  • Tr - FUNGSI DARI SWITCHGEAR :

    PERALATAN PEMUTUS DAYA YANG FUNGSI UTAMANYA MENCATAT DAN MEMUTUSKAN DAYA LISTRIK KE PERALATAN / BEBAN.

    SWITCHGEAR (CIRCUIT BREAKER) TEGANGAN RENDAH YANG DIBAHAS ADALAH JENIS A.C.B. TIPE DS 416 MERK MITSUBISHI

  • RATING DARI BREAKER TIPE DS 416 :11212/HI/TR/KJ/MYN/minDoc 12/1.1.12/1/97Tr - *

    Doc 12/1.1.12/1/97

    TIPE

    TEGANGAN

    ( VOLT )

    FRAME SIZE

    ( A )

    RATED/ INTERUPTING CURRENT

    ( KA-SYM )

    DS 416

    600

    500

    250

    1600

    42

    50

    50

  • 11212/HI/TR/KJ/MYN/minDoc 12/1.1.12/1/97Tr - *

    Doc 12/1.1.12/1/97

  • LANGKAH-LANGKAH : - KOMUNIKASI HARUS JELAS - KEPERLUAN HARUS JELAS - KEDUDUKAN / POSISI BREAKER SETELAH DILEPAS. - SISTEM PENGAMANAN DIPERLUKAN ATAU TIDAK UNTUK PELEPASAN DILAKUKAN DENGAN 3 CARA PENGOPERASIAN : - OPERASI SECARA REMOTE - OPERASI SECARA LOKAL - OPERASI MANUAL PROSEDUR PELEPASAN SWITCHGEAR

    Doc 12/1.1.12/1/97

  • - YAKINKAN SELECTOR SWITCH PENGOPERASIAN PADA POSISI REMOTE - PASTIKAN SWITCHGEAR (CIRCUIT BREAKER) AKAN DILEPAS. - LEPAS CIRCUIT BREAKER DENGAN MENGGUNAKAN SAKLAR START / STOP DENGAN MENGGERAKKAN BERLAWANAN ARAH JARUM JAM ATAU PUSH BUTTON ON/OFF. - PASTIKAN KONTAK BREAKER SUDAH TERBUKA OPEN DENGAN MEMPERHATIKAN INDIKASI CONTACT POSITION. BENDERA - HIJAU LAMPU - HIJAU NYALA DAN MERAH HATI. - LAKSANAKAN LANGKAH-LANGKAH KERJA SELANJUTNYA SESUAI DENGAN PETUNJUK. PROSEDUR PELEPASAN SWITCHGEAR SECARA REMOTE

    Doc 12/1.1.12/1/97

  • 11212/HI/TR/KJ/MYN/minDoc 12/1.1.12/1/97Tr - * PELEPASAN SECARA OPERASI LOKAL- SELECTOR SWITCH PENGOPERASIAN POSISI LOCAL. - PELEPASAN DILAKUKAN DENGAN MENGGERAKKAN TRIP PLAT. - PERHATIKAN CONTACT POSITION INDICATOR BENDERA HIJAU ATAU NOL (0) BAHWA KONTAK TERBUKA OPEN. PELEPASAN SECARA MANUAL- DILAKUKAN DILUAR CUBICLE. - CHARGING PEGAS PEMASUKKAN. - MASUKKAN BREAKER DENGAN MENEKAN TOMBOL PEMASUKKAN (CLOSE BUTTON) - LEPAS CIRCUIT BREAKER DENGAN MENEKAN TRIP PLAT DAN PERHATIKAN KONTAK SECARA PENGAMATAN SUDAH TERBUKA OPEN.

    Doc 12/1.1.12/1/97

  • 11212/HI/TR/KJ/MYN/minDoc 12/1.1.12/1/97Tr - * TERDAPAT 3 KEDUDUKAN / POSISI BREAKER DI CUBICLE : 1. POSISI CONNECTED 2. POSISI TEST 3. POSISI DISCONNECTED 4. DRAW OUT ( DILUAR CUBICLE ). - POSISI CONNECTED : PRIMARY JUNCTION TERHUBUNG, SECONDARY JUNCTION TERHUBUNG - POSISI TEST : PRIMARY JUNCTION TIDAK TERHUBUNG, SECONDARY JUNCTION TERHUBUNG - POSISI DISCONNECTED : PRIMARY & SECONDARY JUNCTION TIDAK TERHUBUNG, - DRAW OUT : BREAKER DILUAR CUBICLE ( PRIMARY DAN SECONDARY JUNCTION TIDAK TERHUBUNG )PROSEDUR PELEPASAN SWITCHGEAR

    Doc 12/1.1.12/1/97

  • 11212/HI/TR/KJ/MYN/minDoc 12/1.1.12/1/97Tr - * PEMERIKSAAN ARC CHUTE : TANDA-TANDA TERBAKAR, DEPOSITE, KERETAKAN INSULATING PLATE A DAN INSULATING PLATE B, KEDALAMAN ALUR, PERMUKAAN MOULDED CASE, KERETAKAN.PEMERIKSAAN KOMPONEN UTAMA

    Doc 12/1.1.12/1/97

  • 11212/HI/TR/KJ/MYN/minDoc 12/1.1.12/1/97Tr - * - PERMUKAAN KONTAK : KASAR / TIDAK RATA, KETEBALAN LAPISAN ( + 1mm ) JARAK PERMUKAAN KONTAK UTAMA SAAT KONTAK BUSUR MASUK TIDAK KURANG DARI 3 mm, KELURUSAN SAAT MASUK, JARAK KERUSAKAN BUSUR SAAT BREAKER CLOSE TIDAK BOLEH KURANG DARI 1 mm. KONTAK UTAMA DAN KONTAK BANTU

