7/22/2019 Table CB Dan Proteksi
1/5
1 / 5
Load BREAKER RELAY Minimum Tripping
Time Remarks
Capacity RATING (In)
1 VCB Incoming SWGR, from STG EVOLIS 1250 0.08 SEPAM S20
2 VCB Incoming SWGR, from DEG EVOLIS 1250 0.08 SEPAM S20
3 VCB FEEDER TO 01-TR-01 EVOLIS 630 0.08 SEPAM T20
4 VCB FEEDER TO 02-TR-01 EVOLIS 630 0.08 SEPAM T20
5 VCB FEEDER TO 02-TR-02 EVOLIS 630 0.08 SEPAM T206 VCB FEEDER TO 03-TR-01 EVOLIS 630 0.08 SEPAM T20
7 VCB FEEDER TO 04-TR-01 EVOLIS 630 0.08 SEPAM T20
Rating BREAKER Minimum BREAKER THERMAL Remarks
(kW)tripping
time RATING (In) OVERLOAD RELAY
1INCOMING INCOMING BREAKER 3000A - -
ACB,4P,NW32H1,3200A
Micrologic 2.00.27
2 01-P-01A S/S 01 Pump 01A 18.5 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3355
3 01-P-01 B S/S 01 Pump 01B 18.5 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3355
4 01-P-02 A S/S 01 Pump 02A 15.0 def 3.0 MCCB,3P,NS100H-TM40D 0.02
5 01-P-02 B S/S 01 Pump 02B 15.0 def 3.0 MCCB,3P,NS100H-TM40D 0.02
6 01-LP-01 Lighting Panel Area 01 A 8.0 - - MCCB,3P,NS100H-TM32D 0.02
7 01-LP-02 Lighting Panel Area 01 B 36.0 - - MCCB,3P,NS160H-TM125D 0.02
8 01-WO-01 Welding Outlet 20.0 - - MCCB,3P,NS100H-TM63D 0.02
9 00-LP-01 Lighting Panel Area 00 A 8.0 - - MCCB,3P,NS100H-TM32D 0.02
10 00-LP-02 Lighting Panel Area 00 B 24.0 - - MCCB,3P,NS100H-TM80D 0.02
11 00-LP-03 Lighting Panel Area 00 C 12.0 - - MCCB,3P,NS100H-TM50D 0.02
12 00-LP-04 Lighting Panel Area 00 D 8.0 - - MCCB,3P,NS100H-TM32D 0.02
13 00-LP-05 Lighting Panel Area 00 E 8.0 - - MCCB,3P,NS100H-TM32D 0.02
14 00-LP-06 Lighting Panel Area 00 F 8.0 - - MCCB,3P,NS100H-TM32D 0.02
15 00-LP-07 Lighting Panel Area 00 G 12.0 - - MCCB,3P,NS100H-TM50D 0.02
MV SWITCHGEAR
No. EQUIPMENT FLA Isc BREAKERDESCRIPTION
01-MCC-01
No. EQUIPMENT NO DESCRIPTION FLA IscLRC Tstart
Attachment-1
Table protection setting
1 Of 5
-
7/22/2019 Table CB Dan Proteksi
2/5
2 / 6
RATING FLA Isc BREAKER Minimum BREAKER THERMAL ADDITIONAL Remarks
(kW) tripping time
RELAY
1 INCOMING 02-MCC-01 0 - - ACB, 4P NW32H1 0.27 3000 MICROLOGIC 2.0A
2 TIE BUS NORMAL DAN EMERGENCY - - MCCB 4P, NS1000H MICROLOGIC 2.0A
3 P-2101 A S/S 02A Pump 01A 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-F5369
4 P-2101 B S/S 02A Pump 01B 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-F53695 P-2102 A S/S 02A Pump 02A 90.00 def 3.0 MCCB,3P,NS250H-MA220 0.02 LR9-F5371
6 P-2102 B S/S 02A Pump 02B 90.00 def 3.0 MCCB,3P,NS250H-MA220 0.02 LR9-F5371
7 P-2103 A S/S 02A Pump 03A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
8 P-2103 B S/S 02A Pump 03B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
9 P-2104 A S/S 02A Pump 04A 3.00 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14
10 P-2104 B S/S 02A Pump 04B 3.00 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14
11 P-2105A S/S 02A Pump 05A 7.50 def 3.0 MCCB,3P,NS80H-MA25 0.005 LRD-21
12 P-2105B S/S 02A Pump 05B 7.50 def 3.0 MCCB,3P,NS80H-MA25 0.005 LRD-21
13 P-2106 A S/S 02A Pump 06A 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-05
14 P-2106 B S/S 02A Pump 06B 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-0515 P-2107 A S/S 02A Pump 07A 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-05
16 P-2107 B S/S 02A Pump 07B 0.25 def 3.0 MCCB,3P,NS80H-MA1.5 0.005 LRD-05
17 P-2108 A S/S 02A Pump 08A 5.50 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-16
