fire suppression system

34
FIRE SUPPRESSION SYSTEM INDOLOK BAKTI UTAMA, PT – Business Area System 5 February 2013

Upload: ianthe

Post on 30-Jan-2016

300 views

Category:

Documents


55 download

DESCRIPTION

FIRE SUPPRESSION SYSTEM. INDOLOK BAKTI UTAMA, PT – Business Area System 5 February 2013. INTRODUCTION. Api dapat terjadi dikarenakan adanya tiga unsur yang berhubungan yang dikenal dengan istilah “TRIANGLE OF FIRE /SEGITIGA API” , tiga unsur tersebut adalah : Unsur Oksigen - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: FIRE SUPPRESSION SYSTEM

FIRE SUPPRESSION SYSTEMINDOLOK BAKTI UTAMA, PT – Business Area System5 February 2013

Page 2: FIRE SUPPRESSION SYSTEM

22 April 2023, page 2

Api dapat terjadi dikarenakan adanya tiga unsur yang berhubungan yang

dikenal dengan istilah “TRIANGLE OF FIRE /SEGITIGA API”, tiga unsur

tersebut adalah :

1. Unsur Oksigen

2. Unsur Bahan bakar / Combustible material

3. Unsur Panas / Heat

Proses pemadaman api dapat dilakukan dengan menghilangkan atau

memisahkan paling sedikit salah satu dari 3 unsur tersebut, salah satu

caranya dengan menggunakan gas bertekanan.

INTRODUCTION

Page 3: FIRE SUPPRESSION SYSTEM

22 April 2023, page 3

THREE ANGEL OF FIRE

TRIANGLE OF FIRE

Api akan timbul ketika bahan bakar, oxidizer dan sumber api sudah menyatu atau tercampur pada tingkat tertentu.

Bahan bakar Padat : plastik, serbuk kayu, fiber, partikel logam Cair : bensin, aseton, eter, pentana Gas : asitilen, propana, metana, karbon monoksida, hidrogen

Oxidizer Padat : metal peroksida, amonium nitrit. Cair : hidrogen peroksida, asam nitrat, asam perklorat Gas : oksigen, flourine, klor, flour

Sumber api Korek api, listrik statis, puntung rokok,dll

Page 4: FIRE SUPPRESSION SYSTEM

22 April 2023, page 4

THREE ANGEL OF FIRE

FIRE SUPPRESSION SYSTEM

Merupakan System Pemadaman Kebakaran Otomatis dengan

menggunakan media Gas atau bahan kimia untuk memadamkan api.

Ada beberapa sistem pemadaman api dengan menggunakan gas

bertekanan sebagai media untuk proses pemadaman api, diantaranya :

1. FM200 System HFC-227ea

2. Argonite System IG-55 (50% Argon / 50% Nitrogen)

3. CO2 System

4. NOVEC 1230 FK 5-1-12 / C6F12O

Page 5: FIRE SUPPRESSION SYSTEM

22 April 2023, page 5

FM200 SYSTEM FLOWCHART

Page 6: FIRE SUPPRESSION SYSTEM

22 April 2023, page 6

Sistem dapat dioperasikan secara otomatis dan manual. System berjalan secara otomatis selama 24 jam.

Dengan Pengoperasian secara otomatis biasanya akan menimbulkan kejadian-kejadian dibawah ini:

Bila rangkaian Zone Detector 1 & 2 dalam kondisi alarm (maka alarm bell dan multi alert akan berbunyi).

Tegangan output akan bekerja, mengaktifkan electric actuator, sehingga valve ditabung akan terbuka, maka gas akan keluar didalam ruang yang diproteksi.

Jika Detector yang didalam ruangan tidak berfungsi, sedangkan didalam ruang tersebut terjadi sumber kebakaran, maka untuk mengeluarkan Gas dapat dilakukan dengan mengaktifkan tombol “ Manual Release”.

Setelah Gas keluar maka lampu DNE diatas ruangan akan menyala.

Selama Gas terpancar, jangan membuka ruangan tersebut sampai Gas habis.

HOW THE SYSTEM WORK?

Page 7: FIRE SUPPRESSION SYSTEM

22 April 2023, page 7

Pengoperasian secara manual, dilakukan bila listrik PLN atau panel tidak berfungsi, maka harus mengikuti langkah dibawah ini:

Ketahui dengan pasti ruangan yang terjadi kebakaran.

Tentukan tabung yang berhubungan dengan ruangan yang terjadi kebakaran

Pastikan ruangan tertutup rapat

Kemudian tarik “ pin pengaman “ dan tekan tuas (lever actuator) yang terdapat pada tabung.

HOW THE SYSTEM WORK?

Page 8: FIRE SUPPRESSION SYSTEM

22 April 2023, page 8

HOW THE SYSTEM WORK?

