fire suppression system
Post on 30-Jan-2016
310 Views
Preview:
DESCRIPTION
TRANSCRIPT
FIRE SUPPRESSION SYSTEMINDOLOK BAKTI UTAMA, PT – Business Area System5 February 2013
22 April 2023, page 2
Api dapat terjadi dikarenakan adanya tiga unsur yang berhubungan yang
dikenal dengan istilah “TRIANGLE OF FIRE /SEGITIGA API”, tiga unsur
tersebut adalah :
1. Unsur Oksigen
2. Unsur Bahan bakar / Combustible material
3. Unsur Panas / Heat
Proses pemadaman api dapat dilakukan dengan menghilangkan atau
memisahkan paling sedikit salah satu dari 3 unsur tersebut, salah satu
caranya dengan menggunakan gas bertekanan.
INTRODUCTION
22 April 2023, page 3
THREE ANGEL OF FIRE
TRIANGLE OF FIRE
Api akan timbul ketika bahan bakar, oxidizer dan sumber api sudah menyatu atau tercampur pada tingkat tertentu.
Bahan bakar Padat : plastik, serbuk kayu, fiber, partikel logam Cair : bensin, aseton, eter, pentana Gas : asitilen, propana, metana, karbon monoksida, hidrogen
Oxidizer Padat : metal peroksida, amonium nitrit. Cair : hidrogen peroksida, asam nitrat, asam perklorat Gas : oksigen, flourine, klor, flour
Sumber api Korek api, listrik statis, puntung rokok,dll
22 April 2023, page 4
THREE ANGEL OF FIRE
FIRE SUPPRESSION SYSTEM
Merupakan System Pemadaman Kebakaran Otomatis dengan
menggunakan media Gas atau bahan kimia untuk memadamkan api.
Ada beberapa sistem pemadaman api dengan menggunakan gas
bertekanan sebagai media untuk proses pemadaman api, diantaranya :
1. FM200 System HFC-227ea
2. Argonite System IG-55 (50% Argon / 50% Nitrogen)
3. CO2 System
4. NOVEC 1230 FK 5-1-12 / C6F12O
22 April 2023, page 5
FM200 SYSTEM FLOWCHART
22 April 2023, page 6
Sistem dapat dioperasikan secara otomatis dan manual. System berjalan secara otomatis selama 24 jam.
Dengan Pengoperasian secara otomatis biasanya akan menimbulkan kejadian-kejadian dibawah ini:
Bila rangkaian Zone Detector 1 & 2 dalam kondisi alarm (maka alarm bell dan multi alert akan berbunyi).
Tegangan output akan bekerja, mengaktifkan electric actuator, sehingga valve ditabung akan terbuka, maka gas akan keluar didalam ruang yang diproteksi.
Jika Detector yang didalam ruangan tidak berfungsi, sedangkan didalam ruang tersebut terjadi sumber kebakaran, maka untuk mengeluarkan Gas dapat dilakukan dengan mengaktifkan tombol “ Manual Release”.
Setelah Gas keluar maka lampu DNE diatas ruangan akan menyala.
Selama Gas terpancar, jangan membuka ruangan tersebut sampai Gas habis.
HOW THE SYSTEM WORK?
22 April 2023, page 7
Pengoperasian secara manual, dilakukan bila listrik PLN atau panel tidak berfungsi, maka harus mengikuti langkah dibawah ini:
Ketahui dengan pasti ruangan yang terjadi kebakaran.
Tentukan tabung yang berhubungan dengan ruangan yang terjadi kebakaran
Pastikan ruangan tertutup rapat
Kemudian tarik “ pin pengaman “ dan tekan tuas (lever actuator) yang terdapat pada tabung.
HOW THE SYSTEM WORK?
22 April 2023, page 8
HOW THE SYSTEM WORK?
