  • 7/22/2019 Table CB Dan Proteksi

    1/5

    1 / 5

    Load BREAKER RELAY Minimum Tripping

    Time Remarks

    Capacity RATING (In)

    1 VCB Incoming SWGR, from STG EVOLIS 1250 0.08 SEPAM S20

    2 VCB Incoming SWGR, from DEG EVOLIS 1250 0.08 SEPAM S20

    3 VCB FEEDER TO 01-TR-01 EVOLIS 630 0.08 SEPAM T20

    4 VCB FEEDER TO 02-TR-01 EVOLIS 630 0.08 SEPAM T20

    5 VCB FEEDER TO 02-TR-02 EVOLIS 630 0.08 SEPAM T206 VCB FEEDER TO 03-TR-01 EVOLIS 630 0.08 SEPAM T20

    7 VCB FEEDER TO 04-TR-01 EVOLIS 630 0.08 SEPAM T20

    Rating BREAKER Minimum BREAKER THERMAL Remarks

    (kW)tripping

    time RATING (In) OVERLOAD RELAY

    1INCOMING INCOMING BREAKER 3000A - -

    ACB,4P,NW32H1,3200A

    Micrologic 2.00.27

    2 01-P-01A S/S 01 Pump 01A 18.5 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3355

    3 01-P-01 B S/S 01 Pump 01B 18.5 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3355

    4 01-P-02 A S/S 01 Pump 02A 15.0 def 3.0 MCCB,3P,NS100H-TM40D 0.02

    5 01-P-02 B S/S 01 Pump 02B 15.0 def 3.0 MCCB,3P,NS100H-TM40D 0.02

    6 01-LP-01 Lighting Panel Area 01 A 8.0 - - MCCB,3P,NS100H-TM32D 0.02

    7 01-LP-02 Lighting Panel Area 01 B 36.0 - - MCCB,3P,NS160H-TM125D 0.02

    8 01-WO-01 Welding Outlet 20.0 - - MCCB,3P,NS100H-TM63D 0.02

    9 00-LP-01 Lighting Panel Area 00 A 8.0 - - MCCB,3P,NS100H-TM32D 0.02

    10 00-LP-02 Lighting Panel Area 00 B 24.0 - - MCCB,3P,NS100H-TM80D 0.02

    11 00-LP-03 Lighting Panel Area 00 C 12.0 - - MCCB,3P,NS100H-TM50D 0.02

    12 00-LP-04 Lighting Panel Area 00 D 8.0 - - MCCB,3P,NS100H-TM32D 0.02

    13 00-LP-05 Lighting Panel Area 00 E 8.0 - - MCCB,3P,NS100H-TM32D 0.02

    14 00-LP-06 Lighting Panel Area 00 F 8.0 - - MCCB,3P,NS100H-TM32D 0.02

    15 00-LP-07 Lighting Panel Area 00 G 12.0 - - MCCB,3P,NS100H-TM50D 0.02

    MV SWITCHGEAR

    No. EQUIPMENT FLA Isc BREAKERDESCRIPTION

    01-MCC-01

    No. EQUIPMENT NO DESCRIPTION FLA IscLRC Tstart

    Attachment-1

    Table protection setting

    1 Of 5

  • 7/22/2019 Table CB Dan Proteksi

    2/5

    2 / 6

    RATING FLA Isc BREAKER Minimum BREAKER THERMAL ADDITIONAL Remarks

    (kW) tripping time

    RELAY

    1 INCOMING 02-MCC-01 0 - - ACB, 4P NW32H1 0.27 3000 MICROLOGIC 2.0A

    2 TIE BUS NORMAL DAN EMERGENCY - - MCCB 4P, NS1000H MICROLOGIC 2.0A

    3 P-2101 A S/S 02A Pump 01A 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-F5369

    4 P-2101 B S/S 02A Pump 01B 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-F53695 P-2102 A S/S 02A Pump 02A 90.00 def 3.0 MCCB,3P,NS250H-MA220 0.02 LR9-F5371

    6 P-2102 B S/S 02A Pump 02B 90.00 def 3.0 MCCB,3P,NS250H-MA220 0.02 LR9-F5371

    7 P-2103 A S/S 02A Pump 03A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    8 P-2103 B S/S 02A Pump 03B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    9 P-2104 A S/S 02A Pump 04A 3.00 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14