Input

Photo Smoke Detector

Ion Smoke Detector

MCFAA

Output

Strobe Lamp + Bell Alarm

Manual Release &

Abort switch

Input

Gas FM 200 discharge to Room

FM 200 Activated

Output

Fire SuppressedSmoke cause from fire

Page 9: FIRE SUPPRESSION SYSTEM

22 April 2023, page 9

WIRING INSTALLATION (Conventional)

Zone 1

Zone 2

Alarm

220VAC

Manual Release

Abort

Horn&Strobe

Page 10: FIRE SUPPRESSION SYSTEM

22 April 2023, page 10

WIRING INSTALLATION (Conventional/Zone 1 Active)

Zone 1

Zone 2

Alarm

220VAC

Manual Release

Abort

Horn&Strobe

Page 11: FIRE SUPPRESSION SYSTEM

22 April 2023, page 11

WIRING INSTALLATION (Conventional/Zone 2 Active)

Zone 1

Zone 2

Alarm

220VAC

Manual Release

Abort

Horn&Strobe

Page 12: FIRE SUPPRESSION SYSTEM

22 April 2023, page 12

WIRING INSTALLATION (Conventional/Cross Zones)

Zone 1

Zone 2

Alarm

220VAC

Manual Release

Abort

Horn&Strobe

FM200

Page 13: FIRE SUPPRESSION SYSTEM

22 April 2023, page 13

WIRING INSTALLATION (Conventional/Manual Release)

Zone 1

Zone 2

Alarm

220VAC

Manual Release

Abort

Horn&Strobe

FM200

Page 14: FIRE SUPPRESSION SYSTEM

22 April 2023, page 14

WIRING INSTALLATION (Addressable)

Zone 1 Zone 2

Alarm

220VAC

Horn&Strobe

Manual Release

AbortOutputMod

OutputMod

OutputMod

OutputMod

InputMod

InputMod

Page 15: FIRE SUPPRESSION SYSTEM

22 April 2023, page 15

Fire System Application Area

SYSTEM

AREA FIRE ALARM

SYSTEMGAS

DETECTIONNovec 1230

/FM 200 CO2/Inert gasHydrant System

Sprinkler System

Waterspray System

Foam System

Fire Extinquisher

OFFICE/ADMIN Building yes n/a yes n/a yes yes n/a n/a yesPower House yes yes n/a yes yes n/a yes n/a yesFactory Plant yes n/a n/a n/a yes n/a n/a yes yesWarehouse yes n/a n/a n/a yes yes n/a n/a yesFuel Tank Area yes n/a n/a n/a yes n/a yes yes yesBoiler Area yes yes n/a n/a yes n/a yes yes yesPower Plant yes yes n/a yes yes yes yes n/a yesMCC Panel Room yes n/a yes n/a yes n/a n/a n/a yesLaboratories yes yes/no yes n/a yes yes n/a n/a yesJetty Area yes n/a n/a n/a yes n/a n/a n/a yesConveyor yes n/a n/a n/a yes yes n/a n/a yesYard area yes n/a n/a n/a yes n/a n/a n/a n/aControl Room yes n/a yes n/a n/a n/a n/a n/a yesTransformer Area yes n/a n/a n/a yes n/a yes n/a yesFurnace yes yes n/a n/a yes n/a yes n/a yes

FIRE FIGTHING SYSTEMFIRE DETECTION SYSTEM FIRE SUPPRESSION SYSTEM

Page 16: FIRE SUPPRESSION SYSTEM

FM200 SYSTEMINDOLOK BAKTI UTAMA, PT – Business Area System2 May 2012

Page 17: FIRE SUPPRESSION SYSTEM

22 April 2023, page 17

In today’s global business environment, the need for clean agent fire suppression has never been greater.

INTRODUCTION

Page 18: FIRE SUPPRESSION SYSTEM

22 April 2023, page 18

FM200 IS THE RIGHT CHOICE

FM-200 is the best protection for your business

Fast and efficient performance

Safe for people / Human friendly

No collateral damage

Environmentally responsible

Page 19: FIRE SUPPRESSION SYSTEM

22 April 2023, page 19

CHEMISTRY PERFORMANCE

REMOVES HEAT SO FIRECAN NOT SUSTAIN

ITSELF

CF3CHFCF3 (Is compound of Carbon,

Fluorine & Hydrogen)

Page 20: FIRE SUPPRESSION SYSTEM

22 April 2023, page 20

STANDARIZATION PERFORMANCE

UL listed

FM approved

Page 21: FIRE SUPPRESSION SYSTEM

22 April 2023, page 21

FAST AND EFFICIENT PERFORMANCE

Suppresses all classes of fires

Class A Surface Fires - wood, paper etc

Class B – flammable liquids

Class C – electrical equipment

Page 22: FIRE SUPPRESSION SYSTEM

22 April 2023, page 22

NO COLLATERAL DAMAGE

FM-200 is a CLEAN AGENT that doesn’t leave oily residues, particulates, water or corrosive material.

With FM-200 could be eliminates collateral damage to high tech equipment, artwork and other delicate and sensitive objects.

After it has been discharged, it can be removed by simple ventilation, allowing businesses to resume their normal operation almost immediately.

Page 23: FIRE SUPPRESSION SYSTEM

22 April 2023, page 23

HUMAN SAFETY

FM-200 is so safe, it has been designated as a replacement for CFCs as propellant in medical inhalers.

