STANDAR PT PLN (PERSERO) SPLN S5.001: 2008 Lampiran Surat Keputusan Direksi PT PLN (PERSERO) No: 168.K/DIR/2009 TELEINFORMASI DATA UNTUK OPERASI JARINGAN TENAGA LISTRIK PT PLN (PERSERO) JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU JAKARTA SELATAN 12160

Upload: terdesak

Post on 26-Oct-2015

893 views

Category:

Documents


127 download

DESCRIPTION

TELE INFORMASI DATA UNTUK OPERASI JARINGAN

TRANSCRIPT

Page 1: SPLN S5.001:2008

STANDAR PT PLN (PERSERO)

SPLN S5.001: 2008 Lampiran Surat Keputusan Direksi

PT PLN (PERSERO) No: 168.K/DIR/2009

TELEINFORMASI DATA UNTUK OPERASI JARINGAN

TENAGA LISTRIK

PT PLN (PERSERO)

JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU

JAKARTA SELATAN 12160

Page 2: SPLN S5.001:2008

TELEINFORMASI DATA UNTUK OPERASI JARINGAN

TENAGA LISTRIK

Disusun oleh:

Kelompok Bidang SCADA dengan Surat Keputusan Direksi

PT PLN (PERSERO) No.094.K/DIR/2006

Kelompok Kerja Kaidah Rancangan Dasar Sistem SCADA Untuk Operasi Jaringan tenaga Listrik

dengan Surat Keputusan General Manager PT PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan

No. 006.K/LITBANG/2007

Diterbitkan oleh:

PT PLN (PERSERO) Jalan Trunojoyo Blok M-I /135, Kebayoran Baru

Jakarta Selatan

Page 3: SPLN S5.001:2008

Susunan Kelompok Bidang SCADA Standardisasi

Surat Keputusan Direksi PT PLN (PERSERO) No: 094.K/DIR/2006

1. Ir. Nur Pamudji, M.Eng, MPM : Sebagai Ketua merangkap Anggota

2. Ir. Harry Hartoyo, MM, MPM : Sebagai Wakil Ketua merangkap Anggota

3. Ir. Hernadi Buhron : Sebagai Sekretaris merangkap Anggota

4. Novrizal Erdiansyah, ST : Sebagai Wakil Sekretaris merangkap Anggota

5. Ir. Solida : Sebagai Anggota

6. Ir. Sudibyo : Sebagai Anggota

7. Agus H Maulana, ST : Sebagai Anggota

8. Ir. Joko Pramono : Sebagai Anggota

9. Ir. A. Sugeng Sugarjito : Sebagai Anggota

10. Ir. Yarid Pabisa : Sebagai Anggota

11. Ir. Ruly Chaerul : Sebagai Anggota

12. Ir. Herry Santoso : Sebagai Anggota

13. Ir. Yanuar I. Prakoso : Sebagai Anggota

14. Ir. Hesti Sayoga : Sebagai Anggota

15. Ir. Deany EA Rumengan : Sebagai Anggota

Susunan kelompok kerja Kaidah Rancangan Dasar Sistem SCADA Untuk Operasi Jaringan

Tenaga Listrik Surat Keputusan General Manager PT PLN (Persero) Litbang Ketenagalistrikan

No: 006.K/LITBANG/2007

1. Ir. Solida : Sebagai Ketua merangkap Anggota

2. Novrizal Erdiansyah, ST : Sebagai Sekretaris merangkap Anggota

3. Ir. A. Sugeng Sugarjito : Sebagai Anggota

4. Ir. Ruly Chaerul : Sebagai Anggota

5. Tri Hardimasyar, ST : Sebagai Anggota

6. Ir. Yarid Pabisa : Sebagai Anggota

7. Ir. Joko Pramono : Sebagai Anggota

8. Ir. Denden Ruhdani : Sebagai Anggota

Page 4: SPLN S5.001:2008
Page 5: SPLN S5.001:2008

SPLN S5.001: 2008

i

DAFTAR ISI

Daftar Isi ......................................................................................................................................i

Daftar Tabel ............................................................................................................................... iii

Daftar Gambar ........................................................................................................................... iv

Daftar Lampiran ..........................................................................................................................v

Prakata ..................................................................................................................................... vii

1. Ruang Lingkup .............................................................................................................. 1

2. Tujuan ........................................................................................................................... 1

3. Acuan Normatif ............................................................................................................. 1

4. Istilah dan Definisi ......................................................................................................... 1

4.1 Alarm ............................................................................................................................. 1

4.2 Control center ................................................................................................................ 2

4.3 Distribution control center (DCC) .................................................................................. 2

4.4 Feeder colouring ........................................................................................................... 2

4.5 Gardu hubung ............................................................................................................... 2

4.6 Gardu tengah ................................................................................................................ 2

4.7 Earth Fault Indicator (EFI) ............................................................................................. 2

4.8 Inter distribution control center (IDCC) .......................................................................... 2

4.9 Inter regional control center (IRCC) .............................................................................. 2

4.10 Keypoint ........................................................................................................................ 2

4.11 National control center (NCC) ....................................................................................... 2

4.12 Regional control center (RCC) ...................................................................................... 2

4.13 Supervisory control and data acquisition (SCADA) ....................................................... 3

4.14 Telecontrol .................................................................................................................... 3

4.15 Telesignal ...................................................................................................................... 3

4.16 Telemetering ................................................................................................................. 3

4.17 Teleprotection ............................................................................................................... 3

5. Umum ........................................................................................................................... 3

5.1 Fasilitas SCADA ............................................................................................................ 3

5.2 Teleinformasi data ......................................................................................................... 3

5.3 Struktur informasi .......................................................................................................... 4

5.4 Simbol dan warna ......................................................................................................... 4

Page 6: SPLN S5.001:2008

SPLN S5.001: 2008

ii

6. Perbatasan Kebutuhan Teleinformasi Data .................................................................. 4

6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC ................................ 4

6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC ................................. 5

Lampiran A – Daftar Teleinformasi (Transmisi) ......................................................................... 7

Lampiran B – Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk) ..... 15

Lampiran C – Daftar Teleinformasi (Distribusi) ....................................................................... 89

Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) ........................................................................................... 95

Lampiran E – Struktur Informasi ............................................................................................ 118

Lampiran F – Simbol dan Warna ........................................................................................... 126

Page 7: SPLN S5.001:2008

SPLN S5.001: 2008

iii

DAFTAR TABEL Tabel 1. Struktur informasi ............................................................................................... 119 Tabel 2. Level tegangan .................................................................................................. 121 Tabel 3. Nama bay atau feeder ....................................................................................... 122 Tabel 4. Kode tegangan dari primer dan sekunder trafo ................................................. 122 Tabel 5. Kode nama peralatan/alarm/elemen .................................................................. 123 Tabel 6. Warna tampilan .................................................................................................. 129

Page 8: SPLN S5.001:2008

SPLN S5.001: 2008

iv

DAFTAR GAMBAR Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a) ....................................... 5 Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b) ....................................... 5 Gambar 3. Batas wewenang antara RCC dengan DCC ..................................................... 6 Gambar 4. Struktur informasi khusus (bay diameter) ...................................................... 124 Gambar 5. Struktur informasi khusus (gardu induk 1½ breaker) .................................... 125 Gambar 6. Simbol gambar .............................................................................................. 127 Gambar 7. Tampilan status ............................................................................................. 128

Page 9: SPLN S5.001:2008

SPLN S5.001: 2008

v

DAFTAR LAMPIRAN

Lampiran A – Daftar Teleinformasi (Transmisi) ........................................................................ 7 A-1: Telesignal ......................................................................................................................................... 8 A-2: Telemeasurement ......................................................................................................................... 11 A-3: Tap changer position .................................................................................................................... 12 A-4: Remote control digital ................................................................................................................... 13 A-5: Remote control analog ................................................................................................................. 14

Lampiran B – Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk) .... 15 TA-01: Konfigurasi umum pada 1½ breaker ..................................................................................... 16 TA-02: Konfigurasi umum pada double busbar ................................................................................ 20 TA-03: Konfigurasi umum pada single busbar .................................................................................. 25 TB-01: Generator combined cycle pada konfigurasi 1½ breaker ................................................... 30 TB-02: 2 generator terhubung ke MTR 3-belitan pada konfigurasi 1½ breaker .......................... 32 TB-03: 2 generator terhubung ke MTR 3-belitan pada konfigurasi double busbar ..................... 34 TB-04: 2 generator terhubung ke MTR 3-belitan pada konfigurasi single busbar ....................... 36 TB-05: 1 generator terhubung ke MTR 2-belitan pada konfigurasi 1½ breaker .......................... 38 TB-06: 1 generator terhubung ke MTR 2-belitan pada konfigurasi double busbar ..................... 40 TB-07: 1 generator terhubung ke MTR 2-belitan pada konfigurasi single busbar ....................... 42 TB-08: 2 generator terhubung ke MTR 2-belitan pada konfigurasi 1½ breaker .......................... 44 TB-09: 2 generator terhubung ke MTR 2-belitan pada konfigurasi double busbar ..................... 46 TB-10: 2 generator terhubung ke MTR 2-belitan pada konfigurasi single busbar ....................... 48 TB-11: Interbus transformer (secondary side connected to 1½ breaker) ....................................................................................... 50 TB-12: Interbus transformer (secondary side connected to double busbar) .................................................................................. 52 TB-13: Interbus transformer (secondary side connected to single busbar) .................................................................................... 54 TB-14: Interbus transformer (secondary side connected to 1½ breaker dilengkapi

shunt reaktor pada kumparan tersier) .................................................................................. 56 TB-15: Interbus transformer (secondary side connected to double busbar dilengkapi

shunt reaktor pada kumparan tersier) .................................................................................. 58 TB-16: Interbus transformer (secondary side connected to single busbar dilengkapi

shunt reaktor pada kumparan tersier) .................................................................................. 60 TB-17: Bay trafo tenaga pada konfigurasi 1½ breaker .................................................................... 62 TB-18: Bay trafo tenaga pada konfigurasi double busbar ............................................................... 64 TB-19: Bay trafo tenaga pada konfigurasi single busbar ................................................................ 66 TB-20: Bay reaktor pada konfigurasi 1 ½ breaker ............................................................................ 68 TB-21: Bay reaktor pada konfigurasi double busbar ........................................................................ 69 TB-22: Bay reaktor pada konfigurasi single busbar ......................................................................... 70 TB-23: Bay capasitor pada konfigurasi double busbar .................................................................... 71 TB-24: Bay capasitor pada konfigurasi single busbar ...................................................................... 72 TB-25: Bay penghantar pada konfigurasi 1 ½ breaker .................................................................... 73 TB-26: Bay penghantar pada konfigurasi double busbar ................................................................ 75 TB-27: Bay penghantar pada konfigurasi single busbar .................................................................. 77 TB-28: Bay penghantar paralel dengan reaktor pada konfigurasi double busbar ....................... 79 TB-29: Bay penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker ......................... 81 TB-30: Bay penghantar paralel dengan 2 reaktor seri pada konfigurasi 1½ breaker ................. 83 TB-31: Bay kopel pada konfigurasi double busbar ........................................................................... 85 TB-32: Bus section ................................................................................................................................ 86

