apakah ada kontinuitas
dalam kawat timah?
in lead wire?
NO
YES
5.19 Ketidaknormalan Sistem Saklar Tekanan Tinggi
Kode Kesalahan H3
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Sirkuit perangkat perlindungan memeriksa kontinuitas dalam saklar tekanan tinggi.
Kondisi
Putusan
Kesalahan
Ketika tidak ada kontinuitas dalam saklar tekanan tinggi selama kompresor berhenti beroperasi
Penyebab
Seharusnya
Saklar tekanan tinggi yang tidak lengkap
Sambungan konektor saklar tekanan tinggi rusak
PCB unit outdoor rusak
Kawat Timah tidak terhubung
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Hubungkan dengan benar.
Ganti saklar tekanan tinggi
tanpa kontinuitas. Hambatan
dalam operasi normal: 10
atau kurang
Ganti kawat timah.
Ganti PCB unit outdoor.
Catatan:
1. Konektor
Model Konektor
RZR X32A (A1P)
YA
TIDAK
TIDAK
YA
TIDAK
YA
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 114
5.20 Ketidaknormalan Termistor
Kode Kesalahan H9, J3, J5, J6, J7
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Ketidaknormalan terdeteksi sesuai dengan suhu yang dideteksi oleh masing-masing termistor.
Kondisi
Putusan
Kesalahan
Ketika termistor terputus atau korsleting selama operasi
Penyebab
Seharusnya
Termistor rusak
Sambungan konektor rusak
PCB unit outdoor rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Hubungkan konektor dengan benar.
Ganti termistor yang rusak.
Catatan: 1. Konektor termistor
Ganti PCB (A1P) unit outdoor.
Kode Kesalahan Termistor rusak Termistor Konektor
H9 Termistor udara Outdoor R1T X11A
J3 Termistor pipa pembuangan R2T X12A
J5 Termistor pipa hisap R3T X12A
J6 Termistor pipa cair R4T X12A
J7 Termistor penukar panas sedang
R5T X12A
CHECK 1 Lihat Halaman 139, 140.
Periksa konektor untuk koneksi. (1)
Lepas termistor dari PCB unit outdoor, kemudian ukur hambatan
dengan menggunakan penguji.
Normal?
YA
TIDAK
CHECK 1
Normal?
YA
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
115 Service Diagnosis
5.21 Ketidaknormalan Sensor Tekanan
Kode Kesalahan J1
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Kesalahan terdeteksi oleh tekanan yang diukur dengan sensor tekanan
Kondisi
Putusan
Kesalahan
Ketika tekanan terdeteksi sebagai berikut;
Tekanan terdeteksi 4.4 MPa sekitar 185 detik
Penyebab
Seharusnya
Sensor tekanan rusak
PCB unit outdoor rusak
Sambungan konektor tidak benar
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Hubungkan konektor dengan benar.
Ganti sensor tekanan (S1NPH).
Ganti PCB (A1P) unit
outdoor.
CHECK 9 Lihat halaman 147.
CHECK 10 Lihat Halaman 147.
Periksa apakah konektor untuk sensor tekanan (X17A) dengan benar
terhubung ke PCB (A1P) unit outdoor
Ukur tegangan (V) antara pin (1) dan
(3) konektor di atas CHECK 9 .
Apakah terhubung
dengan benar? YA
TIDAK
Apakah hubungan antara
tekanan dan tegangan normal?
CHECK 10
TIDAK
YA
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 116
5.22 Ketidaknormalan PCB Unit Outdoor
Kode Kesalahan L1
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Mendeteksi kesalahan dengan nilai arus selama output bentuk gelombang sebelum pengaktifan kompresor.
Mendeteksi kesalahan dengan nilai sensor arus selama operasi disinkronkan pada waktu pengaktifan
Mendeteksi kesalahan dengan menggunakan sensor tegangan berlebih kapasitor seri MP-PAM.
Kondisi
Putusan
Kesalahan
Ketika arus berlebih terdeteksi pada saat output bentuk gelombang sebelum
mengoperasikan kompresor
Ketika kesalahan sensor arus selama operasi disinkronkan
Ketika tegangan berlebih terjadi di MP-PAM (1)
Dalam hal kesalahan IGBT
Penyebab
seharusnya
Catatan:
PCB (A1P) unit outdoor rusak
Kegagalan IPM (2)
Kegagalan sensor arus
Kegagalan SP-PAM
IGBT (3) atau sirkuit pengerak rusak
Sambungan konektor kompresor rusak
Motor kipas unit outdoor rusak
Sekring rusak
Faktor eksternal (kebisingan, dll.)
1. MP: Multi Pulse (Beberapa pulsa)
2. IPM: IPM adalah perangkat semikonduktor untuk tenaga listrik yang menggabungkan sirkuit
pengerak dan fitur perlindungan diri dari perangkat daya yang mengontrol tenaga listrik.
3. IGBT:IGBT adalah perangkat semikonduktor daya terutama digunakan sebagai saklar
elektronik.
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
117 Service Diagnosis
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Hubungkan dengan erat dan benar.
Ganti motor kipas.
Ganti sekring. Gunakan sekring yang ditentukan saja.
Ganti PCB unit outdoor.
Tidak ada masalah dengan
unit. Faktor eksternal
(kebisingan, dll) selain
kegagalan unit dapat menjadi penyebabnya.
Matikan catu daya sekali.
Periksa nilai hambatan untuk motor
kipas.
Nyalakan lagi.
Apakah kawat timah
untuk kompresor terhubung ke
PCB dan kompresor
tanpa pelepasan yang layak?
YA
TIDAK
Apakah nilai hambatan motor kipas normal?
TIDAK
YA
Apakah sekring memiliki kontinuitas?
YA
TIDAK
Kesalahan ditampilkan lagi. YA
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Service Diagnosis 118
5.23 Suhu Sirip Radiasi Naik
Kode Kesalahan L4
Model yang
berlaku
RZR
Metode deteksi
kesalahan
Suhu sirip radiasi terdeteksi oleh termistor sirip radiasi.
Kondisi
Putusan
Kesalahan
Ketika suhu sirip radiasi inverter meningkat secara tidak normal karena penyebaran panas
rusak
Penyebab
seharusnya
Termistor sirip radiasi rusak
Suhu udara outdoor tinggi
Pembukaan hisap terhalang
Sirip radiasi kotor
PCB unit outdoor rusak
Aktivasi saklar termal sirip
Pendinginan sirip radiasi inverter tidak memadai
Sambungan konektor rusak
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
119 Service Diagnosis
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Hilangkan penyebabnya.
Hubungkan dengan benar.
Masuk ke diagnosis kesalahan "P4".