    10 P-2104 B S/S 02A Pump 04B 3.00 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14

    11 P-2105A S/S 02A Pump 05A 7.50 def 3.0 MCCB,3P,NS80H-MA25 0.005 LRD-21

    12 P-2105B S/S 02A Pump 05B 7.50 def 3.0 MCCB,3P,NS80H-MA25 0.005 LRD-21

    13 P-2106 A S/S 02A Pump 06A 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-05

    14 P-2106 B S/S 02A Pump 06B 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-0515 P-2107 A S/S 02A Pump 07A 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-05

    16 P-2107 B S/S 02A Pump 07B 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-05

    17 P-2108 A S/S 02A Pump 08A 5.50 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-16

    18 P-2108 B S/S 02A Pump 08B 5.50 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-16

    19 P-2109 A S/S 02A Pump 09A 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14

    20 P-2109 B S/S 02A Pump 09B 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14

    21 A-2101 S/S 02A Agita tor motor 01 14.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353

    22 A-2102 S/S 02A Agita tor motor 02 14.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353

    23 A-2103 S/S 02A Agita tor motor 03 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    24 P-2110 A S/S 02A Pump 10A 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D536925 P-2110 B S/S 02A Pump 10B 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D5369

    26 P-2111 A S/S 02A Pump 11A 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D5369

    27 P-2111 B S/S 02A Pump 11B 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D5369

    28 P-2112 A S/S 02A Pump 12A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    29 P-2112 B S/S 02A Pump 12B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    30 P-2113 A S/S 02A Pump 13A 1.00 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    31 P-2113 B S/S 02A Pump 13B 1.00 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    32 P-2113 C S/S 02A Pump 13C 1.00 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    OTHERS33 02-LP-01 Lighting Panel Area 02 A 24.00 - - MCCB,3P,NS100H-TM80D

    34 02-LP-02 Lighting Panel Area 02 B 24.00 - - MCCB,3P,NS100H-TM80D

    35 02-WO-01 Welding Outlet 20.00 - - MCCB,3P,NS100H-TM63D

    36 02-WO-02 Welding Outlet 20.00 - - MCCB,3P,NS100H-TM63D

    37 02-UPS-01 UPS A 32.00 - - MCCB,3P,NS100H-TM100D

    02-MCC-01

    QUIPMENT NNo. DESCRIPTION LRC Tstart

    Attachment-1

    Table protection setting

    2 Of 6

  • 7/22/2019 Table CB Dan Proteksi

    3/5

    3 / 6

    Rating FLA Isc BREAKER Minimum BREAKER THERMAL ADDITIONAL Remarks

    (kW) tripping time RATING (In) OVERLOAD RELAY RELAY

    1 INCOMING 02-MCC-02 0 - - ACB 4P, NW20H1 0.27 2000 MICROLOGIC 2.0A

    2 TIE BREAKER - - NS1250H, 1250A MICROLOGIC 2.0A

    3 P-2201 A S/S 02B Pump 01A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    4 P-2201 B S/S 02B Pump 01B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    5 P-2202 A S/S 02B Pump 02A 22.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-33576 P-2202 B S/S 02B Pump 02B 22.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3357

    7 P-2203 A S/S 02B Pump 03A 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    8 P-2203 B S/S 02B Pump 03B 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    9 P-2204 A S/S 02B Pump 04A 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    10 P-2204 B S/S 02B Pump 04B 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    11 P-2205 A S/S 02B Pump 05A 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.005 LR9-F5369

    12 P-2205 B S/S 02B Pump 05B 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.005 LR9-F5369

    13 P-2206 A S/S 02B Pump 06A 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353

    14 P-2206 B S/S 02B Pump 06B 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353

    15 P-2207 A S/S 02B Pump 07A 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08

    16 P-2207 B S/S 02B Pump 07B 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-0817 P-2208 A S/S 02B Pump 08A 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14

    18 P-2208 B S/S 02B Pump 08B 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14

    19 P-2209 A S/S 02B Pump 09A 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10

    20 P-2209 B S/S 02B Pump 09B 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10

    21 P-2210 A S/S 02B Pump 10A 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10

    22 P-2210 B S/S 02B Pump 10B 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10

    OTHERS

    23 02-LP-03 Lighting Panel Area 02 C 32.00 - - MCCB,3P,NS100H-TM100D 0.02

    24 02-UPS-02 UPS B 32.00 - - MCCB,3P,NS100H-TM100D 0.02

    25 02-UPS-03 UPS C 32.00 - - MCCB,3P,NS100H-TM100D 0.02

    26 02-SH-1 Space Heater 20.00 - - MCCB,3P,NS100H-TM63D 0.02

    Tstart

    02-MCC-02

    No. EQUIPMENT NO DESCRIPTION LRC

    Attachment-1

    Table protection setting

    3 Of 6

  • 7/22/2019 Table CB Dan Proteksi

    4/5

    RATING Minimum BREAKER THERMAL ADDITION

    (Kw) tripping time RATING (In)