Page 10: SPLN S5.001:2008

SPLN S5.001: 2008

vi

TB-33: Bay diameter pada konfigurasi 1½ breaker ......................................................................... 87 TB-34: Bus bar ...................................................................................................................................... 88

Lampiran C – Daftar Teleinformasi (Distribusi) ....................................................................... 89 C-1: Telesignal ...................................................................................................................................... 90 C-2: Telemeasurement ........................................................................................................................ 92 C-3: Tap changer position ................................................................................................................... 93 C-4: Remote control digital .................................................................................................................. 94

Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) ............................................................................................ 95

DA-01: Konfigurasi umum pada double busbar ............................................................................... 96 DA-02: Konfigurasi umum pada single busbar ................................................................................. 99 DB-01: Trafo 150/20 kV dan 70/20 kV tipe 1 .................................................................................. 102 DB-02: Trafo 150/20 kV dan 70/20 kV tipe 2 .................................................................................. 103 DB-03: Trafo 150/20 kV dan 70/20 kV tipe 3 .................................................................................. 104 DB-04: Generator pada konfigurasi double busbar ....................................................................... 105 DB-05: Generator pada konfigurasi single busbar ........................................................................ 106 DB-06: Feeder 20 kV tipe 1 ............................................................................................................... 107 DB-07: Feeder 20 kV tipe 2 ............................................................................................................... 108 DB-08: Feeder 20 kV Tipe 3 ............................................................................................................. 109 DB-09: Bus Section 20 kV tipe 1 ...................................................................................................... 110 DB-10: Bus section 20 kV tipe 2 ....................................................................................................... 111 DB-11: Kopel ....................................................................................................................................... 112 DB-12: Capacitor bay ......................................................................................................................... 113 DB-13: SUTM radial dengan keypoint dan PBO ............................................................................ 114 DB-14: SUTM radial dengan keypoint tanpa PBO ........................................................................ 115 DB-15: SUTM loop dengan beberapa keypoint ............................................................................. 116 DB-16: Spindle 20 kV ......................................................................................................................... 117

Lampiran E – Struktur Informasi ............................................................................................ 118 A. Nomor ID ......................................................................................................................................... 119 B. Time stamp ..................................................................................................................................... 121 C. Nama GI/GH/GT ............................................................................................................................ 121 D. Level Tegangan ............................................................................................................................. 121 E. Nama Bay / Feeder ........................................................................................................................ 122 F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen ................................................ 123 G. Status Peralatan atau Status Alarm ........................................................................................... 123 H. Nama user yang melakukan aksi ................................................................................................ 123 I. Prioritas Alarm .................................................................................................................................. 124 Struktur Informasi Khusus ................................................................................................................. 124

Lampiran F – Simbol dan Warna ........................................................................................... 126

Page 11: SPLN S5.001:2008

SPLN S5.001: 2008

vii

PRAKATA Standar SCADA ini merupakan pengganti dari Pola SCADA SPLN No. 109 Tahun 1996, dalam rangka mengikuti perkembangan teknologi SCADA. Standar ini menjelaskan mengenai master station, komunikasi dan remote station yang terdiri dari enam bagian, yaitu: 1. S3.001: 2008 Peralatan SCADA sistem tenaga listrik 2. S5.001: 2008 Teleinformasi data untuk operasi jaringan tenaga listrik 3. S5.002: 2008 Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik 4. S4.001: 2008 Pengujian sistem SCADA 5. S6.001: 2008 Perencanaan dan pembangunan sistem SCADA 6. S7.001: 2008 Operasi dan pemeliharaan sistem SCADA Keenam standar di atas adalah yang telah diselesaikan dalam tahun 2008 dan direncanakan akan ditambah dengan beberapa standar lainnya mengenai SCADA. Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan pemeliharaan yang memiliki hubungan dengan sistem SCADA. Standar ini dapat menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan pemeliharaan sistem SCADA di PT PLN (PERSERO) secara nasional.

Page 12: SPLN S5.001:2008
Page 13: SPLN S5.001:2008

SPLN S5.001: 2008

1

Teleinformasi Data Untuk Operasi Jaringan Tenaga Listrik

1. Ruang Lingkup

Teleinformasi data terdiri dari telecontrol, telesignal dan telemetering. Sesuai dengan penggunaannya, teleinformasi data dibedakan untuk kepentingan operasi dan kebutuhan pemeliharaan. Standar ini dimaksudkan untuk menetapkan standar teleinformasi data untuk kepentingan operasi dan mencakup sistem transmisi dan sistem distribusi.

Standar ini berlaku untuk sistem SCADA: a. National Control Center, disingkat NCC; b. Inter Regional Control Center, disingkat IRCC; c. Regional Control Center, disingkat RCC; d. Inter Distribution Control Center, disingkat IDCC; e. Distribution Control Center, disingkat DCC.

2. Tujuan

Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam penerapan teleinformasi data bagi kebutuhan operasi sistem transmisi dan sistem distribusi tenaga listrik yang mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakan acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem SCADA yang telah ada.

3. Acuan Normatif

Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam pembuatan standar SCADA: Teleinformasi Data Untuk Operasi Jaringan Tenaga Listrik. a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol – Bagian 1:

Pertimbangan Umum – Seksi 1: Prinsip Umum; b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004,

Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali;

4. Istilah dan Definisi

4.1 Alarm

Perubahan kondisi dari peralatan atau sistem yang telah terdeteksi sebelumnya karena fungsi yang tidak dilakukan oleh operator/dispatcher, atau kegagalan peralatan untuk merespon secara benar. Indikasi alarm berupa audible atau visual, atau keduanya.

Page 14: SPLN S5.001:2008

SPLN S5.001: 2008

2

4.2 Control center

Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan.

4.3 Distribution control center (DCC)

Pusat kendali jaringan distribusi.

4.4 Feeder colouring

Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi bertegangan.

4.5 Gardu hubung

Gardu yang mempunyai fungsi utama melakukan manuver antar feeder.

4.6 Gardu tengah

Gardu yang merupakan titik tengah beban atau titik tengah feeder.

4.7 Earth Fault Indicator (EFI)

Penunjukan arah dari indikator gangguan tanah.

4.8 Inter distribution control center (IDCC)

Pusat kendali yang terhubung dengan beberapa distribution control center.

4.9 Inter regional control center (IRCC)

Pusat kendali yang terhubung dengan beberapa regional control center.

4.10 Keypoint

Peralatan switching dimana bisa dilakukan manuver antara dua feeder atau lebih.

4.11 National control center (NCC)

Pusat kendali yang terhubung dengan beberapa inter regional control center.

4.12 Regional control center (RCC)

Pusat kendali jaringan transmisi tegangan tinggi.

Page 15: SPLN S5.001:2008

SPLN S5.001: 2008

3

4.13 Supervisory control and data acquisition (SCADA)

Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara geografis. [ IEC 870-1-3 ]

4.14 Telecontrol

Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik telekomunikasi. [IEV 371-01-01] CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran, proteksi dan fasilitas tripping, tidak menggunakan pesan suara.

4.15 Telesignal

Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-04]

4.16 Telemetering

Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV 371-01-03]

4.17 Teleprotection

Peralatan komunikasi yang diperlukan oleh sistem proteksi yang berfungsi untuk pengamanan peralatan sistem tenaga listrik.

5. Umum

5.1 Fasilitas SCADA

Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu tengah, key point dan fasilitas sistem tenaga listrik yang baru harus dapat dipantau dari control center dan dilakukan pengujian sebelum diintegrasikan ke sistem transmisi atau sistem distribusi tenaga listrik.

5.2 Teleinformasi data

Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi data untuk operasi jaringan tenaga listrik dapat dilihat pada Lampiran A – Daftar Teleinformasi (Transmisi) sampai dengan Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi).

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi, maka master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi yang digunakan mengacu pada teleinformasi data transmisi dan distribusi.

Page 16: SPLN S5.001:2008

SPLN S5.001: 2008

4

Teleinformasi data untuk kepentingan operasi jaringan tenaga listrik ditampilkan pada workstation dispatcher.

Setiap pembangunan SCADA untuk fasilitas sistem tenaga listrik, kebutuhan teleinformasi datanya harus mengacu pada SPLN S5.001: 2008 Teleinformasi data untuk operasi jaringan tenaga listrik dan SPLN S5.002: 2008 Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik.

5.3 Struktur informasi

Event dan alarm merupakan pemberitahuan kepada dispatcher atau operator tentang kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di data historikal. Struktur informasi event dan alarm SCADA dapat dilihat pada Lampiran E – Struktur Informasi.

5.4 Simbol dan warna

Simbol dan warna diperlukan untuk penyajian diagram sistem tenaga listrik pada monitor dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat informatif dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenali oleh dispatcher. Simbol dan warna dapat dilihat pada Lampiran F – Simbol dan Warna.