Page 24: FIRE SUPPRESSION SYSTEM

22 April 2023, page 24

ENVIRONMENTAL RESPONSIBILITY

Zero Potential to Deplete Ozone

Page 25: FIRE SUPPRESSION SYSTEM

22 April 2023, page 25

Critical electronics system

Computer Room with data processing equipment

Bank Vaults

File rooms and data archives

etc

APPLICATIONS

Page 26: FIRE SUPPRESSION SYSTEM

22 April 2023, page 26

FM200 PIPE LAYOUT

Page 27: FIRE SUPPRESSION SYSTEM

22 April 2023, page 27

SYSTEM COMPONENTS

FM200 SYSTEM EQUIPMENTS

Page 28: FIRE SUPPRESSION SYSTEM

22 April 2023, page 28

SYSTEM COMPONENTS

FM200 SYSTEM EQUIPMENTS (Conventional)

Panel, Control Panel RP-2002E RP-2002E / NotifierBattery 12 V - 6,5/ 7 AH Sealed Acid  Panasonic / LocalRelay for Shutdown OMRON    Photoelectric smoke detector 2151 / System SensorIonization smoke detector 1451 / System SensorManual release & abort switch (Notifier) NBG 12LRA + SBA-10Alarm bell SSM24-6 / System SensorHorn Strobe P2R / System SensorDo Not Enter light LocalEvacuate light LocalManual release label LocalDoor warning label Local   Cylinder Assembly, 125 lbs. KIDDEDischarge Hose, KIDDECylinder strap KIDDEGas FM 200  DUPONTElectric Control Head, Stackable, 24 VDC (Ex. Proof) KIDDELever operated control head KIDDEPressure switch, 3 pole double throw KIDDEDischarge nozzle KIDDE

Page 29: FIRE SUPPRESSION SYSTEM

22 April 2023, page 29

SYSTEM COMPONENTS

FM200 SYSTEM EQUIPMENTS (Addressable)

NFS-320 Intelligent Fire Alarm Panel;  NotifierBack Up Battery  PanasonicRelay for Shutdown  OMRON   Photoelectric smoke detector FSP-851 CHIonization smoke detector FSI -851 CHManual release & abort switch NBG 12LRA + SBA-10Alarm bell SSM24-6Horn Strobe P2RDo Not Enter light LocalEvacuate light LocalManual release lable LocalDoor warning lable LocalModule, FCM-1 CH Control Flashcan FCM-1Module, FMM-101 CH Monitor with flashcan FMM-101Relay Module FRM-1 CH with flashscan FRM-1      Cylinder Assembly, 125 Lbs KIDDEDischarge Hose, KIDDECylinder strap KIDDEGas FM 200  DUPONTElectric Control Head, Stackable, 24 VDC (Ex. Proof) KIDDELever operated control head KIDDEPressure switch, 3 pole double throw KIDDEDischarge nozzle KIDDE

Page 30: FIRE SUPPRESSION SYSTEM

22 April 2023, page 30

FM200 CYLINDER COMPONENTS

Page 31: FIRE SUPPRESSION SYSTEM

22 April 2023, page 31

Halon 1301

CO2

Inert Gas

Compact storage space requirements

EFFICIENT PERFORMANCE

Page 32: FIRE SUPPRESSION SYSTEM

22 April 2023, page 32

EXCEPTION

FM200 system shall not be used to extinguish fires in :

chemicals containing their own supply of oxygen, such as cellulose nitrate, gunpowder.

Mixtures containing oxidising materials, such as sodium chlorate or sodium nitrate.

Reactive metals, such as sodium, potassium, magnesium, titanium, and zirconium.

All above materials would in case of fire create an explosion.

Page 33: FIRE SUPPRESSION SYSTEM

THANK YOUINDOLOK BAKTI UTAMA, PT – Business Area System5 February 2013

Page 34: FIRE SUPPRESSION SYSTEM

22 April 2023, page 34

EXAM FOR TRAINING FIRE SUPPRESSION SYSTEM

1. Sebutkan dan jelaskan apa yang dimaksud dengan segitiga api!2. Sebutkan beberapa macam Fire Suppression menurut media pemadamannya!3. Sebutkan dan Jelaskan tahapan / langkah-langkah kerja dari mulai pendeteksian

sampai dengan pemadaman pada Fire Suppression System!4. Berdasarkan NFPA (National Fire Protection Association) CO2, FM-200 dan Fire Alarm

System mengacu kepada NFPA berapa?5. Dari beberapa ruangan berikut, apakah efektif jika digunakan FM-200 sebagai media

Fire Suppression-nya:a. Server Room c. MCC Room e. Transformer Field

b. Control Room d. Power House f. Sodium chlorate Storage

6. Sebutkan dan Jelaskan mengapa FM-200 menjadi solusi terbaik untuk Fire Suppression System?

7. Jika sebuah Ruangan Server dengan ukuran (PxLxT) 5 x 8 x 3.5 Meter (menggunakan Raised Floor 0.3 meter) ingin diproteksi dengan FM-200, sebutkan berapa banyak detector yang harus digunakan dan jumlah gas yang diperlukan.

GOOD LUCK!!!