18 P-2108 B S/S 02A Pump 08B 5.50 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-16
19 P-2109 A S/S 02A Pump 09A 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14
20 P-2109 B S/S 02A Pump 09B 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14
21 A-2101 S/S 02A Agita tor motor 01 14.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353
22 A-2102 S/S 02A Agita tor motor 02 14.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353
23 A-2103 S/S 02A Agita tor motor 03 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
24 P-2110 A S/S 02A Pump 10A 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D536925 P-2110 B S/S 02A Pump 10B 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D5369
26 P-2111 A S/S 02A Pump 11A 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D5369
27 P-2111 B S/S 02A Pump 11B 55.00 def 3.0 MCCB,3P,NS160H-MA150 0.02 LR9-D5369
28 P-2112 A S/S 02A Pump 12A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
29 P-2112 B S/S 02A Pump 12B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
30 P-2113 A S/S 02A Pump 13A 1.00 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
31 P-2113 B S/S 02A Pump 13B 1.00 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
32 P-2113 C S/S 02A Pump 13C 1.00 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
OTHERS33 02-LP-01 Lighting Panel Area 02 A 24.00 - - MCCB,3P,NS100H-TM80D
34 02-LP-02 Lighting Panel Area 02 B 24.00 - - MCCB,3P,NS100H-TM80D
35 02-WO-01 Welding Outlet 20.00 - - MCCB,3P,NS100H-TM63D
36 02-WO-02 Welding Outlet 20.00 - - MCCB,3P,NS100H-TM63D
37 02-UPS-01 UPS A 32.00 - - MCCB,3P,NS100H-TM100D
02-MCC-01
QUIPMENT NNo. DESCRIPTION LRC Tstart
Attachment-1
Table protection setting
2 Of 6
-
7/22/2019 Table CB Dan Proteksi
3/5
3 / 6
Rating FLA Isc BREAKER Minimum BREAKER THERMAL ADDITIONAL Remarks
(kW) tripping time RATING (In) OVERLOAD RELAY RELAY
1 INCOMING 02-MCC-02 0 - - ACB 4P, NW20H1 0.27 2000 MICROLOGIC 2.0A
2 TIE BREAKER - - NS1250H, 1250A MICROLOGIC 2.0A
3 P-2201 A S/S 02B Pump 01A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
4 P-2201 B S/S 02B Pump 01B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
5 P-2202 A S/S 02B Pump 02A 22.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-33576 P-2202 B S/S 02B Pump 02B 22.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3357
7 P-2203 A S/S 02B Pump 03A 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
8 P-2203 B S/S 02B Pump 03B 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
9 P-2204 A S/S 02B Pump 04A 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
10 P-2204 B S/S 02B Pump 04B 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
11 P-2205 A S/S 02B Pump 05A 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.005 LR9-F5369
12 P-2205 B S/S 02B Pump 05B 75.00 def 3.0 MCCB,3P,NS160H-MA150 0.005 LR9-F5369
13 P-2206 A S/S 02B Pump 06A 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353
14 P-2206 B S/S 02B Pump 06B 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353
15 P-2207 A S/S 02B Pump 07A 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-08
16 P-2207 B S/S 02B Pump 07B 1.50 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-0817 P-2208 A S/S 02B Pump 08A 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14
18 P-2208 B S/S 02B Pump 08B 3.70 def 3.0 MCCB,3P,NS80H-MA12.5 0.005 LRD-14
19 P-2209 A S/S 02B Pump 09A 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10