6. Perbatasan Kebutuhan Teleinformasi Data

Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan DCC.

6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC

Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 1 dan Gambar 2.

Page 17: SPLN S5.001:2008

SPLN S5.001: 2008

5

a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar.

IRCC

RCC

BUSBAR TT

BUSBAR TET/TT

Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a)

b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1½ Breaker.

IR C C

R C C

B U S B A R T T

B U S B A R T T

B U S B A R T E T /T T

Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b)

6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC

Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukkan pada Gambar 3.

Page 18: SPLN S5.001:2008

SPLN S5.001: 2008

6

B U S B A R T T

B U S B A R T M

L /R

PQVI

R C C

D C C

Gambar 3. Batas wewenang antara RCC dengan DCC

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi data dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP yang berlaku di daerah tersebut.

Page 19: SPLN S5.001:2008

SPLN S5.001: 2008

7

Lampiran A – Daftar Teleinformasi (Transmisi)

Page 20: SPLN S5.001:2008

SPLN S5.001: 2008

8

A-1: Telesignal

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

1 BI Bus isolator switch closed/opened

Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

2 CAM Capasitor Auto/Manual Capasitor D I

3 CB Circuit breaker closed/opened

Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

4 CD Control disable switch RTU D I

5 CSO Check synchronizing override

Gardu induk, Kopel, Feeder, Diameter

D I

6 DCBC Dummy breaker closed/opened Gardu induk D I

7 ES Earth Switch Closed/Opened

Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

8 GUC Generator unit run/stop Generator D I 9 LFA Load frequency available/not available Generator D I

10 LFC Load frequency control on/off switch Generator D I 11 LFR Load frequency request on/off Generator D I 12 LI Line isolator switch closed/opened Feeder, Trafo D I

13 LR Local remote

Gardu induk, Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

14 LRT Local remote switch for tapchanger Trafo D I 15 PSO Power station operated Generator D I

16 RACK Circuit Breaker Rack-In/Rack-Out Distribution Transformer D I

17 RMT Reset Master Trip Gardu induk D I

18 SAM Synchronization Auto/Manual

Gardu induk, Kopel, Feeder, Trafo, Diameter

D I

19 TC Tap changer raise/lower Trafo D I 20 TCC Tap changer auto/manual Trafo D I 21 TFAM Transformer Fan Auto/Manual Transformer D I 22 AQR Automatic power factor regulator active Generator S I 23 AR Circuit breaker auto reclose Feeder S I 24 ARO Auto reclose off Feeder S I 25 AVR Automatic voltage regulator on/off Generator S I

Page 21: SPLN S5.001:2008

SPLN S5.001: 2008

9

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

26 BF Bay fault dc

Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

S A

27 BRF Breaker fault

Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

S A

28 CBTR Circuit breaker trip

Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor, Generator

S A

29 COM Communication faulty Gardu induk S A 30 CSP Check synchronizing in progress Gardu induk S I 31 GOV Free acting governor active Generator S I

32 GTT Generator transformer trip Trafo Generator S A

33 LFF Load frequency control unit failure Generator S A 34 OVR Over voltage relay operate Busbar S A 35 P1BP Busbar protection Busbar S A 36 P1CD Current defferential Feeder S A 37 P1DEF Directional earth fault Feeder S A

38 P1DIF Differential Trafo, Capasitor, Reaktor

S A

39 P1REF Restricted earth fault Trafo S A 40 P1Z1 Distance protection zone 1 Feeder S A 41 P1Z2 Distance protection zone 2 Feeder S A 42 P1Z3 Distance protection zone 3 Feeder S A

43 P2GFR Ground fault relay

Kopel, Feeder, Trafo, Capasitor, Reaktor

S A

44 P2OCR Over current relay

Kopel, Feeder, Trafo, Capasitor, Reaktor

S A

45 P3DTT Direct transfer trip Diameter S A 46 PTF Protection faulty Gardu induk S A 47 PHA Peripheral alarm Gardu induk S A 48 RA Reactor alarm Reactor S A 49 RF Reactor failure Reactor S A 50 RT Reactor Trip Reactor S A 51 RTUA RTU alarm RTU S A 52 SYNF Synchronizing failure Gardu induk S A 53 TAF Tranformer AVR failure Trafo S A 54 TCA Tap changer alarm Trafo S A 55 TCH Tap changer high limit Trafo S A 56 TCL Tap changer low limit Trafo S A 57 TEA Temperature alarm Trafo S A

Page 22: SPLN S5.001:2008

SPLN S5.001: 2008

10

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

58 TET Temperature trip Trafo S A 59 TRA Transformer alarm Trafo S A 60 TRT Transformer trip Trafo S A 61 TTR Teleprotection trip receive Feeder S I 62 TTT Teleprotection trip transmit Feeder S I 63 UT Unit trip Generator S A 64 UVR Under voltage relay Busbar S A 65 VACF Vac failure Gardu induk S A 66 VDCF Vdc failure Gardu induk S A 67 VS Voltage status Busbar S I 68 SIB Software interlocking bypass Gardu Induk S A 69 IEDF IED Faulty Gardu Induk S A 70 SOTF Switch on to fault Gardu Induk S A 71 MTO Master Trip Operate Gardu Induk S A 72 TCT Tap changer trip Trafo S A

Keterangan: A = Announciation of abnormal condition (audible alarm, flashing display, etc) I = Event/Indication (normal condition)

Page 23: SPLN S5.001:2008

SPLN S5.001: 2008

11

A-2: Telemeasurement

No Kode Fungsi Implementasi

1 F Frekuensi Gardu induk

2 I Arus Feeder, InterBus Transformer, Generator Transformer, Kopel

3 P Daya Aktif Feeder, Transformer, Generator

4 POAQ Real power setting Generator

5 PRAQ Maksimum power variation setting Generator

6 Q Daya Reaktif Feeder, Transformer, Generator, Capasitor, Reaktor

7 V Tegangan Feeder, InterBus Transformer, Generator, Busbar

Page 24: SPLN S5.001:2008

SPLN S5.001: 2008

12

A-3: Tap changer position

No Kode Fungsi Implementasi

1 TPI Tap position indication Transformer

Page 25: SPLN S5.001:2008

SPLN S5.001: 2008

13

A-4: Remote control digital

No Kode Fungsi Implementasi

1 BI Bus isolator switch closed/opened Kopel, Feeder, Transformer, Capasitor, Reaktor, Diameter

2 CB Circuit breaker closed/opened Kopel, Feeder, Transformer, Capasitor, Reaktor, Diameter

3 CSO Check synchronizing override Gardu induk

4 DCBC Dummy circuit breaker closed/opened RTU

5 GUC Generator Unit Run/Stop Generator

6 LFR Load frequency request on/off Generator

7 TC Tap changer raise/lower Interbus Transformer

8 TCC Tap changer auto/manual Interbus Transformer

Page 26: SPLN S5.001:2008

SPLN S5.001: 2008

14

A-5: Remote control analog

No Kode Fungsi Implementasi

1 N Load frequency control N_level Generator

2 POOP Real power set point Generator

3 PROP Maksimum power variation set point Generator

Page 27: SPLN S5.001:2008

SPLN S5.001: 2008

15

Lampiran B – Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk)

Page 28: SPLN S5.001:2008

SPLN S5.001: 2008

16

TA-01: Konfigurasi umum pada 1½ breaker

KONFIGURASI UMUM PADA 1½ BREAKER

BUSBAR - A

LFC(Po,Pr,N)

TA-01

BUSBAR - B

Q

L/R

PQV

PQ

I

PQV

PQ

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBT BAY TRAFO TENAGA

VI

PQ

L/R

L/R

L/R

L/R

L/R

L/R

L/R

L/R

L/R

V

V

I

Page 29: SPLN S5.001:2008

SPLN S5.001: 2008

17

Teleinformasi Data Untuk Konfigurasi Umum Pada 1½ Breaker Group Bay Data No Kode Fungsi Tipe Jmh

GARDU INDUK

TM 1 F Frekuensi 1

TSS

29 COM Communication alarm A 1 46 PTF Protection faulty A 1 47 PHA Peripheral alarm A 1 51 RTUA RTU alarm A 1 52 SYNF Synchronizing failure A 1 65 VACF Vac failure A 1 66 VDCF Vdc failure A 1 68 SIB Software interlocking bypass A 1 69 IEDF IED faulty A 1 70 SOTF Switch on to fault A 1 71 MTO Master Trip Operate A 1

TSD

4 CD Control disable switch I 1 5 CSO Check synchronizing override I 1 6 DCBC Dummy breaker closed/opened I 1 13 LR Local remote I 1

RCD 3 CSO Check synchronizing override 1 4 DCBC Dummy breaker closed/opened 1

BUSBAR

TM 7 V Tegangan 2

TSS

26 BF Bay fault DC A 234 OVR Over voltage relay operate A 235 P1BP Busbar protection A 264 UVR Under voltage relay A 267 VS Voltage status A 2

DIAMETER

TSS 27 BRF Breaker fault A 3 28 CBTR CB trip A 3 30 CSP Check synchronizing in progress I 3

TSD

1 BI Bus isolator switch I 6 3 CB Circuit breaker closed/opened I 3 5 CSO Check synchronizing override I 3 13 LR Local remote I 3

RCD 1 BI Bus isolator switch 6 2 CB Circuit breaker closed/opened 3

BAY TRANSMISI

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1

Page 30: SPLN S5.001:2008

SPLN S5.001: 2008

18

Group Bay Data No Kode Fungsi Tipe Jmh 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD 12 LI Line isolator switch closed/opened I 1

BAY IBT

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

3 CB Circuit breaker closed/opened I 1 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD 2 CB Circuit breaker closed/opened I 1 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

BAY TRAFO TENAGA

TM 3 P Daya aktif 1 6 Q Daya reaktif 1

TSS

26 BF Bay fault DC A 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1

TSD 12 LI Line isolator switch closed/opened I 1

BAY REAKTOR

TM 6 Q Daya reaktif 1

TSS

26 BF Bay fault DC A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1

Page 31: SPLN S5.001:2008

SPLN S5.001: 2008

19

Group Bay Data No Kode Fungsi Tipe Jmh 49 RF Reactor failure A 1

TSD 12 LI Line isolator switch closed/opened I 1

BAY GENERATOR

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

19 AQR Automatic power factor regulator on/off I 1 25 AVR Automatic voltage regulator on/off I 1 26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 1 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 1 63 UT Unit trip A 1

TSD

8 GUC Generator unit run/stop I 1 9 LFA Load frequency control available I 1 10 LFC Load frequency control on/off switch I 1 11 LFR Load frequency request on/off I 1 12 LI Line isolator switch closed/opened I 1 15 PSO Power set on/off switch I 1

RCD 5 GUC Generator unit run/stop 1 6 LFR Load frequency request on/off 1

RCA 1 N Load frequency control N_level 1 2 POOP Real power set point 1 3 PROP Maksimum power variation set point 1

KETERANGAN: *) = Khusus untuk OHL Feeder A = Alarm I = Indikasi Untuk LFC ditampilkan di tabel LFC Generator. Rincian Teleinformasi diatas adalah rincian per bay.