Ganti PCB unit outdoor.
Catatan: 1. Nilai deteksi sirip radiasi
Lanjutkan operasi.
Model Deteksi Atur ulang
RZR-LUY1(4) 76°C 66°C
Hidupkan catu daya, dan kemudian
tekan tombol periksa remote kontrol
sekali.
Apakah dianggap bahwa suhu sirip radiasi tinggi? (1) YA
Apakah konektor termistor sirip radiasi
dengan benar terpasang
ke PCB unit outdoor?
TIDAK
YA
Apakah kode kesalahan "P4" ditampilkan pada
remote kontrol?
YA
Apakah
kode kesalahan "L4" terulang ketika
operasi awal unit?
YA
TIDAK
TIDAK
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 120
5.24 Arus Lebih Output DC (sesaat)
Kode Kesalahan L5
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Kesalahan terdeteksi dengan mengubah arus yang mengalir ke transistor daya menjadi
tegangan dengan CT1 (sensor arus DC).
Kondisi
Putusan
Kesalahan
Ketika arus berlebih cukup untuk transistor daya.
(Digerakkan juga oleh arus berlebih seketika)
Penyebab
Seharusnya
Kumparan kompresor rusak (pemutusan, isolasi buruk)
Kesalahan pengaktifan kompresor (kunci mekanis)
PCB unit outdoor rusak
Fluktuasi tegangan catu daya Sesaat
Kompresor rusak (Jika bantalan tergores)
Katup penghenti tidak terbuka
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
121 Diagnosis Servis
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Periksa kondisi instalasi.
TIDAK
YA
Buka katup penghenti.
Apakah kumparan
kompresor terputus atau
apakah isolasi rusak?
YA
Ganti kompresor.
TIDAK
Matikan catu daya utama, dan kemudian putuskan sambungan antara
kompresor dan inverter.
CHECK 5 Periksa kontinuitas di transistor daya (IGBT). Apakah kontinuitas
normal?
TIDAK
Ganti PCB unit outdoor.
(A2P)
YA
Apakah tegangan output inverter yang dihasilkan
kira-kira pada kecepatan
kian meningkat yang sama untuk setiap fasa
setelah menyalakan lagi?
(1) (U-V, V-W, W-U)
YA
TIDAK
Ketika mengoperasikan kompresor dengan jalur output kompresor yang
terputus, kompresor berhenti karena
kesalahan setelah lewat waktu 5 detik. Oleh karena itu, periksa
kenaikan tegangan selama 5 detik.
Ganti PCB unit outdoor.
Periksa tegangan catu daya.
Apakah penurunan tegangan sesaat
dihasilkan?
YA Perbaiki catu daya.
TIDAK
Catatan:
1. Nilai perkiraan
inspeksi Kompresor. Inspeksi sesuai dengan prosedur
diagnosis untuk kebisingan,
getaran, status operasi normal, dll dari kompresor.
Model nilai deteksi arus berlebih sesaat
RZR 32.3A
CHECK 5 Lihat Halaman 143.
Apakah katup
penghenti terbuka?
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 122
5.25 Termal Elektronik (Jeda Waktu)
Kode Kesalahan L8
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Kesalahan terdeteksi dengan mengubah arus yang mengalir ke transistor daya menjadi
tegangan dengan menggunakan CT1 (sensor arus DC).
PCB Inverter mendeteksi gangguan sinyal posisi.
Kondisi
Putusan
Kesalahan
Ketika kelebihan beban kompresor (kecuali saat pengaktifan) terdeteksi
Penyebab
Seharusnya
Beban lebih kompresor (selama operasi)
Kumparan kompresor terputus
Kompresor rusak (jika bantalan tergores)
PCB unit outdoor rusak
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
123 Diagnosis Servis
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Beban lebih kompresor.
Pemeriksaan sistem
kompresor dan refrigeran diperlukan.
Ganti PCB unit outdoor. (RZR-
LUY1 (4): A2P)
Ganti PCB unit outdoor. (A2P)
Catatan:
1. Nilai deteksi termal elektronik
Pemeriksaan kompresor. Periksa sesuai dengan prosedur diagnosis untuk
kebisingan, getaran, status
operasi yang tidak normal, dll dari kompresor tersebut.
Model Nilai Deteksi
RZR 17A × 5 detik atau 12.1A × 260 detik
CHECK 5 Lihat halaman 143.
Matikan catu daya utama, dan
kemudian putus sambungan antara
kompresor dan inverter.
Apakah arus sekunder
inverter lebih tinggi dari A
(1) untuk setiap fasa?
YA
CHECK 5
Periksa kontinuitas di transistor daya (IGBT).
Apakah kontinuitas normal?
TIDAK
YA
Apakah
tegangan output inverter yang dihasilkan
kurang lebih pada kecepatan
peningkatan yang sama pada setiap fasa setelah menyalakan
lagi?
() (U-V, V-W, W- U)
YA
TIDAK
Ketika mengoperasikan kompresor
dengan jalur output kompresor yang
terputus, kompresor berhenti karena kesalahan setelah waktu berlalu 5
detik. Oleh karena itu, periksa
kenaikan tegangan selama 5 detik.
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 124
5.26 Pencegahan Stall (Jeda waktu)
Kode Kesalahan L9
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Kesalahan dideteksi dari arus yang mengalir ke transistor daya menjadi tegangan dengan
menggunakan CT1 (sensor arus DC).
PCB Inverter mendeteksi gangguan sinyal posisi.
Kondisi
Putusan
Kesalahan
Ketika beban lebih kompresor dan perubahan beban pada kompresor dideteksi
Penyebab
seharusnya
Katup penghenti tidak terbuka
Pengaktifan diferensial tekanan
PCB unit outdoor rusak
Kompresor rusak (dikunci)
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
125 Diagnosis Servis
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Buka katup penghenti.
Pemerataan tekanan tidak memadai.
Periksa sistem refrigeran.
Ganti PCB unit outdoor. (A2P)
Ganti kompresor.
Pemeriksaan kompresor. Periksa sesuai dengan prosedur diagnosis untuk
kebisingan, getaran, status
operasi yang tidak normal, dll. dari kompresor tersebut.
CHECK 5 Lihat Halaman 143.
Periksa kondisi instalasi
Matikan catu daya utama, dan kemudian putuskan sambungan antara
kompresor dan inverter.
Apakah katup penghenti terbuka?
YA
TIDAK
Apakah perbedaan antara
tekanan tinggi dan rendah sebelum pengaktifan tidak
lebih dari 0.2MPa?
TIDAK
YA
CHECK 5
Periksa kontinuitas di
transistor daya (IGBT).
Apakah kontinuitas normal?