20 P-2209 B S/S 02B Pump 09B 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10
21 P-2210 A S/S 02B Pump 10A 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10
22 P-2210 B S/S 02B Pump 10B 2.20 def 3.0 MCCB,3P,NS80H-MA6.3 0.005 LRD-10
OTHERS
23 02-LP-03 Lighting Panel Area 02 C 32.00 - - MCCB,3P,NS100H-TM100D 0.02
24 02-UPS-02 UPS B 32.00 - - MCCB,3P,NS100H-TM100D 0.02
25 02-UPS-03 UPS C 32.00 - - MCCB,3P,NS100H-TM100D 0.02
26 02-SH-1 Space Heater 20.00 - - MCCB,3P,NS100H-TM63D 0.02
Tstart
02-MCC-02
No. EQUIPMENT NO DESCRIPTION LRC
Attachment-1
Table protection setting
3 Of 6
-
7/22/2019 Table CB Dan Proteksi
4/5
RATING Minimum BREAKER THERMAL ADDITION
(Kw) tripping time RATING (In)
OVERLOAD
RELAY RELAY
1 INCOMING - -ACB,4P,NW20H,2000A
Micrologic 2.0A 0.272 TIE BREAKER - - MCCB 4P, NS1000H MICROLOGIC
3 03-MCC-B Local Panel for STG 30.0 - - MCCB,3P,NS100H-TM100D 0.02
4 P-301 A S/S 03 Pump 01A 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353
5 P-301 B S/S 03 Pump 01B 15.00 def 3.0 MCCB,3P,NS80H-MA50 0.005 LRD-3353
6 P-302 A S/S 03 Pump 02A 0.75 def 3.0 MCCB,3P,NS80H-MA2.5 0.005 LRD-07
7 P-302 B S/S 03 Pump 02B 0.75 def 3.0 MCCB,3P,NS80H-MA2.5 0.005 LRD-07
8 03-MCC-C Local Panel for Coal Handling System 18.0 def 3.0 MCCB,3P,NS100H-TM50D 0.02
ADDITIONAL
9 P-303 A S/S 03 Pump 03A 90.00 def 3.0 MCCB,3P,NS250H-MA220 0.02 LR9-F5371
10 P-303 B S/S 03 Pump 03B 7.50 def 3.0 MCCB,3P,NS80H-MA25 0.005 LRD-21
11 P-304 S/S 03 Pump 04 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
12 P-305 A S/S 03 Pump 05A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
13 P-305 B S/S 03 Pump 05B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
Others14 03-BC-01 Baterry charger 16.00 - - MCCB,3P,NS100H-TM50D 0.02
15 03-BC-02 Battery for STG 55.00 - - MCCB,3P,NS160H-TM160D 0.02
16 03-BC-03 Battery RCP STG 1.60 - - MCCB,3P,NS100H-TM16D 0.02
17 03-BC-04 Battery RCP DEG 1.60 - - MCCB,3P,NS100H-TM16D 0.02
18 03-CP-01 Cathodic Protection 4.00 - - MCCB,3P,NS100H-TM25D 0.02
19 03-LP-01 Lighting Panel Area 03 A 16.0 - - MCCB,3P,NS100H-TM50D 0.02
20 03-LP-02 Lighting Panel Area 03B 24.0 - - MCCB,3P,NS100H-TM80D 0.02
21 03-WP-01 Welding Outlet 20.0 - - MCCB,3P,NS100H-TM63D 0.02
03-MCC-01
No. EQUIPMENT NO DESCRIPTION FLA Isc BREAKERLRC Tstart
-
7/22/2019 Table CB Dan Proteksi
5/5
5 / 6
Rating Minimum BREAKER THERMAL ADDITIONAL Remarks(kW) Tripping time RATING (In) OVERLOAD RELAY RELAY
1INCOMING 04-SWGR-01 - -
ACB 4P, NW20H1
Micrologic 2.00.27
2 TIE BREAKER - - MCCB 4P, NS1000H 0.02 MICROLOGIC 2.0A
3 04-MCC-A Local Panel Water Treatment 150
4 P-401 A S/S 04 Pump 01A 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
5 P-401 B S/S 04 Pump 01B 30.00 def 3.0 MCCB,3P,NS80H-MA80 0.005 LRD-3359
6 P-411 A Cooling Water Pump 11 A 160.00 def 3.0 MCCB,3P,NS400H-MA320 0.02 LR9-F7375
7 P-411 B Cooling Water Pump 11 B 160.00 def 3.0 MCCB,3P,NS400H-MA320 0.02 LR9-F7375
8 P-411 C Cooling Water Pump 11 C 160.00 def 3.0 MCCB,3P,NS400H-MA320 0.02 LR9-F7375
Others
9 04-LP-01 Lighting Panel Area 05 A 8.0 - - MCCB,3P,NS100H-TM32D 0.02
10 04-LP-02 Lighting Panel Area 05 B 16.0 - - MCCB,3P,NS100H-TM50D 0.02
11 04-CP-01 Cathodic Protection 4.00 - - MCCB,3P,NS100H-TM16D 0.02
12 04-WO-01 Welding Outlet 20.0 - - MCCB,3P,NS100H-TM63D 0.02
Isc
04-MCC-01
BREAKERLRC TstartNo. EQUIPMENT NO DESCRIPTION FLA
Attachment-1
Table protection setting