Page 32: SPLN S5.001:2008

SPLN S5.001: 2008

20

TA-02: Konfigurasi umum pada double busbar

KONFIGURASI UMUM PADA DOUBLE BUSBAR

BUSBAR - A

LFC (Po,Pr,N)

TA-02

BUSBAR - B

Q P

PQ

I

PQV

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBTBAY TRAFO TENAGA

L/R

Q

BAY KOPEL

V

PQ

I

L/R L/R

V

V

I

QP

V

L/R

L/R L/R L/R

Page 33: SPLN S5.001:2008

SPLN S5.001: 2008

21

Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Bay Data No Kode Fungsi Tipe Jmh

GARDU INDUK

TM 1 F Frekuensi 1

TSS

29 COM Communication alarm A 1 46 PTF Protection faulty A 1 47 PHA Peripheral alarm A 1 51 RTUA RTU alarm A 1 52 SYNF Synchronizing failure A 1 65 VACF Vac failure A 1 66 VDCF Vdc failure A 1 68 SIB Software interlocking bypass A 1 69 IEDF IED faulty A 1 70 SOTF Switch on to fault A 1 71 MTO Master Trip Operate A 1

TSD

4 CD Control disable switch I 1 5 CSO Check synchronizing override I 1 6 DCBC Dummy breaker closed/opened I 1 13 LR Local remote I 1

RCD 3 CSO Check synchronizing override 1 4 DCBC Dummy breaker closed/opened 1

BUSBAR

TM 7 V Tegangan 2

TSS

26 BF Bay fault DC A 234 OVR Over voltage relay operate A 235 P1BP Busbar protection A 264 UVR Under voltage relay A 267 VS Voltage status A 2

KOPEL

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR CB trip A 1 30 CSP Check synchronizing in progress I 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

BAY TRANSMISI

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1

Page 34: SPLN S5.001:2008

SPLN S5.001: 2008

22

Group Bay Data No Kode Fungsi Tipe Jmh 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

BAY IBT

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD

1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

BAY TRAFO TENAGA

TM 3 P Daya aktif 1 6 Q Daya reaktif 1

TSS 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1

Page 35: SPLN S5.001:2008

SPLN S5.001: 2008

23

Group Bay Data No Kode Fungsi Tipe Jmh 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1

TSD 1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

BAY REAKTOR

TM 6 Q Daya reaktif 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 49 RF Reactor failure A 1

TSD 1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

BAY GENERATOR

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 1 25 AVR Automatic voltage regulator on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 1 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 1 63 UT Unit trip A 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 8 GUC Generator unit run/stop I 1 9 LFA Load frequency control available I 1 10 LFC Load frequency control on/off switch I 1 11 LFR Load frequency request on/off I 1 13 LR Local remote I 1 15 PSO Power set on/off switch I 1

Page 36: SPLN S5.001:2008

SPLN S5.001: 2008

24

Group Bay Data No Kode Fungsi Tipe Jmh

RCD

1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 1 6 LFR Load frequency request on/off 1

RCA 1 N Load frequency control N level 1 2 POOP Real power set point 1 3 PROP Maksimum power variation set point 1

KETERANGAN: *) = Khusus untuk OHL Feeder A = Alarm I = Indikasi Untuk LFC ditampilkan di tabel LFC Generator. Rincian Teleinformasi diatas adalah rincian per bay

Page 37: SPLN S5.001:2008

SPLN S5.001: 2008

25

TA-03: Konfigurasi umum pada single busbar

KONFIGURASI UMUM PADA SINGLE BUSBAR

BUSBAR

LFC (Po,Pr,N)

TA-03

QP

V

PQ

I

PQV

PQ

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBTBAY TRAFO TENAGA

Q

VI

V

I

PQ

L/R L/R L/R

L/R

L/R L/R

Page 38: SPLN S5.001:2008

SPLN S5.001: 2008

26

Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar Group Bay Data No Kode Fungsi Tipe Jmh

GARDU INDUK

TM 1 F Frekuensi 1

TSS

29 COM Communication alarm A 1 46 PTF Protection faulty A 1 47 PHA Peripheral alarm A 1 51 RTUA RTU alarm A 1 52 SYNF Synchronizing failure A 1 65 VACF Vac failure A 1 66 VDCF Vdc failure A 1 68 SIB Software interlocking bypass A 1 69 IEDF IED faulty A 1 70 SOTF Switch on to fault A 1 71 MTO Master Trip Operate A 1

TSD

4 CD Control disable switch I 1 5 CSO Check synchronizing override I 1 6 DCBC Dummy breaker closed/opened I 1 13 LR Local remote I 1

RCD 3 CSO Check synchronizing override 1 4 DCBC Dummy breaker closed/opened 1

BUSBAR

TM 7 V Tegangan 1

TSS

26 BF Bay fault DC A 134 OVR Over voltage relay operate A 135 P1BP Busbar protection A 164 UVR Under voltage relay A 167 VS Voltage status A 1

KOPEL

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR CB trip A 1 30 CSP Check synchronizing in progress I 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

BAY TRANSMISI

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1

Page 39: SPLN S5.001:2008

SPLN S5.001: 2008

27

Group Bay Data No Kode Fungsi Tipe Jmh 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

BAY IBT

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD

1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

BAY TRAFO TENAGA

TM 3 P Daya aktif 1 6 Q Daya reaktif 1

TSS 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1

Page 40: SPLN S5.001:2008

SPLN S5.001: 2008

28

Group Bay Data No Kode Fungsi Tipe Jmh 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1

TSD 1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

BAY REAKTOR

TM 6 Q Daya Reaktif 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 49 RF Reactor failure A 1

TSD 1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

BAY GENERATOR

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 1 25 AVR Automatic voltage regulator on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 1 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 1 63 UT Unit trip A 1

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 8 GUC Generator unit run/stop I 1 9 LFA Load frequency control available I 1 10 LFC Load frequency control on/off switch I 1 11 LFR Load frequency request on/off I 1 13 LR Local remote I 1 15 PSO Power set on/off switch I 1

Page 41: SPLN S5.001:2008

SPLN S5.001: 2008

29

Group Bay Data No Kode Fungsi Tipe Jmh

RCD

1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 1 6 LFR Load frequency request on/off 1

RCA 1 N Load frequency control n level 1 2 POOP Real power set point 1 3 PROP Maksimum power variation set point 1

KETERANGAN: *) = Khusus untuk OHL Feeder A = Alarm I = Indikasi Untuk LFC ditampilkan di tabel LFC Generator. Rincian Teleinformasi diatas adalah rincian per bay

Page 42: SPLN S5.001:2008

SPLN S5.001: 2008

30

TB-01: Generator combined cycle pada konfigurasi 1½ breaker

GENERATOR COMBINED CYCLEPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-01

BUSBAR - B

LFC (Po,Pr,N)

PQ

V

Joint Control

I

PQ

PQI

PQI

V

PQ

V

PQ

V

PQ

Page 43: SPLN S5.001:2008

SPLN S5.001: 2008

31

Teleinformasi Data Untuk Generator Combined Cycle Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 3 3 P Daya aktif 7 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 7 7 V Tegangan 4

TSS

22 AQR Automatic power factor regulator on/off I 4 25 AVR Automatic voltage regulator on/off I 4 26 BF Bay fault DC A 3 30 CSP Check synchronizing in progress I 3 31 GOV Free acting governor active I 4 32 GTT Generator transformer trip A 3 33 LFF Load frequency control unit failure A 1 63 UT Unit trip A 4

TSD

3 CB Circuit breaker closed/opened I 2 8 GUC Generator unit run/stop I 4 9 LFA Load frequency control available I 1 10 LFC Load frequency control on/off switch I 1 11 LFR Load frequency request on/off I 1 12 LI Line isolator switch closed/opened I 3 15 PSO Power set on/off switch I 4

RCD 5 GUC Generator unit run/stop 4 6 LFR Load frequency request on/off 1

RCA 1 N Load frequency control N level 1 2 POOP Real power set point 1 3 PROP Maksimum power variation set point 1

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Page 44: SPLN S5.001:2008

SPLN S5.001: 2008

32

TB-02: 2 generator terhubung ke MTR 3-belitan pada konfigurasi 1½ breaker

2 GENERATOR TERHUBUNG KE MTR 3-BELITANPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

LFC (Po,Pr,N)

TB-02

BUSBAR - B

PQ

LFC (Po,Pr,N)

I

PQV

PQV

Page 45: SPLN S5.001:2008

SPLN S5.001: 2008

33

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 3 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 3 7 V Tegangan 2

TSS

22 AQR Automatic power factor regulator on/off I 2 25 AVR Automatic voltage regulator on/off I 2 26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 2 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 2 63 UT Unit trip A 2