TIDAK
YA
Kompresor dibumikan
dan diputus aliran
listriknya
YA
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 126
5.27 Kesalahan Sistem Transmisi antara PCB Unit Outdoor
Kode Kesalahan LC
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Memeriksa dan melihat apakah transmisi antara PCB unit outdoor dilakukan dengan normal.
Kondisi
Putusan
Kesalahan
Ketika transmisi tidak dilakukan dalam jangka waktu tertentu atau lebih lama
Penyebab
seharusnya
Pengkabelan transmisi antara PCB unit outdoor tidak benar/kontak dalam pengkabelan tidak memadai
PCB unit outdoor rusak
Faktor eksternal (kebisingan, dll.)
Motor kipas unit outdoor rusak
Kontak konektor motor kipas rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Sambungkan konektor tersebut, dan nyalakan lagi.
Ganti motor kipas. transmisi inverter yang
gagal berfungsi karena kesalahan motor kipas.
Ganti PCB (A1P) unit outdoor.
Ganti PCB (A2P) unit
outdoor.
Periksa sambungan konektor yang rusak di pengkabelan transmisi dan untuk klem
dengan jalur tegangan tinggi.
Putuskan konektor motor kipas, dan nyalakan lagi.
Apakah konektor motor
kipas terhubung?
TIDAK
YA
Apakah “E7” yang ditampilkan pada remote
kontrol? (Apakah “LC” tidak ditampilkan?)
YA
Apakah monitor mikro-
komputer (hijau) pada PCB
(A1P) berkedip normal? TIDAK
YA
Apakah monitor
mikro-komputer pada PCB (A2P) berkedip
normal?
YA
TIDAK
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
127 Diagnosis Servis
5.28 Ketidakseimbangan Tegangan Catu Daya atau Fasa Terbuka
Kode Kesalahan P1
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Kesalahan terdeteksi sesuai dengan bentuk gelombang tegangan dari kapasitor sirkuit utama yang dibangun di inverter.
Kondisi
Putusan
Kesalahan
Ketika bentuk gelombang tegangan tersebut menjadi identik dengan bentuk gelombang fasa
terbuka catu daya.
Penyebab
Seharusnya
Fasa terbuka
Ketidakseimbangan tegangan antar fasa
PCB unit outdoor rusak
Kapasitor sirkuit utama rusak
Unit daya (Pemutusan di modul dioda) Relai magnetik rusak
Pengkabelan sirkuit utama tidak benar
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Faktor-faktor lain selain fasa terbuka
Faktor bidang
Faktor bidang
Ganti PCB unit outdoor.
Catatan: Target: ±10V antar fasa, R-S, S-T, T-R
Periksa LED pada PCB unit outdoor (fasa terbuka?)
unit PCB (Open phase?)
TIDAK
Ya
Fasa tegangan catu daya terbuka?
YA
Apakah ketidakseimbangan
antar fasa besar?
YA
TIDAK
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 128
5.29 Ketidaknormalan Termistor Sirip Radiasi
Kode Kesalahan P4
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Deteksi dengan sirkuit terbuka atau hubung singkat termistor sirip radiasi selama kompresor
berhenti beroperasi.
Kondisi
Putusan
Kesalahan
Ketika sirkuit terbuka atau hubung singkat termistor sirip radiasi dideteksi selama kompresor
berhenti beroperasi
Penyebab
Seharusnya Termistor sirip radiasi rusak
PCB unit outdoor rusak
Faktor eksternal (kebisingan, dll.)
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Selidiki faktor-faktor selain kesalahan.
Ganti PCB (A2P) unit outdoor.
Ganti PCB (A2P) unit outdoor.
Catatan: 1. Konektor
Model Termistor Konektor PCB
RZR R10T X111A A2P
CHECK 1 Lihat Halaman 139, 140.
Periksa LED pada PCB unit outdoor.
Lepaskan konektor dari (1) pada PCB, kemudian periksa hambatan
termistor pada suhu normal.
Apakah ada kesalahan
termistor sirip radiasi?
YA
CHECK 1 Normal?
YA
Apakah pengaturan ulang mungkin?
YES
TIDAK
TIDAK
TIDAK
YA
Pengaturan ulang
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
129 Diagnosis Servis
5.30 Ketidaknormalan Pengaturan Kapasitas
Kode Kesalahan PJ
Model yang
berlaku
Metode Deteksi
Kesalahan
Kondisi
Putusan
Kesalahan
Penyebab
Seharusnya
RZR
Memeriksa apakah nilai yang ditetapkan ditulis dalam E2PROM (dari pabriknya) atau nilai
adaptor pengaturan kapasitas yang ditetapkan (untuk penggantian) adalah sama dengan
kapasitas unit outdoor.
Ketika nilai yang ditetapkan pada E2PROM berbeda dari kapasitas unit outdoor atau adaptor
pengaturan kapasitas kecuali untuk PCB model yang berlaku diinstal. (Keputusan Kesalahan
dibuat hanya saat menghidupkan catu daya.)
Nilai E2PROM yang ditetapkan tidak benar
Adaptor pengaturan kapasitas tidak benar
PCB unit outdoor rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Sambungkan adaptor untuk model yang berlaku.
Jika tidak benar,
perbaiki kombinasinya.
Catatan:
1. Adaptor pengaturan kapasitas tidak terhubung dari pabriknya. (Kapasitas ditulis dalam E²PROM.) adaptor
pengaturan kapasitas diperlukan hanya jika PCB digantikan dengan PCB alternatif.
Pastikan bahwa kombinasi adaptor pengaturan kapasitas yang terhubung
benar.
Apakah adaptor pengaturan kapasitas terhubung ke PCB unit
outdoor? (1)
TIDAK
YA
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 130
5.31 Kekurangan Refrigeran
Kode Kesalahan U0
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
(Dalam operasi normal)
Kekurangan Refrigeran dideteksi sesuai dengan derajat bukaan katup ekspansi elektronik
dan suhu dan tekanan yang diukur.
Kondisi
Putusan
Kesalahan
(Dalam Pendinginan)
Ketika katup ekspansi elektronik terbuka sepenuhnya dan tekanan rendah di bawah 0,25 MPa
terus berlanjut selama 30 menit.
Penyebab
Seharusnya
Katup penghenti tidak terbuka
Jumlah refrigeran tidak memadai
Sistem perpipaan refrigeran tersumbat
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Buka katup penghenti.
Catatan:
Alarm kekurangan refrigeran ditunjukkan tetapi operasi terus
berlanjut.
Angkat refrigeran. Setelah pengeringan vakum selesai, isi jumlah refrigerant yang
sesuai.
CHECK 3
Periksa sistem perpipaan refrigeran untuk
penyumbatan.