Input
Photo Smoke Detector
Ion Smoke Detector
MCFAA
Output
Strobe Lamp + Bell Alarm
Manual Release &
Abort switch
Input
Gas FM 200 discharge to Room
FM 200 Activated
Output
Fire SuppressedSmoke cause from fire
22 April 2023, page 9
WIRING INSTALLATION (Conventional)
Zone 1
Zone 2
Alarm
220VAC
Manual Release
Abort
Horn&Strobe
22 April 2023, page 10
WIRING INSTALLATION (Conventional/Zone 1 Active)
Zone 1
Zone 2
Alarm
220VAC
Manual Release
Abort
Horn&Strobe
22 April 2023, page 11
WIRING INSTALLATION (Conventional/Zone 2 Active)
Zone 1
Zone 2
Alarm
220VAC
Manual Release
Abort
Horn&Strobe
22 April 2023, page 12
WIRING INSTALLATION (Conventional/Cross Zones)
Zone 1
Zone 2
Alarm
220VAC
Manual Release
Abort
Horn&Strobe
FM200
22 April 2023, page 13
WIRING INSTALLATION (Conventional/Manual Release)
Zone 1
Zone 2
Alarm
220VAC
Manual Release
Abort
Horn&Strobe
FM200
22 April 2023, page 14
WIRING INSTALLATION (Addressable)
Zone 1 Zone 2
Alarm
220VAC
Horn&Strobe
Manual Release
AbortOutputMod
OutputMod
OutputMod
OutputMod
InputMod
InputMod
22 April 2023, page 15
Fire System Application Area
SYSTEM
AREA FIRE ALARM
SYSTEMGAS
DETECTIONNovec 1230
/FM 200 CO2/Inert gasHydrant System
Sprinkler System
Waterspray System
Foam System
Fire Extinquisher
OFFICE/ADMIN Building yes n/a yes n/a yes yes n/a n/a yesPower House yes yes n/a yes yes n/a yes n/a yesFactory Plant yes n/a n/a n/a yes n/a n/a yes yesWarehouse yes n/a n/a n/a yes yes n/a n/a yesFuel Tank Area yes n/a n/a n/a yes n/a yes yes yesBoiler Area yes yes n/a n/a yes n/a yes yes yesPower Plant yes yes n/a yes yes yes yes n/a yesMCC Panel Room yes n/a yes n/a yes n/a n/a n/a yesLaboratories yes yes/no yes n/a yes yes n/a n/a yesJetty Area yes n/a n/a n/a yes n/a n/a n/a yesConveyor yes n/a n/a n/a yes yes n/a n/a yesYard area yes n/a n/a n/a yes n/a n/a n/a n/aControl Room yes n/a yes n/a n/a n/a n/a n/a yesTransformer Area yes n/a n/a n/a yes n/a yes n/a yesFurnace yes yes n/a n/a yes n/a yes n/a yes
FIRE FIGTHING SYSTEMFIRE DETECTION SYSTEM FIRE SUPPRESSION SYSTEM
FM200 SYSTEMINDOLOK BAKTI UTAMA, PT – Business Area System2 May 2012
22 April 2023, page 17
In today’s global business environment, the need for clean agent fire suppression has never been greater.
INTRODUCTION
22 April 2023, page 18
FM200 IS THE RIGHT CHOICE
FM-200 is the best protection for your business
Fast and efficient performance
Safe for people / Human friendly
No collateral damage
Environmentally responsible
22 April 2023, page 19
CHEMISTRY PERFORMANCE
REMOVES HEAT SO FIRECAN NOT SUSTAIN
ITSELF
CF3CHFCF3 (Is compound of Carbon,
Fluorine & Hydrogen)
22 April 2023, page 20
STANDARIZATION PERFORMANCE
UL listed
FM approved
22 April 2023, page 21
FAST AND EFFICIENT PERFORMANCE
Suppresses all classes of fires
Class A Surface Fires - wood, paper etc
Class B – flammable liquids
Class C – electrical equipment
22 April 2023, page 22
NO COLLATERAL DAMAGE
FM-200 is a CLEAN AGENT that doesn’t leave oily residues, particulates, water or corrosive material.
With FM-200 could be eliminates collateral damage to high tech equipment, artwork and other delicate and sensitive objects.
After it has been discharged, it can be removed by simple ventilation, allowing businesses to resume their normal operation almost immediately.
22 April 2023, page 23
HUMAN SAFETY
FM-200 is so safe, it has been designated as a replacement for CFCs as propellant in medical inhalers.