TSD

3 CB Circuit breaker closed/opened I 2 8 GUC Generator unit run/stop I 2 9 LFA Load frequency control available I 2 10 LFC Load frequency control on/off switch I 2 11 LFR Load frequency request on/off I 2 12 LI Line isolator switch closed/opened I 1 15 PSO Power set on/off switch I 2

RCD 5 GUC Generator unit run/stop 2 6 LFR Load frequency request on/off 2

RCA 1 N Load frequency control N level 2 2 POOP Real power set point 2 3 PROP Maksimum power variation set point 2

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Page 46: SPLN S5.001:2008

SPLN S5.001: 2008

34

TB-03: 2 generator terhubung ke MTR 3-belitan pada konfigurasi double busbar

2 GENERATOR TERHUBUNG KE MTR 3-BELITANPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-03

BUSBAR - B

PQ

LFC (Po,Pr,N)

LFC (Po,Pr,N)

I

PQV

PQV

L/R

Page 47: SPLN S5.001:2008

SPLN S5.001: 2008

35

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 3 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 3 7 V Tegangan 2

TSS

22 AQR Automatic power factor regulator on/off I 2 25 AVR Automatic voltage regulator on/off I 2 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 2 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 2 63 UT Unit trip A 2

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 3 8 GUC Generator unit run/stop I 2 9 LFA Load frequency control available I 2 10 LFC Load frequency control on/off switch I 2 11 LFR Load frequency request on/off I 2 12 LR Local remote I 1 15 PSO Power set on/off switch I 2

RCD

1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 2 6 LFR Load frequency request on/off 2

RCA 1 N Load frequency control n level 2 2 POOP Real power set point 2 3 PROP Maksimum power variation set point 2

Page 48: SPLN S5.001:2008

SPLN S5.001: 2008

36

TB-04: 2 generator terhubung ke MTR 3-belitan pada konfigurasi single busbar

2 GENERATOR TERHUBUNG KE MTR 3-BELITANPADA KONFIGURASI SINGLE BUSBAR

BUSBAR

TB-04

PQ

LFC (Po,Pr,N)

LFC (Po,Pr,N)

I

PQV

PQV

L/R

Page 49: SPLN S5.001:2008

SPLN S5.001: 2008

37

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 3 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 3 7 V Tegangan 2

TSS

22 AQR Automatic power factor regulator on/off I 2 25 AVR Automatic voltage regulator on/off I 2 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 2 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 2 63 UT Unit trip A 2

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 3 8 GUC Generator unit run/stop I 2 9 LFA Load frequency control available I 2 10 LFC Load frequency control on/off switch I 2 11 LFR Load frequency request on/off I 2 13 LR Local remote I 1 15 PSO Power set on/off switch I 2

RCD

1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 2 6 LFR Load frequency request on/off 2

RCA 1 N Load frequency control n level 2 2 POOP Real power set point 2 3 PROP Maksimum power variation set point 2

Page 50: SPLN S5.001:2008

SPLN S5.001: 2008

38

TB-05: 1 generator terhubung ke MTR 2-belitan pada konfigurasi 1½ breaker

1 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

LFC (Po,Pr,N)

TB-05

BUSBAR - B

PQ

V

I

PQ

Page 51: SPLN S5.001:2008

SPLN S5.001: 2008

39

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 1 25 AVR Automatic voltage regulator on/off I 1 26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 1 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 1 63 UT Unit trip A 1

TSD

8 GUC Generator unit run/stop I 1 9 LFA Load frequency control available I 1 10 LFC Load frequency control on/off switch I 1 11 LFR Load frequency request on/off I 1 12 LI Line isolator switch closed/opened I 1 15 PSO Power set on/off switch I 1

RCD 5 GUC Generator unit run/stop 1 6 LFR Load frequency request on/off 1

RCA 1 N Load frequency control n level 1 2 POOP Real power set point 1 3 PROP Maksimum power variation set point 1

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Page 52: SPLN S5.001:2008

SPLN S5.001: 2008

40

TB-06: 1 generator terhubung ke MTR 2-belitan pada konfigurasi double busbar

1 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

LFC (Po,Pr,N)

TB-06

BUSBAR - B

P

V

QI

PQ

L/R

Page 53: SPLN S5.001:2008

SPLN S5.001: 2008

41

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 1 25 AVR Automatic voltage regulator on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 1 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 1 63 UT Unit trip A 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 8 GUC Generator unit run/stop I 1 9 LFA Load frequency control available I 1 10 LFC Load frequency control on/off switch I 1 11 LFR Load frequency request on/off I 1 13 LR Local remote I 1 15 PSO Power set on/off switch I 1

RCD

1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 1 6 LFR Load frequency request on/off 1

RCA 1 N Load frequency control n level 1 2 POOP Real power set point 1 3 PROP Maksimum power variation set point 1

Page 54: SPLN S5.001:2008

SPLN S5.001: 2008

42

TB-07: 1 generator terhubung ke MTR 2-belitan pada konfigurasi single busbar

1 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI SINGLE BUSBAR

BUSBAR

LFC (Po,Pr,N)

TB-07

P

V

QI

PQ

L/R

Page 55: SPLN S5.001:2008

SPLN S5.001: 2008

43

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 1 25 AVR Automatic voltage regulator on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 1 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 1 63 UT Unit trip A 1

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 8 GUC Generator unit run/stop I 1 9 LFA Load frequency control available I 1 10 LFC Load frequency control on/off switch I 1 11 LFR Load frequency request on/off I 1 13 LR Local remote I 1 15 PSO Power set on/off switch I 1

RCD

1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 1 6 LFR Load frequency request on/off 1

RCA 1 N Load frequency control n level 1 2 POOP Real power set point 1 3 PROP Maksimum power variation set point 1

Page 56: SPLN S5.001:2008

SPLN S5.001: 2008

44

TB-08: 2 generator terhubung ke MTR 2-belitan pada konfigurasi 1½ breaker

Page 57: SPLN S5.001:2008

SPLN S5.001: 2008

45

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 2 25 AVR Automatic voltage regulator on/off I 2 26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 2 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 2 63 UT Unit trip A 2

TSD

3 CB Circuit breaker closed/opened I 2 8 GUC Generator unit run/stop I 2 9 LFA Load frequency control available I 2 10 LFC Load frequency control on/off switch I 2 11 LFR Load frequency request on/off I 2 12 LI Line isolator switch closed/opened I 1 15 PSO Power set on/off switch I 2

RCD 5 GUC Generator unit run/stop 2 6 LFR Load frequency request on/off 2

RCA 1 N Load frequency control n level 2 2 POOP Real power set point 2 3 PROP Maksimum power variation set point 2

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Page 58: SPLN S5.001:2008

SPLN S5.001: 2008

46

TB-09: 2 generator terhubung ke MTR 2-belitan pada konfigurasi double busbar

2 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-09

BUSBAR - B

PQ

LFC (Po,Pr,N)

LFC (Po,Pr,N)

I

PQV

L/R

Page 59: SPLN S5.001:2008

SPLN S5.001: 2008

47

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 2 25 AVR Automatic voltage regulator on/off I 2 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 2 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 2 63 UT Unit trip A 2

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 3 8 GUC Generator unit run/stop I 2 9 LFA Load frequency control available I 2 10 LFC Load frequency control on/off switch I 2 11 LFR Load frequency request on/off I 2 13 LR Local remote I 1 15 PSO Power set on/off switch I 2

RCD

1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 2 6 LFR Load frequency request on/off 2

RCA 1 N Load frequency control n level 2 2 POOP Real power set point 2 3 PROP Maksimum power variation set point 2

Page 60: SPLN S5.001:2008

SPLN S5.001: 2008

48

TB-10: 2 generator terhubung ke MTR 2-belitan pada konfigurasi single busbar

2 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI SINGLE BUSBAR

BUSBAR

TB-10

PQ

LFC (Po,Pr,N)

LFC (Po,Pr,N)

I

PQV

L/R

Page 61: SPLN S5.001:2008

SPLN S5.001: 2008

49

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar

KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.

Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 2 4 POAQ Real power setting 1 5 PRAQ Maksimum power variation setting 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

22 AQR Automatic power factor regulator on/off I 2 25 AVR Automatic voltage regulator on/off I 2 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 31 GOV Free acting governor active I 2 32 GTT Generator transformer trip A 1 33 LFF Load frequency control unit failure A 2 63 UT Unit trip A 2

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 3 8 GUC Generator unit run/stop I 2 9 LFA Load frequency control available I 2 10 LFC Load frequency control on/off switch I 2 11 LFR Load frequency request on/off I 2 13 LR Local remote I 1 15 PSO Power set on/off switch I 2

RCD

1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1 5 GUC Generator unit run/stop 2 6 LFR Load frequency request on/off 2

RCA 1 N Load frequency control n level 2 2 POOP Real power set point 2 3 PROP Maksimum power variation set point 2

Page 62: SPLN S5.001:2008

SPLN S5.001: 2008

50

TB-11: Interbus transformer

(secondary side connected to 1½ breaker)

INTERBUS TRANSFORMERSecondary Side Connected to 1½ Breaker

BUSBAR - A

TB-11

BUSBAR - B

PQ

I

Dioperasikan dari IRCC

Dioperasikan dari RCC Download to RCC

BUSBAR (IRCC)

V

L/R

Page 63: SPLN S5.001:2008

SPLN S5.001: 2008

51

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1½ Breaker)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

12 LI Line isolator switch closed/opened I 2 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

Page 64: SPLN S5.001:2008

SPLN S5.001: 2008

52

TB-12: Interbus transformer

(secondary side connected to double busbar)

INTERBUS TRANSFORMERSecondary Side Connected to Double Busbar

BUSBAR - A

TB-12

BUSBAR - B

BUSBAR (IRCC or RCC)

PQ

IV

Operation Responsibility by IRCC or RCC

Operation Responsibility by RCC

Download to RCC

L/R

L/R

Page 65: SPLN S5.001:2008

SPLN S5.001: 2008

53

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1-2 *) 28 CBTR Circuit breaker trip A 1-2 *) 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