CHECK 3 Lihat Halaman142.
Apakah katup penghenti terbuka? TIDAK
YA
Apakah jumlah refrigeran sesuai?
TIDAK
YA
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
131 Diagnosis Servis
5.32 Ketidaknormalan Tegangan Catu Daya
Kode Kesalahan U2
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Kesalahan terdeteksi sesuai dengan tegangan kapasitor sirkuit utama yang dibangun pada
tegangan inverter dan catu daya.
Kondisi
Putusan
Kesalahan
Ketika tegangan kapasitor sirkuit utama yang dibangun pada tegangan inverter dan catu daya
turun atau ketika kegagalan daya (listrik padam) beberapa puluh milidetik atau lebih dihasilkan
Remote kontrol tidak menyimpulkan ketidaknormalan tersebut.
Penyebab
Seharusnya
Anjloknya tegangan catu daya
Kegagalan listrik seketika
Pengkabelan sirkuit utama rusak
PCB unit outdoor rusak
Bagian sirkuit utama rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Faktor-faktor lain
Faktor bidang
Perbaiki pengkabelan.
Pantau tegangan tersebut
(penurunan tegangan sesaat)
Ganti PCB (A1P) unit outdoor.
Ketika kompresor berjalan, ukur
tegangan antara + dan - kapasitor
elektrolit (C+, C-).
Periksa LED
pada PCB unit outdoor. (Apakah tegangan tidak memadai?)
TIDAK
YA
Apakah tegangan catu daya antara 380 ~
415V ±10%?
TIDAK
YA Apakah
pengkabelan benar?
YA
TIDAK
Apakah tegangan yang terukur 380 ~ 415V ±10% atau lebih?
TIDAK
YA
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 132
Apakah tegangan catu daya antara 380
- 415V?
YA
Apakah ada tipe kabel yang salah,
terminal longgar, atau kegagalan kontak di
pengkabelan
transmisi antara unit indoor dan outdoor?
YA
Apakah ada aksesori
opsional (1) yang terhubung?
YA
Apakah daya untuk
aksesori opsional dipasok dari antara 1 dan 2 pada
blok terminal X1M atau X2M?
YA
Apakah HAP pada PCB unit outdoor berkedip? (PCB unit
Outdoor)
TIDAK
A
5.33 Kesalahan Transmisi Antara Unit Indoor Dan Unit Outdoor
Kode Kesalahan U4
Model yang
berlaku
RZR
Kesalahan dihasilkan ketika mikro-prosesor mendeteksi bahwa transmisi antara unit indoor
dan outdoor tidak normal selama waktu tertentu.
Kondisi
Putusan
Kesalahan
Ketika transmisi normal tidak dilakukan untuk jangka waktu tertentu atau lebih
Penyebab
Seharusnya
Kabel transmisi (pengkabelan indoor-outdoor) tidak benar
PCB unit indoor rusak
PCB unit outdoor rusak
Sekring habis terbakar
Motor kipas rusak
Faktor eksternal (kebisingan, dll.)
Catu daya rusak
Pemecahan masalah
Diagnosis pengkabelan tidak benar atau rusak/terputus. Jika LED pada PCB unit indoor MATI, menunjukkan
bahwa pengkabelan transmisi antara unit indoor dan outdoor mungkin tidak benar atau rusak / terputus.
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
TIDAK faktor bidang
TIDAK Pasang kabel dengan benar dan aman,
kencangkan sekrup terminal.
TIDAK Pasang kabel dengan benar.
YA S B
Pembangkitan
kesalahan
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
133 Diagnosis Servis
Matikan catu daya dan lepaskan
konektor motor kipas unit outdoor.
Kemudian hidupkan lagi.
Periksa nilai hambatan motor kipas
unit outdoor.
CHECK 13 Periksa tegangan pulsa kecepatan
kipas unit outdoor.
Setelah mematikan catu daya, dengan benar masukkan konektor motor kipas dan
kemudian pulihkan daya.
Setelah mematikan catu daya, dengan benar masukkan konektor motor kipas dan
kemudian pulikan daya.
B
A
YA
( PCB unit Outdoor) Ganti motor kipas unit outdoor.
TIDAK
Apakah nilai
hambatan motor kipas
unit outdoor normal?
TIDAK
Ganti motor kipas unit outdoor.
YA
Apakah sekring memiliki
kontinuitas?
TIDAK Ganti sekring
YA
Apakah tegangan output normal?
TIDAK Ganti PCB unit outdoor.
YA
Apakah kesalahan "U4" YA
terjadi lagi? Ganti PCB unit outdoor.
TIDAK
Apakah kesalahan
"U4" atau "UF" terjadi lagi?
TIDAK
YA
Ganti PCB unit indoor.
Tidak ada masalah dengan unit.
Faktor eksternal (kebisingan,
dll) selain kegagalan unit dapat menjadi penyebabnya.
Catatan: 1. Aksesoris opsional mengacu pada adaptor untuk aksesoris kabel, auto grill dan aksesoris lainnya.
CHECK 13 Lihat Halaman 148.
Apakah HAP berkedip?
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 134
5.34 Kesalahan transmisi antara Unit Indoor dan Remote Kontrol
Kode Kesalahan U5
Model yang
berlaku
Semua model indoor
Kesalahan dihasilkan ketika mikro-prosesor mendeteksi bahwa transmisi antara unit indoor
dan remote kontrol tidak normal selama waktu tertentu.
Penyebab
seharusnya Remote kontrol rusak
PCB unit indoor rusak
Faktor eksternal (kebisingan, dll.)
Koneksi 2 remote kontrol utama (ketika menggunakan 2 remote kontrol).
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Atur salah satu remote kontrol ke SUB, matikan catu daya
sementara, kemudian nyalakan
kembali operasi.
Ganti PCB unit indoor.
Kesalahan dapat dibangkitkan oleh
kebisingan. Periksa daerah sekitarnya dan
nyalakan ulang operasi.
Ubah ke kabel independen dua
inti.
Kegagalan PCB remote kontrol atau ganti PCB unit indoor yang
rusak.
Masalah dapat disebabkan oleh faktor eksternal (kebisingan, dll) selain kesalahan.
Kontrol dengan 2 remote kontrol
YA
SS1 kedua
remote kontrol diatur ke MAIN.
TIDAK
YA
Semua lampu kedip PCB unit indoor,
mikro-komputer, monitor normal
T
YA
Menggunakan kabel transmisi multi-core
antara unit indoor dan remote kontrol
TIDAK
YA
Apakah "U5" ditampilkan
terus-menerus? YA
TIDAK
IDAK
Atur ulang seperti biasa ketika catu daya dimatikan
sementara.