22 April 2023, page 24
ENVIRONMENTAL RESPONSIBILITY
Zero Potential to Deplete Ozone
22 April 2023, page 25
Critical electronics system
Computer Room with data processing equipment
Bank Vaults
File rooms and data archives
etc
APPLICATIONS
22 April 2023, page 26
FM200 PIPE LAYOUT
22 April 2023, page 27
SYSTEM COMPONENTS
FM200 SYSTEM EQUIPMENTS
22 April 2023, page 28
SYSTEM COMPONENTS
FM200 SYSTEM EQUIPMENTS (Conventional)
Panel, Control Panel RP-2002E RP-2002E / NotifierBattery 12 V - 6,5/ 7 AH Sealed Acid Panasonic / LocalRelay for Shutdown OMRON Photoelectric smoke detector 2151 / System SensorIonization smoke detector 1451 / System SensorManual release & abort switch (Notifier) NBG 12LRA + SBA-10Alarm bell SSM24-6 / System SensorHorn Strobe P2R / System SensorDo Not Enter light LocalEvacuate light LocalManual release label LocalDoor warning label Local Cylinder Assembly, 125 lbs. KIDDEDischarge Hose, KIDDECylinder strap KIDDEGas FM 200 DUPONTElectric Control Head, Stackable, 24 VDC (Ex. Proof) KIDDELever operated control head KIDDEPressure switch, 3 pole double throw KIDDEDischarge nozzle KIDDE
22 April 2023, page 29
SYSTEM COMPONENTS
FM200 SYSTEM EQUIPMENTS (Addressable)
NFS-320 Intelligent Fire Alarm Panel; NotifierBack Up Battery PanasonicRelay for Shutdown OMRON Photoelectric smoke detector FSP-851 CHIonization smoke detector FSI -851 CHManual release & abort switch NBG 12LRA + SBA-10Alarm bell SSM24-6Horn Strobe P2RDo Not Enter light LocalEvacuate light LocalManual release lable LocalDoor warning lable LocalModule, FCM-1 CH Control Flashcan FCM-1Module, FMM-101 CH Monitor with flashcan FMM-101Relay Module FRM-1 CH with flashscan FRM-1 Cylinder Assembly, 125 Lbs KIDDEDischarge Hose, KIDDECylinder strap KIDDEGas FM 200 DUPONTElectric Control Head, Stackable, 24 VDC (Ex. Proof) KIDDELever operated control head KIDDEPressure switch, 3 pole double throw KIDDEDischarge nozzle KIDDE
22 April 2023, page 30
FM200 CYLINDER COMPONENTS
22 April 2023, page 31
Halon 1301
CO2
Inert Gas
Compact storage space requirements
EFFICIENT PERFORMANCE
22 April 2023, page 32
EXCEPTION
FM200 system shall not be used to extinguish fires in :
chemicals containing their own supply of oxygen, such as cellulose nitrate, gunpowder.
Mixtures containing oxidising materials, such as sodium chlorate or sodium nitrate.
Reactive metals, such as sodium, potassium, magnesium, titanium, and zirconium.
All above materials would in case of fire create an explosion.
THANK YOUINDOLOK BAKTI UTAMA, PT – Business Area System5 February 2013
22 April 2023, page 34
EXAM FOR TRAINING FIRE SUPPRESSION SYSTEM
1. Sebutkan dan jelaskan apa yang dimaksud dengan segitiga api!2. Sebutkan beberapa macam Fire Suppression menurut media pemadamannya!3. Sebutkan dan Jelaskan tahapan / langkah-langkah kerja dari mulai pendeteksian
sampai dengan pemadaman pada Fire Suppression System!4. Berdasarkan NFPA (National Fire Protection Association) CO2, FM-200 dan Fire Alarm
System mengacu kepada NFPA berapa?5. Dari beberapa ruangan berikut, apakah efektif jika digunakan FM-200 sebagai media
Fire Suppression-nya:a. Server Room c. MCC Room e. Transformer Field
b. Control Room d. Power House f. Sodium chlorate Storage
6. Sebutkan dan Jelaskan mengapa FM-200 menjadi solusi terbaik untuk Fire Suppression System?
7. Jika sebuah Ruangan Server dengan ukuran (PxLxT) 5 x 8 x 3.5 Meter (menggunakan Raised Floor 0.3 meter) ingin diproteksi dengan FM-200, sebutkan berapa banyak detector yang harus digunakan dan jumlah gas yang diperlukan.
GOOD LUCK!!!