1 BI Bus isolator switch I 2-4 *) 3 CB Circuit breaker closed/opened I 1-2 *) 12 LI Line isolator switch closed/opened I 1-0 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD

1 BI Bus isolator switch 2-4 *) 2 CB Circuit breaker closed/opened 1-2 *) 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 66: SPLN S5.001:2008

SPLN S5.001: 2008

54

TB-13: Interbus transformer

(secondary side connected to single busbar)

INTERBUS TRANSFORMERSecondary Side Connected to Single Busbar

BUSBAR

TB-13

BUSBAR (IRCC or RCC)

PQ

IV

Operation Responsibility by IRCC or RCC

Operation Responsibility by RCC

Download to RCC

L/R

L/R

Page 67: SPLN S5.001:2008

SPLN S5.001: 2008

55

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1-2 *) 28 CBTR Circuit breaker trip A 1-2 *) 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

1 BI Bus isolator switch I 1-3 *) 3 CB Circuit breaker closed/opened I 1-2 *) 12 LI Line isolator switch closed/opened I 1-0 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD

1 BI Bus isolator switch 1-3 *) 2 CB Circuit breaker closed/opened 1-2 *) 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 68: SPLN S5.001:2008

SPLN S5.001: 2008

56

TB-14: Interbus transformer

(secondary side connected to 1½ breaker dilengkapi shunt reaktor pada kumparan tersier)

Page 69: SPLN S5.001:2008

SPLN S5.001: 2008

57

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

12 LI Line isolator switch closed/opened I 3 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

Page 70: SPLN S5.001:2008

SPLN S5.001: 2008

58

TB-15: Interbus transformer

(secondary side connected to double busbar dilengkapi shunt reaktor pada kumparan tersier)

Page 71: SPLN S5.001:2008

SPLN S5.001: 2008

59

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1-2 *) 28 CBTR Circuit breaker trip A 1-2 *) 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

1 BI Bus isolator switch I 2-4 *) 3 CB Circuit breaker closed/opened I 1-2 *) 12 LI Line isolator switch closed/opened I 2-1 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD

1 BI Bus isolator switch 2-4 *) 2 CB Circuit breaker closed/opened 1-2 *) 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 72: SPLN S5.001:2008

SPLN S5.001: 2008

60

TB-16: Interbus transformer

(secondary side connected to single busbar dilengkapi shunt reaktor pada kumparan tersier)

INTERBUS TRANSFORMERSecondary Side Connected to Single Busbar

Dilengkapi Shunt Reaktor Pada Kumparan Tersier

BUSBAR

TB-16

BUSBAR (IRCC or RCC)

PQ

IV

Operation Responsibility by IRCC or RCC

Operation Responsibility by RCC

Download to RCC

Q

L/R

L/R

Page 73: SPLN S5.001:2008

SPLN S5.001: 2008

61

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 2 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1-2 *) 28 CBTR Circuit breaker trip A 1-2 *) 30 CSP Check synchronizing in progress I 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 53 TAF Tranformer avr failure A 1 54 TCA Tap changer alarm A 1 55 TCH Tap changer high limit A 1 56 TCL Tap changer low limit A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1 72 TCT Tap changer trip A 1

TSD

1 BI Bus isolator switch I 1-3 *) 3 CB Circuit breaker closed/opened I 1-2 *) 12 LI Line isolator switch closed/opened I 2-1 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/remote I 1

RCD

1 BI Bus isolator switch 1-3 *) 2 CB Circuit breaker closed/opened 1-2 *) 7 TC Tap changer raise/lower 1 8 TCC Tap changer auto/manual 1

KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 74: SPLN S5.001:2008

SPLN S5.001: 2008

62

TB-17: Bay trafo tenaga pada konfigurasi 1½ breaker

Page 75: SPLN S5.001:2008

SPLN S5.001: 2008

63

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker Data No Kode Fungsi Tipe Jmh

TM 3 P Daya aktif 1 6 Q Daya reaktif 1

TSS

26 BF Bay fault DC A 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1

TSD 12 LI Line isolator switch closed/opened I 1

Page 76: SPLN S5.001:2008

SPLN S5.001: 2008

64

TB-18: Bay trafo tenaga pada konfigurasi double busbar

BAY TRAFO TENAGAPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-18

BUSBAR - B

PQ

TEGANGAN TINGGI

TEGANGAN MENENGAH

DOUBLE BUSBAR

Batas wewenang

L/R

Page 77: SPLN S5.001:2008

SPLN S5.001: 2008

65

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Double Busbar Data No Kode Fungsi Tipe Jmh

TM 3 P Daya aktif 1 6 Q Daya reaktif 1

TSS

26 BF bay fault DC A 1 27 BRF breaker fault A 1 28 CBTR circuit breaker trip A 1 38 P1DIF Differential A 1 39 P1REF restricted earth fault A 1 43 P2GFR ground fault relay A 1 44 P2OCR over current relay A 1 57 TEA temperature alarm A 1 58 TET temperature trip A 1 59 TRA transformer alarm A 1 60 TRT transformer trip A 1

TSD 1 BI bus isolator switch I 2 3 CB circuit breaker closed/opened I 1 13 LR local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

Page 78: SPLN S5.001:2008

SPLN S5.001: 2008

66

TB-19: Bay trafo tenaga pada konfigurasi single busbar

BAY TRAFO TENAGAPADA KONFIGURASI SINGLE BUSBAR

TB-19

BUSBAR

PQ

TEGANGAN TINGGI

TEGANGAN MENENGAH

DOUBLE BUSBAR

Batas wewenang

L/R

Page 79: SPLN S5.001:2008

SPLN S5.001: 2008

67

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Single Busbar Data No Kode Fungsi Tipe Jmh

TM 3 P Daya aktif 1 6 Q Daya reaktif 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 38 P1DIF Differential A 1 39 P1REF Restricted earth fault A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 57 TEA Temperature alarm A 1 58 TET Temperature trip A 1 59 TRA Transformer alarm A 1 60 TRT Transformer trip A 1

TSD 1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

Page 80: SPLN S5.001:2008

SPLN S5.001: 2008

68

TB-20: Bay reaktor pada konfigurasi 1 ½ breaker

BAY REAKTORPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-20

BUSBAR - B

Q

Reaktor

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi 1 ½ Breaker Data No Kode Fungsi Tipe Jmh TM 6 Q Daya Reaktif 1

TSS

26 BF Bay fault DC A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 49 RF Reactor failure A 1

TSD 12 LI Line isolator switch closed/opened I 1

Page 81: SPLN S5.001:2008

SPLN S5.001: 2008

69

TB-21: Bay reaktor pada konfigurasi double busbar

BAY REAKTORPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-21

BUSBAR - B

Q

Reaktor

L/R

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Double Busbar Data No Kode Fungsi Tipe Jmh TM 6 Q Daya Reaktif 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 49 RF Reactor failure A 1

TSD 1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

Page 82: SPLN S5.001:2008

SPLN S5.001: 2008

70

TB-22: Bay reaktor pada konfigurasi single busbar

BAY REAKTORPADA KONFIGURASI SINGLE BUSBAR

TB-22

BUSBAR

Q

Reaktor

L/R

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Single Busbar Data No Kode Fungsi Tipe Jmh TM 6 Q Daya Reaktif 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 49 RF Reactor failure A 1

TSD 1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

Page 83: SPLN S5.001:2008

SPLN S5.001: 2008

71

TB-23: Bay capasitor pada konfigurasi double busbar

BAY KAPASITORPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-23

BUSBAR - B

Q

Capasitor

L/R

Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Double Busbar Data No Kode Fungsi Tipe Jmh TM 6 Q Daya Reaktif 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1

TSD

1 BI Bus isolator switch I 2 2 CAM Capasitor Auto/Manual I 1 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

Page 84: SPLN S5.001:2008

SPLN S5.001: 2008

72

TB-24: Bay capasitor pada konfigurasi single busbar

BAY KAPASITORPADA KONFIGURASI SINGLE BUSBAR

TB-24

BUSBAR

Q

L/R

Capasitor

Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Single Busbar Data No Kode Fungsi Tipe Jmh TM 6 Q Daya Reaktif 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 38 P1DIF Differential A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1

TSD

1 BI Bus isolator switch I 1 2 CAM Capasitor Auto/Manual I 1 3 CB Circuit breaker closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

Page 85: SPLN S5.001:2008

SPLN S5.001: 2008

73

TB-25: Bay penghantar pada konfigurasi 1 ½ breaker

BAY PENGHANTARPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-25

BUSBAR - B

PQVI

Page 86: SPLN S5.001:2008

SPLN S5.001: 2008

74

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi 1 ½ Breaker Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD 12 LI Line isolator switch closed/opened I 1 KETERANGAN:

*) = Khusus untuk OHL Feeder

Page 87: SPLN S5.001:2008

SPLN S5.001: 2008

75

TB-26: Bay penghantar pada konfigurasi double busbar

BAY PENGHANTARPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-26

BUSBAR - B

L/R

QVI

P

Page 88: SPLN S5.001:2008

SPLN S5.001: 2008

76

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Double Busbar Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

KETERANGAN:

*) = Khusus untuk OHL Feeder

Page 89: SPLN S5.001:2008

SPLN S5.001: 2008

77

TB-27: Bay penghantar pada konfigurasi single busbar

Page 90: SPLN S5.001:2008

SPLN S5.001: 2008

78

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Single Busbar Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD

1 BI Bus isolator switch I 1 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 1 2 CB Circuit breaker closed/opened 1

KETERANGAN:

*) = Khusus untuk OHL Feeder

Page 91: SPLN S5.001:2008

SPLN S5.001: 2008

79

TB-28: Bay penghantar paralel dengan reaktor pada konfigurasi double busbar

BAY PENGHANTARPARALEL DENGAN REAKTOR

PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-28

BUSBAR - B

PQV

Q

I

L/R

Page 92: SPLN S5.001:2008

SPLN S5.001: 2008

80

Teleinformasi Data Untuk Bay Penghantar Serial Dengan Reaktor Pada Konfigurasi Double Busbar Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 12 LI Line isolator switch closed/opened I 2 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