TIDAK
YA
Pembangkitan
Kesalahan
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
135 Diagnosis Servis
5.35 Kesalahan Transmisi antara Remote Kontrol MAIN dan Remote Kontrol SUB
Kode Kesalahan U8
Model yang
berlaku
Semua model indoor
Kesalahan dihasilkan ketika, dalam kasus mengontrol dengan menggunakan 2 remote
kontrol, mikro prosesor mendeteksi bahwa transmisi antara unit indoor dan remote kontrol
(MAIN dan SUB) tidak normal selama waktu tertentu.
Penyebab
seharusnya Kesalahan Transmisi antara remote kontrol MAIN dan remote kontrol SUB
Koneksi antara remote kontrol SUB
PCB remote kontrol rusak.
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Ubah saklar SS-1 dari salah satu remote kontrol ke
MAIN. Matikan catu daya, dan hidupkan
ulang operasi.
Matikan daya sekali dan nyalakan ulang operasi.
Ganti PCB remote kontrol jika ada kesalahan dihasilkan.
Ganti kabel remote kontrol.
Ubah saklar SS-1 dari salah satu remote kontrol ke MAIN.
Matikan catu daya, dan nyalakan ulang operasi.
Mengontrol dengan 2 remote kontrol
TIDAK
YA
Saklar SS-1 pada PCB remote kontrol diubah ke
MAIN.
YA
TIDAK
Kedua saklar SS-1 pada remote kontrol
diubah ke SUB.
YA
Apakah ada kontinuitas di
pengkabelan remote
kontrol?
Y YA
TIDAK
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 136
5.36 Ketidaknormalan Saklar Pengaturan Bidang
Kode Kesalahan UA
Model yang
berlaku
Semua model indoor
Kesalahan dihasilkan ketika pengaturan bidang yang tidak benar telah ditetapkan untuk pair /
twin / triple / double twin.
Penyebab
seharusnya PCB unit indoor atau outdoor rusak
PCB catu daya rusak
Pengkabelan transmisi unit Indoor-outdoor, indoor-indoor
Pengkabelan remote kontrol rusak.
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat
rusak.
Hubungkan remote kontrol dengan benar.
Atur ke Pair dengan benar.
Hubungkan dengan benar.
Hubungkan dengan benar.
Ganti transformer.
Pengkabelan bisa salah,
periksa kembali.
Hubungkan dengan benar.
Ganti PCB unit indoor.
Beroperasi secara normal.
Matikan daya sekali, kemudian hidupkan
ulang, dan memulai ulang operasi.
Apakah remote kontrol terhubung ke unit
indoor lebih dari 1?
YA
Apakah pengaturan dari Pair/Twin/Triple
diatur dengan benar?
YA
TIDAK
Apakah monitor mikro-komputer (HAP) dari semua
PCB unit indoor berkedip normal?
YA
T
beroperasi secara normal? TIDAK Apakah jumper indoor-
indoor dan indoor-outdoor dengan benar terhubung?
TIDAK
YA
YA
IDAK Apakah jumper indoor-indoor dan indoor-outdoor dengan benar terhubung?
TIDAK
YA
Apakah PCB catu daya dengan benar terhubung?
TIDAK
YA
Apakah VAC 220-240 antara No.1 dan No.3 dari
X2M (Unit indoor)?
TIDAK
YA
Pembangkitan
Kesalahan
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
137 Diagnosis Servis
5.37 Kesalahan Pengaturan Alamat Terpusat
Kode Kesalahan UC
Model yang
berlaku
Semua model indoor
Metode Deteksi
Kesalahan
Mikro-komputer unit indoor mendeteksi dan menilai sinyal alamat terpusat sesuai dengan
transmisi antara unit indoor.
Kondisi
Putusan
kesalahan
Ketika mikro-komputer menilai sinyal alamat terpusat diduplikasi
Penyebab
seharusnya
Pengaturan alamat terpusat rusak
PCB unit indoor rusak
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau kerusakan bagian dapat terjadi.
Ubah pengaturan sehingga alamat terpusat tidak
diduplikasi.
Ganti PCB unit indoor.
Apakah perangkat yang terkait dengan kontrol terpusat terhubung ke unit indoor?
YA
TIDAK
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 138
5.38 Kesalahan Transmisi antara Unit Indoor dan Outdoor / Perpipaan dan Ketidakcocokan Pengkabelan / Kekurangan Refrigeran
Kode Kesalahan UF
Model yang
berlaku
RZR
Metode Deteksi
Kesalahan
Memeriksa transmisi antara unit indoor dan outdoor dengan mikro-komputer ketika daya
DIHIDUPKAN.
Mendeteksi dengan memeriksa perbedaan suhu berikut selama operasi kompresor.
A: Perbedaan suhu yang dideteksi oleh termistor (R2T) pipa cair penukar panas indoor
dan termistor (R1T) udara hisap indoor
B: Perbedaan suhu uap (Te) yang dideteksi oleh termistor (R2T) pipa cair penukar panas
indoor dan sensor kompresor
Kondisi
Putusan
kesalahan
Ketika kabel transmisi antara unit indoor dan outdoor tidak benar
Ketika kondisi berikut terus berlanjut selama 20 menit selama operasi kompresor
A: R2T – R1T < 4ºC, dan
B: R2T – Te > 14ºC
Penyebab
Seharusnya
Pengkabelan transmisi antara unit indoor dan outdoor rusak
Ketidakcocokan pengkabelan dan pemipaan
Kekurangan refrigeran
Sistem pemipaan refrigeran tersumbat
Pemecahan masalah
Perhatian Pastikan untuk mematikan saklar daya sebelum menghubungkan atau mencabut konektor, atau bagian dapat rusak.
Dengan benar hubungkan
kabel transmisi antara unit indoor dan outdoor.
Cocokkan sambungan kabel dan pipa transmisi antara unit indoor
dan outdoor.
Isi ulang jumlah refrigeran yang sesuai setelah
pemulihan refrigeran dan
pengeringan vakum.
CHECK 3
Periksa sistem pemipaan refrigeran untuk
penyumbatan.
CHECK 3
CHECK 6
Lihat halaman 142.
Lihat halaman 144.
Tahap pengkabelan transmisi antara
unit indoor dan outdoor tidak benar.
Apakah "UF" muncul ketika daya dihidupkan? YA
Apakah sambungan kabel dan pipa transmisi antara unit indoor dan outdoor
cocok? TIDAK
YA
CHECK 6
Apakah tingkat
refrigeran sesuai?
TIDAK
YA
TIDAK
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
139 Diagnosis Servis
5.39 Pemeriksaan
CHECK 1 Periksa termistor
Termistor
Jika penyebab masalah adalah terkait dengan termistor, maka termistor harus diperiksa sebelum
mengubah PCB.