    Doc 12/1.1.12/1/97

  • - PERIKSA SECARA VISUAL TERHADAP KOTORAN, DEBU DAN BENDA-BENDA. - PERIKSA TEST SISTEM KERJA MEKANIS. - PERIKSA PELUMASAN BEARING - TEST PUTARAN DARI PENGUJIAN TRIP ( TRIP LATH ) NO.4 KOMPONEN MEKANIS PENGGERAK

  • - PERIKSA SECARA VISUAL : ISOLASI DAN KUMPARAN KOIL. - UKUR TAHANAN ISOLASI DENGAN MENGGUNAKAN MEGGER 500 VOLT CLOSING DAN TRIPPING COILFUNGSI INTERLOCK : MENGHINDARI TERJADINYA KESALAHAN OPERASI YANG DAPAT MENGAKIBATKAN KERUSAKAN PERALATAN DAN BAHAYA / KESALAHAN TERHADAP MANUSIA FUNGSI CLOSING SPRING DISCHARGE INTERLOCK : MENCEGAH MASUKNYA BREAKER PADA SAAT POSISI DISCONNECTED PEMERIKSAAN YANG DILAKUKAN : SISTEM KERJANYAINTERLOCK MEKANIS

    Doc 12/1.1.12/1/97

  • - PERIKSA SISTEM KERJA SHUTTER INTERLOCK MEKANIS FUNGSI INTERLOCK INI ADALAH UTNUK MENCEGAH AGAR BREAKER PADA POSISI CLOSE, BREAKER TIDAK DAPAT DIKELUARKAN ATAU DIGERAKKAN DARI BILIKNYA ( CUBICLE ), SALAH COBA MERUSAK KONTAK ISOLASI PRIMARY JUNCTION DAN MEMBAHAYAKAN PETUGAS

    Doc 12/1.1.12/1/97

  • PEMERIKSAAN : SISTEM KERJANYA FUNGSINYA : - MENGUNCI BREAKER TIDAK DAPAT DIMASUKKAN ATAU DIKELUARKAN - MENGUNCI BREAKER AGAR TIDAK CEPAT DIMASUKKAN, WALAUPUN DAPAT DIKELUARKAN. PAD LOCKING

  • - PERIKSA KELONGGARAN SKRUP-SKRUP. - PERIKSA DIAL DENGAN EKIVALEN ARUS TRAFO SISI SEKUNDER SOLID STATE REGULATOR

  • PEMERIKSAAN TRAFO TEGANGAN : - UKUR DAN CATAT TEGANGAN TRAFO : PRIMER DAN SEKUNDER. - CHECK ISOLASI, BELITAN, BODI SECARA VISUAL - UKUR TAHANAN ISOLASI TRAFO ARUS : KERETAKAN DAN UKUR ARUS TRAFO DAN TAHANAN ISOLASINYATRIP AKTUATOR

  • -BERSIHKAN CUBICLE DENGAN UDARA BERSIH DAN KERING. -ARC SHUTE, KONTAK-KONTAK MEKANIS : UDARA BERSIH. -KONTAK BUSUR, KONTAK UTAMA, KONTAK BANTU DAN OLESKAN DENGAN GRAPHITE GREASE SECUKUPNYA. -KOMPONEN MEKANIK : BERSIHKAN KOTORAN, DEBU DAN BENDA-BENDAASING, GUNAKAN KUAS, LEMARI BAGIAN-BAGIAN YANG BERGERAK -MOULDED BAGIAN BAWAH BERSIHKAN TERHADAP DEOPSITE PEMBERSIHAN SWITCHGEAR

  • SECARA MANUAL: DILUAR CUBICLE. SECARA ELCTRICAL: DIDALAM CUBICLE / POSISI TEST. SECARA MANUAL : - ISI PEGAS SECARA MANUAL, PERHATIKAN INDIKATOR SPRING CHARGE. - TEKAN TOMBOL PEMASUKKAN, PERHATIKAN SECARA VISUAL BREAKER CON- TACT POSITION INDIKATOR ATAU PERHATIKAN KEDUDUKAN KONTAK UTAMA - LEPAS BREAKER DENGAN MENEKAN TRIP PLATE. SECARA ELEKTRICAL : - MASUKKAN BREAKER KE CUBICLE - POSISIKAN KEDUDUKAN BREAKER PADA POSISI TEST. - MASUKKAN POWER SUPLAI UNTUK KONTROL : PEGAS AKAN TERISI BILA DI LENGKAPI DENGAN CHARGING OTOMATIS ATAU ISI PEGAS SECARA MANUAL - MASUKKAN KONTAK BREAKER DENGAN MENEKAN PUSH BUTTON CLOSE DAN LEPAS KONTAK BREAKER DENGAN TRIP PLATE. PENGETESAN OPERASI SWITCHGEAR

  • KONDISI-KONDISI YANG HARUS TERPENUHI SAAT MEMASUK KAN BREAKER PADA LOKAL OPERASI MAUPUN REMOTE OPERASI - BREAKER DAPAT DIMASUKKAN PADA POSISI TEST DAN CONNECTED. - LEVERING HANDLE DILEPAS DARI BREAKER, SHUTTER HARUS NAIK DAN TRIP PLATE HARUS RESET. - CLOSING SPRING DAPAT DIISI.