KETERANGAN:

*) = Khusus untuk OHL Feeder

Page 93: SPLN S5.001:2008

SPLN S5.001: 2008

81

TB-29: Bay penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker

BAY PENGHANTAR PARALEL DENGAN 1 REAKTOR

PADA KONFIGURASI 1½ BREAKERBUSBAR - A

TB-29

BUSBAR - B

PQVQI

L/R

Page 94: SPLN S5.001:2008

SPLN S5.001: 2008

82

Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½ Breaker Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR Circuit breaker trip A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD 3 CB Circuit breaker closed/opened I 1 12 LI Line isolator switch closed/opened I 2 13 LR Local remote I 1

RCD*) 2 CB Circuit breaker closed/opened 1

KETERANGAN:

*) = Khusus untuk OHL Feeder

Page 95: SPLN S5.001:2008

SPLN S5.001: 2008

83

TB-30: Bay penghantar paralel dengan 2 reaktor seri pada konfigurasi 1½ breaker

BAY PENGHANTAR PARALEL DENGAN 2 REAKTOR SERIPADA KONFIGURASI 1 ½ BREAKER

BUSBAR - A

TB-30

BUSBAR - B

PQV

Q

Q I

Page 96: SPLN S5.001:2008

SPLN S5.001: 2008

84

Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 2 Reaktor seri Pada Konfigurasi 1½ Breaker Data No Kode Fungsi Tipe Jmh

TM

2 I Arus 1 3 P Daya aktif 1 6 Q Daya reaktif 1 7 V Tegangan 1

TSS

23 AR *) Circuit breaker auto reclose I 1 24 ARO *) Auto reclose on/off I 1 26 BF Bay fault DC A 1 30 CSP Check synchronizing in progress I 1 36 P1CD Current differential A 1 37 P1DEF Directional earth fault A 1 40 P1Z1 *) Distance zone 1 A 1 41 P1Z2 *) Distance zone 2 A 1 42 P1Z3 *) Distance zone 3 A 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1 45 P3DTT*) Direct transfer trip A 1 61 TTR Teleprotection trip receive I 1 62 TTT Teleprotection trip transmit I 1

TSD 12 LI Line isolator switch closed/opened I 2 KETERANGAN:

*) = Khusus untuk OHL Feeder

Page 97: SPLN S5.001:2008

SPLN S5.001: 2008

85

TB-31: Bay kopel pada konfigurasi double busbar

BAY KOPELPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-31

BUSBAR - B

L/R

I

Teleinformasi Data Untuk Bay Kopel Pada Konfigurasi Double Busbar Data No Kode Fungsi Tipe Jmh TM 1 I Arus 1

TSS

26 BF Bay fault DC A 1 27 BRF Breaker fault A 1 28 CBTR CB trip A 1 30 CSP Check synchronizing in progress I 1 43 P2GFR Ground fault relay A 1 44 P2OCR Over current relay A 1

TSD

1 BI Bus isolator switch I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1

RCD 1 BI Bus isolator switch 2 2 CB Circuit breaker closed/opened 1

Page 98: SPLN S5.001:2008

SPLN S5.001: 2008

86

TB-32: Bus section

BUS SECTIONTB-32

Tipe-1

L/RTipe-2

L/R

Teleinformasi Data Untuk Bus Section

Data No Kode Fungsi Tipe Jumlah Tipe-1 Tipe-2

TSS

26 BF Bay fault DC A 1 1 27 BRF Breaker fault A 1 28 CBTR CB trip A 1 30 CSP Check synchronizing in progress I 1

TSD

1 BI Bus isolator switch I 2 1 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1 1

RCD 1 BI Bus isolator switch 2 1 2 CB Circuit breaker closed/opened 1

Page 99: SPLN S5.001:2008

SPLN S5.001: 2008

87

TB-33: Bay diameter pada konfigurasi 1½ breaker

BAY DIAMETERPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-33

BUSBAR - B

L/R

L/R

L/R

Teleinformasi Data Untuk Diameter Data No Kode Fungsi Tipe Jmh

TSS 27 BRF Breaker fault A 3 28 CBTR CB trip A 3 30 CSP Check synchronizing in progress I 3

TSD

1 BI Bus isolator switch I 6 3 CB Circuit breaker closed/opened I 3 5 CSO Check synchronizing override I 3 13 LR Local remote I 3

RCD 1 BI Bus isolator switch 6 2 CB Circuit breaker closed/opened 3

Page 100: SPLN S5.001:2008

SPLN S5.001: 2008

88

TB-34: Bus bar

BUS BARTB-34

VBUSBAR - A

Teleinformasi Data Untuk Bus Bar Data No Kode Fungsi Tipe Jumlah TM 7 V Tegangan 1

TSS

26 BF Bay fault DC A 1 34 OVR Over voltage relay operate A 1 35 P1BP Busbar protection A 1 64 UVR Under voltage relay A 1 67 VS Voltage status A 1

Page 101: SPLN S5.001:2008

SPLN S5.001: 2008

89

Lampiran C – Daftar Teleinformasi (Distribusi)

Page 102: SPLN S5.001:2008

SPLN S5.001: 2008

90

C-1: Telesignal

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

1 ARU Auto Recloser Use/Unuse Feeder PBO D I

2 BI Bus Isolator Switch Closed/Opened Feeder Incoming Generator

D I

3 CAM Capacitor Auto/Manual Capacitor D I

4 CB Circuit Breaker Closed/Opened

Bus Coupler Bus Section Feeder Incoming Capacitor Generator PBO

D I

5 DCBC Dummy Breaker Closed/Opened RTU D I

6 GUC Generator Unit Run/Stop Generator D I

7 LBS Load Break Switch Feeder Key Point D I

8 LR Local Remote

Bus Coupler Bus Section Feeder Incoming Keypoint

D I

9 RACK Circuit Breaker Rackin/Rackout Feeder Incoming D I

10 RR Recloser Reset Feeder PBO D I

11 TC Tap Changer Raise/Lower Incoming 20 kV D I

12 TCC Tap Changer Auto/Manual Incoming 20 kV D I

13 AR Circuit Breaker Auto Reclose Feeder PBO S A

14 BRF Breaker Fault

Bus Coupler Bus Section Feeder Capacitor Generator

S A

15 CBTR CB Trip

Bus Coupler Bus Section Feeder Capacitor PBO

S A

16 COM Communication Faulty Comm. Device S A

17 DOOR Door Activated Gardu Induk Gardu Tengah Gardu Hubung

S A

18 FPO Fire Protection Operated Gardu Induk S A

19 FRA Fire Alarm Gardu Induk S A

Page 103: SPLN S5.001:2008

SPLN S5.001: 2008

91

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

20 FRSF Fire Alarm System Failure Gardu Induk S A

21 GTT Generator Transformer Trip Gen Transf S A

22 EFI Earth Fault Indicator Keypoint Gardu Hubung Gardu Tengah

S A

23 P1DEF Directional Earth Fault Feeder S A

24 P2GFR Ground Fault Relay

Bus Coupler Bus Section Feeder Capacitor PBO

S A

25 P2OCR Over Current Relay

Bus Coupler Bus Section Feeder Capacitor PBO

S A

26 PTF Protection Faulty

Bus Coupler Bus Section Feeder Capacitor PBO

S A

27 RTUA Remote Station Alarm RTU IED S A

28 TCH Tap Changer High Limit Incoming 20 kV S A

29 TCL Tap Changer Low Limit Incoming 20 kV S A

30 TPIF Tap Position Indication Failure Incoming 20 kV S A

31 UFR Under Frequency Relay Operate Incoming 20 kV Capacitor S A

32 UT Unit Trip Generator S A

33 VACF VAC Failure Power Supply S A

34 VDCF VDC Failure Power Supply S A

Page 104: SPLN S5.001:2008

SPLN S5.001: 2008

92

C-2: Telemeasurement

No Kode Fungsi Implementasi

1 AMF Ampere Fault (Per Phase) Feeder

2 F Frekuensi Busbar

3 I Arus

Feeder Incoming 20 kV Generator Keypoint PBO

4 P Daya Aktif Feeder Incoming 20 kV Generator

5 PF Power Factor Incoming 20 kV

6 Q Daya Reaktif Incoming 20 kV Capacitor Generator

7 V Tegangan

Busbar Generator Keypoint PBO

8 CCB Counter Of Circuit Breaker

Feeder Incoming 20 kV Capacitor Generator PBO

Page 105: SPLN S5.001:2008

SPLN S5.001: 2008

93

C-3: Tap changer position

No Kode Fungsi Implementasi

1 TPI Tap Position Indication Incoming 20 kV

Page 106: SPLN S5.001:2008

SPLN S5.001: 2008

94

C-4: Remote control digital

No Kode Fungsi Implementasi

1 ARU Auto Recloser use/unuse Feeder PBO

2 CAM Capasitor Auto/Manual Capacitor

3 CB Circuit Breaker Closed/Opened

Bus Coupler Bus Section Feeder Incoming 20 kV Capacitor PBO

4 DCBC Dummy Circuit Breaker Closed/Opened RTU

5 LBS Load Break Switch Close/Open Keypoint Gardu Tengah Gardu Hubung

6 RR Recloser Reset Feeder PBO

7 TC Tap Changer Raise/Lower Incoming 20 kV

8 TCC Tap Changer Auto/Manual Incoming 20 kV

Page 107: SPLN S5.001:2008

SPLN S5.001: 2008

95

Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi)

Page 108: SPLN S5.001:2008

SPLN S5.001: 2008

96

DA-01: Konfigurasi umum pada double busbar

KONFIGURASI UMUM PADA DOUBLE BUSBAR

BUSBAR - A

DA- 01

BUSBAR - B

Q P

GENERATOR

FEEDER

CAPASITOR

INCOMING 20 KV

L/R

Q

PQ

L/R

I

QP

V

L/R L/R L/R

I

PF

V (R)V (S)V (T)

V (R)V (S)V (T)