Untuk informasi lebih lanjut tentang termistor ini, lihat:
“Diagram Pengkabelan’’ di Halaman 150
“Fungsi Komponen Utama dan termistor” di Halaman 25.
Gambaran Umum tentang Termistor
Tabel di bawah ini berisi gambaran umum tentang termistor:
Indoor
FBQ-E Termistor Tabel (di halaman berikut)
R1T Termistor udara hisap 2
R2T Termistor pipa cair penukar panas Indoor 2
R3T Termistor penukar panas Indoor thermistor 3
Outdoor
RZR-LUY1(4) Termistor Tabel
(di halaman berikut)
R1T Termistor udara Outdoor 2
R2T Termistor pipa pembuangan 3
R3T Termistor pipa hisap 2
R4T Termistor pipa cair 2
R5T Termistor penukar panas sedang 2
R10T Termistor sirip radiasi 1
Pemeriksaan
Untuk memeriksa termistor, lakukan sebagai berikut:
Langkah Tindakan
1 Lepaskan thermistor dari PCB
2 Baca suhu dan nilai resistor.
3 Periksa apakah nilai yang diukur sesuai dengan nilai-nilai dalam tabel di halaman berikutnya.
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 140
Karakteristik Suhu / Tahanan Termistor
Tabel 1 Tabel 2 Tabel 3
T°C k
-30 361.7719
-25 265.4704
-20 196.9198
-15 147.5687
-10 111.6578
-5 85.2610
0 65.6705
5 50.9947
10 39.9149
15 31.4796
20 25.0060
25 20.0000
30 16.1008
35 13.0426
40 10.6281
45 8.7097
50 7.1764
55 5.9407
60 4.9439
65 4.1352
70 3.4757
75 2.9349
80 2.4894
85 2.1205
90 1.8138
95 1.5575
100 1.3425
105 1.1614
3SA48001 (AD87A001J)
3PA61998L (AD92A057)
3SA48006 (AD87A001J)
T°C k
-30 354.1
-25 259.7
-20 192.6
-15 144.2
-10 109.1
-5 83.25
0 64.10
5 49.70
10 38.85
15 30.61
20 24.29
25 19.41
30 15.61
35 12.64
40 10.30
45 8.439
50 6.954
55 5.761
60 4.797
65 4.014
70 3.375
75 2.851
80 2.418
85 2.060
90 1.762
95 1.513
100 1.304
105 1.128
110 0.9790
115 0.8527
120 0.7450
125 0.6530
130 0.5741
T°C k
-30 3257.371
-25 2429.222
-20 1827.883
-15 1387.099
-10 1061.098
-5 817.9329
0 635.0831
5 496.5712
10 391.0070
15 309.9511
20 247.2696
25 198.4674
30 160.2244
35 130.0697
40 106.1517
45 87.0725
50 71.7703
55 59.4735
60 49.5180
65 41.4168
70 34.7923
75 29.3499
80 24.8586
85 21.1360
90 18.0377
95 15.4487
100 13.2768
105 11.4395
110 9.8902
115 8.5788
120 7.4650
125 6.5156
130 5.7038
135 5.0073
140 4.4080
145 3.8907
150 3.4429
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
141 Diagnosis Servis
CHECK 2 Evaluasi Tekanan Tinggi yang tidak normal
Tidak normalnya tingkat tekanan tinggi sebagian besar terjadi di sisi kondensor. Isi berikut disediakan oleh
insinyur servis berdasarkan pemeriksaan bidang miliknya.
Dalam pendinginan
Periksa item (Kemungkinan penyebab) Penilaian
Apakah kipas unit outdoor berjalan dengan normal? Inspeksi visual
Apakah penukar panas unit outdoor tersumbat? Inspeksi visual
Apakah ada penyumbatan sebelum atau sesudah katup ekspansi elektronik?
Periksa apakah ada perbedaan suhu sebelum dan sesudah katup ekspansi elektronik. Periksa apakah unit katup utama dari katup ekspansi elektronik beroperasi (dengan kebisingan, getaran).
Apakah katup balik tersumbat? Periksa apakah ada perbedaan suhu sebelum dan sesudah katup balik. Jika YA, katup balik terperangkap.
Apakah saklar tekanan tinggi normal? Periksa kontinuitas dengan menggunakan penguji.
Apakah unit outdoor dipasang di bawah kondisi seperti itu sehingga arus pendek mudah terjadi?
Inspeksi visual
Apakah panjang pipa 5 m atau kurang? Inspeksi visual
Apakah udara memasuki sistem refrigeran? Lakukan koleksi refrigeran dan pengeringan vakum, dan kemudian tambahkan jumlah refrigeran yang tepat.
Apakah refrigeran diisi berlebihan? Lakukan koleksi refrigeran dan pengeringan vakum, dan kemudian tambahkan jumlah refrigeran yang tepat.
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 142
CHECK 3 Titik tersumbat
Perbedaan suhu dapat terjadi sebelum atau sesudah titik tersumbat!
Titik pemeriksaan Faktor pemeriksaan Penyebab Perbaikan
1 Sekitar mekanisme ekspansi
Perbedaan suhu
Debu Uap lembap tersumbat Diameter pipa efektif
berkurang karena kontaminasi zat perekat, dll.
Ganti katup ekspansi elektronik.
2 Aki Pembekuan Uap lembap tersumbat
Tiupkan gas nitrogen, dan kemudian ganti refrigeran.
3 Penyalur Perbedaan suhu Debu Uap lembap tersumbat Diameter pipa efektif
berkurang karena kontaminasi zat perekat, dll.
Ganti penyalur atau penukar panas.
4 Pemipaan bidang Perbedaan suhu Pipa runtuh Ganti pipa.
5 Katup penghenti
Perbedaan suhu
Katup penghenti tidak sepenuhnya terbuka.
Buka katup penghenti sepenuhnya.
4
1
3 3
5
2
ACC COM P
Unit Indoor Unit Outdoor
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
143 Diagnosis Servis
CHECK 4 Jalur Sinyal Motor Kipas
Ukur setiap hambatan antar pin dua kali saat konektor kipas motor tidak terhubung dan periksa apakah sama
atau lebih tinggi dari nilai pada tabel berikut. Tukar bar penguji (merah /hitam) antara pengukuran pertama
dan kedua.
1 Putih
2 Oranye
3 Coklat
4 Biru
5
6
7 Merah
FG
Vsp
Vcc
GND
–
–
Vdc
CHECK 5 Periksa Transistor Daya
Penilaian sesuai dengan pemeriksaan kontinuitas dengan menggunakan penguji analog:
(1) Jangan Sentuh bidang bermuatan (tegangan tinggi) selama 10 menit setelah mematikan catu daya.