    OVERLOAD

    RELAY RELAY

    1 INCOMING - -ACB,4P,NW20H,2000A

    Micrologic 2.0A 0.272 TIE BREAKER - - MCCB 4P, NS1000H MICROLOGIC

    3 03-MCC-B Local Panel for STG 30.0 - - MCCB,3P,NS100H-TM100D 0.02

    4 P-301 A S/S 03 Pump 01A 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353

    5 P-301 B S/S 03 Pump 01B 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353

    6 P-302 A S/S 03 Pump 02A 0.75 def 3.0 MCCB,3P,NS80H-MA2.5 0.005 LRD-07

    7 P-302 B S/S 03 Pump 02B 0.75 def 3.0 MCCB,3P,NS80H-MA2.5 0.005 LRD-07

    8 03-MCC-C Local Panel for Coal Handling System 18.0 def 3.0 MCCB,3P,NS100H-TM50D 0.02

    ADDITIONAL

    9 P-303 A S/S 03 Pump 03A 90.00 def 3.0 MCCB,3P,NS250H-MA220 0.02 LR9-F5371

    10 P-303 B S/S 03 Pump 03B 7.50 def 3.0 MCCB,3P,NS80H-MA25 0.005 LRD-21

    11 P-304 S/S 03 Pump 04 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    12 P-305 A S/S 03 Pump 05A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    13 P-305 B S/S 03 Pump 05B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    Others14 03-BC-01 Baterry charger 16.00 - - MCCB,3P,NS100H-TM50D 0.02

    15 03-BC-02 Battery for STG 55.00 - - MCCB,3P,NS160H-TM160D 0.02

    16 03-BC-03 Battery RCP STG 1.60 - - MCCB,3P,NS100H-TM16D 0.02

    17 03-BC-04 Battery RCP DEG 1.60 - - MCCB,3P,NS100H-TM16D 0.02

    18 03-CP-01 Cathodic Protection 4.00 - - MCCB,3P,NS100H-TM25D 0.02

    19 03-LP-01 Lighting Panel Area 03 A 16.0 - - MCCB,3P,NS100H-TM50D 0.02

    20 03-LP-02 Lighting Panel Area 03B 24.0 - - MCCB,3P,NS100H-TM80D 0.02

    21 03-WP-01 Welding Outlet 20.0 - - MCCB,3P,NS100H-TM63D 0.02

    03-MCC-01

    No. EQUIPMENT NO DESCRIPTION FLA Isc BREAKERLRC Tstart

  • 7/22/2019 Table CB Dan Proteksi

    5/5

    5 / 6

    Rating Minimum BREAKER THERMAL ADDITIONAL Remarks(kW) Tripping time RATING (In) OVERLOAD RELAY RELAY

    1INCOMING 04-SWGR-01 - -

    ACB 4P, NW20H1

    Micrologic 2.00.27

    2 TIE BREAKER - - MCCB 4P, NS1000H 0.02 MICROLOGIC 2.0A

    3 04-MCC-A Local Panel Water Treatment 150

    4 P-401 A S/S 04 Pump 01A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    5 P-401 B S/S 04 Pump 01B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359

    6 P-411 A Cooling Water Pump 11 A 160.00 def 3.0 MCCB,3P,NS400H-MA320 0.02 LR9-F7375

    7 P-411 B Cooling Water Pump 11 B 160.00 def 3.0 MCCB,3P,NS400H-MA320 0.02 LR9-F7375

    8 P-411 C Cooling Water Pump 11 C 160.00 def 3.0 MCCB,3P,NS400H-MA320 0.02 LR9-F7375

    Others

    9 04-LP-01 Lighting Panel Area 05 A 8.0 - - MCCB,3P,NS100H-TM32D 0.02

    10 04-LP-02 Lighting Panel Area 05 B 16.0 - - MCCB,3P,NS100H-TM50D 0.02

    11 04-CP-01 Cathodic Protection 4.00 - - MCCB,3P,NS100H-TM16D 0.02

    12 04-WO-01 Welding Outlet 20.0 - - MCCB,3P,NS100H-TM63D 0.02

    Isc

    04-MCC-01

    BREAKERLRC TstartNo. EQUIPMENT NO DESCRIPTION FLA

    Attachment-1

    Table protection setting

    5 Of 6