(2) Jika anda harus menyentuh bidang tersebut, pastikan bahwa tegangan catu daya dari transistor
daya adalah 50 V atau kurang.
(3) Lepaskan konektor motor kipas unit outdoor.
Ketika kipas unit outdoor berputar melawan angin kencang, kondensor bermuatan dan sengatan listrik
bisa terjadi. Oleh karena itu, lepaskan konektor dari motor kipas unit outdoor setelah mengkonfirmasi
bahwa kipas unit outdoor telah berhenti.
(4) Sebelum mengukur kontinuitas, putuskan koneksi antara kompresor dan transistor daya.
(5) Ukur kontinuitas dalam prosedur berikut.
[Penilaian] Normal jika hasil pemeriksaan kontinuitas sebagai serikut.
Transistor daya (pada PCB)
C+— U
C+— V
C+— W
Kontinuitas
Kontinuitas
Kontinuitas
C- — U
C- — V
C- — W
U — C+ U — C- Kontinuitas
V — C+
W — C+
V — C-
W — C-
Kontinuitas
Kontinuitas
Catatan:
Jika ada kontinuitas, hambatan harus sama dengan setiap fasa.
Jika penguji digital digunakan untuk pengukuran kontinuitas, dan kontinuitas dapat dibalik.
Standar penilaian
Kedua nilai pengukuran pertama dan kedua sama dengan atau lebih tinggi
dari 1.
Pengukuran pertama
Penguji Hambatan
Merah Hitam
FG GND Vsp GND Vcc GND Vdc GND
Pengukuran kedua
Penguji Hambatan
Merah Hitam
GND FG GND Vsp GND Vcc GND Vdc
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 144
CHECK 6 Memeriksa Refrigeran yang tidak memadai
Sebagai kriteria untuk menilai apakah refrigeran memadai atau tidak, lihat pada kondisi operasi berikut.
< Diagnosis refrigeran tidak memadai >
Dalam pendinginan
(1) Ketika derajat super panas hisap meningkat karena kekurangan refrigeran, katup ekspansi
elektronik cenderung terbuka (terbuka penuh) untuk menghindari operasi panas yang berlebihan.
(2) Sebagai respon terhadap kapasitas evaporator berkurang yang disebabkan oleh kekurangan
refrigeran, kapasitas dikendalikan di inverter untuk menjaga tekanan rendah, yang berakibat pada
penurunan frekuensi.
(3) Karena (1) dan (2) di atas, frekuensi kompresor menurun meskipun perbedaan besar (beban besar)
antara suhu yang ditetapkan oleh remote kontrol dan suhu udara hisap indoor, mengakibatkan
kapasitas pendinginan menjadi tidak tersedia.
(4) Jika kekurangan refrigeran menjadi lebih buruk, katup ekspansi elektronik tetap terbuka penuh dan
derajat super panas hisap selanjutnya meningkat. Selain itu, karena frekuensi kompresor turun ke
tingkat frekuensi terendah (52 Hz) dan laju aliran refrigeran menurun, tekanan rendah tidak dapat
dipertahankan.
Pendinginan Peringatan kekurangan refri geran
kek u ra n g a n refr i ge ra n
ya n g ti d ak no rma l
Tekanan tinggi (Termistor penukar panas sedang)
Karena frekuensi kompresor turun, tekanan tinggi turun.
tekanan tinggi yang sebenarnya
Tekanan rendah
(Mempertahankan tingkat tertentu tekanan rendah) )
Ketika laju aliran refrigeran turun, mustahil untuk mempertahankan tekanan rendah.
Karena derajat bukaan katup ekspansi elektronik mencapai maksimum, derajat super panas isapan meningkat.
Derajat super panas isapan
Frekuensi kompresor
Sebagai respon terhadap kapasitas evaporator berkurang yang disebabkan oleh kekurangan refrigeran, kapasitas dikendalikan di inverter dalam rangka untuk mempertahankan tekanan
rendah, yang mengakibatkan penurunan frekuensi.
Mencapai frekuensi terendah
Derajat bukaan maksimum katup ekspansi elektronik (480 pulsa)
Hindari operasi panas yang berlebihan dengan mengubah nilai target SH
Katup ekspansi elektronik
(Derajat refrigeran yang tidak memadai)
tingkat yang memadai tidak memadai
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
145 Diagnosis Servis
CHECK 7 Periksa Pengisian Refrigeran yang berlebihan
Sebagai kriteria untuk menilai apakah refrigeran secara berlebihan diisikan atau tidak, Lihat kondisi operasi
berikut.
< Diagnosis pengisian refrigeran yang berlebihan >
Dalam Pendinginan
(1) Sebab tekanan tinggi naik karena pengisian yang berlebihan, kontrol yang berlebihan dilakukan dan
kapasitas cenderung berjalan secara singkat.
(2) Dengan mempertimbangkan beban tekanan, suhu pipa pembuangan kompresor rendah.
Pendinginan
Tekanan Tinggi (termistor penukar panas sedang)
Tekanan rendah
Karena frekuensi kompresor turun, tekanan rendah naik.
Frekuensi kompresor
Frekuensi
kompresor
Katup ekspansi
elektronik
Frekuensi maksimum
Frekuensi kompresor meningkat dalam rangka untuk mempertahankan tekanan rendah.
turun karena kontrol perlindungan tekanan tinggi
Frekuensi minimum
derajat bukaan katup elektronik menurun karena kontrol perlindungan basah
Derajat bukaan minimum
Derajat super panas
hisap
Derajat super panas pembuangan
derajat super panas hisap adalah sekitar. 0 derajat.
tingkat yang memadai
(Derajat pengisian refrigeran yang berlebihan)
Isi yang berlebihan
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 146
Defective valve coil
Defective valve body
Tempat Kompresor sering memulai dan berhenti refrigeran
Wet operation
Kapasitas penguapan
berkurang
Dirty evaporator
Decreased
fan airflow rate
CHECK 8 Periksa Faktor yang menyebabkan Operasi basah
Mengacu pada Fault Tree Analysis (FTA) yang ditunjukkan di bawah ini, mengidentifikasikan titik-titik yang rusak.
Lihat CHECK 7 .
Apakah hambatan
kumparan dan isolasi normal?
Sensor tekanan rendah rusa k
Termistor pipa hisap rusak PCB
unit outdoor rusak
Apakah karakteristik tegangan normal?
Apakah konektor dengan tepat terhubung?
Apakah karakteristik resistansi termistor normal? Apakah nilai tekanan yang diperiksa dengan Service Checker sesuai dengan pengukuran sensor?
Apakah penukar panas tersumbat?
output
kipas turun
Motor kipas rusak
PCB unit outdoor rusak (termasuk pengaturan
kapasitas)
Apakah motor kipas
bisa diputar menggunakan tangan?
Apakah hambatan
kumparan motor dan
isolasi normal?
Catatan:
Nilai referensi untuk derajat super panas yang akan digunakan dalam penilaian operasi basah
(1) Derajat super panas pipa hisap: 4°C atau lebih
(2) Derajat super panas pipa pembuangan: 5°C atau kurang
(Nilai-nilai di atas harus digunakan hanya untuk tujuan referensi. Bahkan dioperasikan dalam kisaran di
atas, operasi mungkin normal dalam kondisi lain.)
pengisian refrigeran yang berlebihan
Katup ekspansi
elektronik rusak
Kontrol derajat super
panas rus ak
Kontrol rusak
Operasi basah
Kumparan katup rusak
Bodi katup rusak
Evaporator kotor
Laju aliran udara
kipas turun
SiMT281515E Pemecahan masalah dengan Indikasi pada Remote Kontrol
147 Diagnosis Servis
CHECK 9 Titik Pengukuran Tegangan
CHECK 10 “Sensor tekanan”, Grafik Karakteristik Tekanan / Tegangan.
PH (MPa) =
4.15 × VH –
4.15 × 0.5
3.0 2.5
3.0
2.0
1.5
1.0
0.5
0
–0.5 –0.5 0
0.5 1
1.5 2
2.5 3
3.5 4 Tegangan Output VH (VDC)
CHECK 11 Kriteria Hambatan Kumparan dan Konektor Katup Ekspansi
(Jingga) 1
(Merah) 2
(Kuning) 3
(Hitam) 4
(abu-abu) 5
(Putih) 6
Kriteria
40 - 50
RZR100/125/140
PCB (A1P) unit Outdoor
+5V
(Merah)
GND
Merah
Hitam
input A/D Mikro-komputer
Putih
Ukur tegangan DC di sini.
Te
ka
na
n t
erd
ete
ksi
PH
(M
Pa)
se
ns
or
tek
an
an
3.0
PH
Titik Pengukuran
1 - 5
3 - 5
2 - 6
4 - 6
Pemecahan masalah dengan Indikasi pada Remote Kontrol SiMT281515E
Diagnosis Servis 148
CHECK 13 Pulsa Kecepatan Kipas
(1) Atur operasi OFF dan daya OFF. Lepaskan konektor (1).
(2) Periksa tegangan antara pin 3 - 4 adalah sekitar 15 VDC.
(3) Periksa tegangan antara pin 1 - 4 adalah sekitar 5 VDC.
(4) Jaga operasi tetap OFF dan daya OFF. Sambungkan konektor (1).
(5) Periksa apakah 2 pulsa (0 dan 5 VDC) adalah output 4 kali di pin 1 - 4 ketika motor kipas diputar 1 putaran
dengan tangan.
Periksa Ukur
Jika NG di langkah 2 dan 3 PCB yang rusak Ganti PCB unit outdoor.
Jika NG di langkah 5 IC Hall yang rusak Ganti motor kipas unit outdoor.
Jika OK di langkah 2, 3 dan 5 Ganti PCB unit outdoor.
PCB
Input pulsa perintah rotasi (0 dan5 VDC) 0
VDC
15 VDC
250~320 VDC
Catatan:
1. Konektor dan PCB unit outdoor
Model Konektor untuk motor kipas (1) PCB
RZR-LUY1 (4) X106A, X107A A2P
(1)
1
2
3
4
5
6
7
SiMT281515E
149 Lampiran
Bagian 7
Lampiran
1. Diagram Pengkabelan ........................................................................... 150 1.1 Unit Indoor .................................................................................. 150
1.2 Unit Outdoor ............................................................................... 151
SiMT281515E Diagram Pengkabelan
Appendix 150
1. Diagram Pengkabelan
1.1 Unit Indoor FBQ60EVE(4) / FBQ71EVE(4) / FBQ100EVE(4) / FBQ125EVE(4) / FBQ140EVE(4)
3D
092
733A
SiMT281515E
151 Lampiran
1.2 Unit Outdoor RZR100LUY1(4) / RZR125LUY1(4) / RZR140LUY1(4)
3D
079
826C
Appendix 152
Diagram Pengkabelan SiMT281515E
Riwayat Revisi
Bulan / Tahun Versi Isi yang direvisi
09 / 2015 SiMT281515E Edisi pertama
Peringatan Produk Daikin diproduksi untuk ekspor ke berbagai negara di seluruh dunia. Sebelum membeli,
harap konfirmasikan dengan importir, distributor dan / atau pengecer resmi setempat apakah produk
ini sesuai dengan standar yang berlaku, dan cocok untuk digunakan, di daerah di mana produk akan
digunakan. Pernyataan ini tidak dimaksudkan untuk mengecualikan, membatasi atau memodifikasi
aplikasi dari setiap peraturan setempat.
Ajukan installer atau kontraktor yang memenuhi syarat untuk memasang produk ini. Jangan
mencoba untuk memasang produk ini sendiri. instalasi yang tidak tepat dapat mengakibatkan
kebocoran air atau refrigeran, sengatan listrik, kebakaran atau ledakan.
Gunakan hanya komponen dan aksesori yang disediakan atau yang ditentukan oleh Daikin.
Minta installer atau kontraktor yang memenuhi syarat untuk memasang komponen dan aksesori
tersebut. Penggunaan komponen dan aksesori yang tidak resmi atau instalasi komponen dan
aksesori yang tidak tepat dapat mengakibatkan kebocoran air atau refrigeran, sengatan listrik,
kebakaran atau ledakan.
Baca panduan pengguna dengan seksama sebelum menggunakan produk ini. panduan
pengguna memberikan petunjuk keselamatan dan peringatan penting. Pastikan untuk mengikuti
petunjuk dan peringatan ini.
Jika Anda memiliki pertanyaan, silahkan hubungi importir, distributor dan / atau pengecer setempat.
Perhatian terhadap korosi produk
1. Pendingin ruangan sebaiknya tidak dipasang di daerah di mana gas korosif, seperti gas asam atau gas alkali, dihasilkan. 2. Jika unit outdoor akan dipasang dekat dengan tepi laut, paparan langsung angin laut harus dihindari. Jika Anda perlu
memasang unit outdoor dekat dengan tepi laut, hubungi distributor setempat.
Spesifikasi, desain dan konten lainnya yang muncul dalam brosur ini berlaku sejak September 2015 namun dapat berubah tanpa pember itahuan. SiMT281515E
09/2015 AK.K