PI

KOPEL

Page 109: SPLN S5.001:2008

SPLN S5.001: 2008

97

Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Bay Data No Kode Fungsi Tipe Jmh

Busbar TM 2 F Frekuensi 1 7 V Tegangan 6

Feeder

TM

1 AMF Ampere Fault 1 3 I Arus 1 4 P Daya Aktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

13 AR Circuit Breaker Auto Reclose A 1 14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1 31 UFR Under Frequency Relay Operate A 1

TSD

1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 10 RR Recloser Reset I 1

RCD

1 ARU Auto Recloser Use/Unuse 1 3 CB Circuit Breaker Closed/Opened 1 6 RR Recloser Reset 1

Incoming 20 kV

TM

3 I Arus 1 4 P Daya Aktif 1 5 PF Power Factor 1 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS 28 TCH Tap Changer High Limit A 1 29 TCL Tap Changer Low Limit A 1 30 TPIF Tap Position Indication Failure A 1

TSD

2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 11 TC Tap Changer Raise/Lower I 1 12 TCC Tap Changer Auto/Manual I 1

RCD

3 CB Circuit Breaker Closed/Opened 1 7 TC Tap Changer Raise/Lower 1 8 TCC Tap Changer Auto/Manual 1

Capasitor

TM 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD 2 BI Bus Isolator Switch Closed/Opened I 2 3 CAM Capacitor Auto/Manual I 1

Page 110: SPLN S5.001:2008

SPLN S5.001: 2008

98

Group Bay Data No Kode Fungsi Tipe Jmh

4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1

RCD 2 CAM Capacitor Auto/Manual I 1 3 CB Circuit Breaker Closed/Opened 1

Generator

TM

3 I Arus 1 4 P Daya aktif 2 6 Q Daya reaktif 2 7 V Tegangan 1 8 CCB Counter Of Circuit Breaker 1

TSS 14 BRF Breaker fault A 1 15 CBTR Circuit breaker trip A 1 32 UT Unit trip A 1

TSD

2 BI Bus isolator switch I 2 4 CB Circuit breaker closed/opened I 2 6 GUC Generator unit run/stop I 1 8 LR Local remote I 1

RCD 3 CB Circuit breaker closed/opened 1

Kopel

TSS

14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 9 RACK Circuit Breaker Rackin/Rackout I 1

RCD 3 CB Circuit Breaker Closed/Opened 1

Page 111: SPLN S5.001:2008

SPLN S5.001: 2008

99

DA-02: Konfigurasi umum pada single busbar

KONFIGURASI UMUM PADA SINGLE BUSBAR

BUSBAR - A

DA- 02

Q P

GENERATOR

FEEDER

CAPASITOR

INCOMING 20 KV

L/R

Q

PQ

L/R

I

QP

V

L/R L/R

I

PF

V (R)V (S)V (T)

PI

Page 112: SPLN S5.001:2008

SPLN S5.001: 2008

100

Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar Group Bay Data No Kode Fungsi Tipe Jmh

Busbar TM 2 F Frekuensi 1 7 V Tegangan 3

Feeder

TM

1 AMF Ampere Fault 1 3 I Arus 1 4 P Daya Aktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

13 AR Circuit Breaker Auto Reclose A 1 14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1 31 UFR Under Frequency Relay Operate A 1

TSD

1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 1 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 10 RR Recloser Reset I 1

RCD

1 ARU Auto Recloser Use/Unuse 1 3 CB Circuit Breaker Closed/Opened 1 6 RR Recloser Reset 1

Incoming 20 kV

TM

3 I Arus 1 4 P Daya Aktif 1 5 PF Power Factor 1 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS 28 TCH Tap Changer High Limit A 1 29 TCL Tap Changer Low Limit A 1 30 TPIF Tap Position Indication Failure A 1

TSD

2 BI Bus Isolator Switch Closed/Opened I 1 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 11 TC Tap Changer Raise/Lower I 1 12 TCC Tap Changer Auto/Manual I 1

RCD

3 CB Circuit Breaker Closed/Opened 1 7 TC Tap Changer Raise/Lower 1 8 TCC Tap Changer Auto/Manual 1

Capasitor

TM 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD 2 BI Bus Isolator Switch Closed/Opened I 1 3 CAM Capacitor Auto/Manual I 1

Page 113: SPLN S5.001:2008

SPLN S5.001: 2008

101

Group Bay Data No Kode Fungsi Tipe Jmh

4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1

RCD 2 CAM Capacitor Auto/Manual I 1 3 CB Circuit Breaker Closed/Opened 1

Generator

TM

3 I Arus 1 4 P Daya aktif 2 6 Q Daya reaktif 2 7 V Tegangan 1 8 CCB Counter Of Circuit Breaker 1

TSS 14 BRF Breaker fault A 1 15 CBTR Circuit breaker trip A 1 32 UT Unit trip A 1

TSD

2 BI Bus isolator switch I 1 4 CB Circuit breaker closed/opened I 2 6 GUC Generator unit run/stop I 1 8 LR Local remote I 1

RCD 3 CB Circuit breaker closed/opened 1

Page 114: SPLN S5.001:2008

SPLN S5.001: 2008

102

DB-01: Trafo 150/20 kV dan 70/20 kV tipe 1

TRAFO 150/20 KV DAN 70/20 KV DB- 01

TYPE 1

RCC

DCCL/RPQ

I

PF

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 1

Group Bay Data No Kode Fungsi Tipe Jmh

Incoming 20 kV

TM

3 I Arus 1 4 P Daya Aktif 1 5 PF Power Factor 1 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS 28 TCH Tap Changer High Limit A 1 29 TCL Tap Changer Low Limit A 1 30 TPIF Tap Position Indication Failure A 1

TSD

2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 11 TC Tap Changer Raise/Lower I 1 12 TCC Tap Changer Auto/Manual I 1

RCD

3 CB Circuit Breaker Closed/Opened 1 7 TC Tap Changer Raise/Lower 1 8 TCC Tap Changer Auto/Manual 1

Busbar TM 7 V Tegangan 6

Page 115: SPLN S5.001:2008

SPLN S5.001: 2008

103

DB-02: Trafo 150/20 kV dan 70/20 kV tipe 2

TRAFO 150/20 KV DAN 70/20 KV DB -02

TYPE 2

RCC

DCC

PQ

I

PF

L/R

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 2

Group Bay Data No Kode Fungsi Tipe Jmh

Incoming 20 kV

TM

3 I Arus 1 4 P Daya Aktif 1 5 PF Power Factor 1 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS 28 TCH Tap Changer High Limit A 1 29 TCL Tap Changer Low Limit A 1 30 TPIF Tap Position Indication Failure A 1

TSD

2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 9 RACK Circuit Breaker Rackin/Rackout I 1 11 TC Tap Changer Raise/Lower I 1 12 TCC Tap Changer Auto/Manual I 1

RCD

3 CB Circuit Breaker Closed/Opened 1 7 TC Tap Changer Raise/Lower 1 8 TCC Tap Changer Auto/Manual 1

Busbar TM 7 V Tegangan 6

Page 116: SPLN S5.001:2008

SPLN S5.001: 2008

104

DB-03: Trafo 150/20 kV dan 70/20 kV tipe 3

TRAFO 150/20 KV DAN 70/20 KV DB -03

TYPE 3

RCC

DCCPQ

I

PF

L/R

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 3

Group Bay Data No Kode Fungsi Tipe Jmh

Incoming 20 kV

TM

3 I Arus 1 4 P Daya Aktif 1 5 PF Power Factor 1 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS 28 TCH Tap Changer High Limit A 1 29 TCL Tap Changer Low Limit A 1 30 TPIF Tap Position Indication Failure A 1

TSD

2 BI Bus Isolator Switch Closed/Opened I 1 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 11 TC Tap Changer Raise/Lower I 1 12 TCC Tap Changer Auto/Manual I 1

RCD

3 CB Circuit Breaker Closed/Opened 1 7 TC Tap Changer Raise/Lower 1 8 TCC Tap Changer Auto/Manual 1

Busbar TM 7 V Tegangan 3

Page 117: SPLN S5.001:2008

SPLN S5.001: 2008

105

DB-04: Generator pada konfigurasi double busbar

GENERATOR PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

DB-04

BUSBAR - B

P

V

QI

PQ

L/R

Teleinformasi Data Untuk Generator Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

TM

3 I Arus 1 4 P Daya aktif 2 6 Q Daya reaktif 2 7 V Tegangan 1 8 CCB Counter Of Circuit Breaker 1

TSS 14 BRF Breaker fault A 1 15 CBTR Circuit breaker trip A 1 32 UT Unit trip A 1

TSD

2 BI Bus isolator switch I 2 4 CB Circuit breaker closed/opened I 2 6 GUC Generator unit run/stop I 1 8 LR Local remote I 1

RCD 3 CB Circuit breaker closed/opened 1

Page 118: SPLN S5.001:2008

SPLN S5.001: 2008

106

DB-05: Generator pada konfigurasi single busbar

GENERATOR PADA KONFIGURASI SINGLE BUSBAR

BUSBAR

DB-05

P

V

QI

PQ

L/R

Teleinformasi Data Untuk Generator Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

TM

3 I Arus 1 4 P Daya aktif 2 6 Q Daya reaktif 2 7 V Tegangan 1 8 CCB Counter Of Circuit Breaker 1

TSS 14 BRF Breaker fault A 1 15 CBTR Circuit breaker trip A 1 32 UT Unit trip A 1

TSD

2 BI Bus isolator switch I 2 4 CB Circuit breaker closed/opened I 2 6 GUC Generator unit run/stop I 1 8 LR Local remote I 1

RCD CB Circuit breaker closed/opened 1

Page 119: SPLN S5.001:2008

SPLN S5.001: 2008

107

DB-06: Feeder 20 kV tipe 1

FEEDER 20 KVDB - 06

TYPE 1

L/RPI

Teleinformasi Data Untuk Feeder 20 kV Tipe 1

Group Bay Data No Kode Fungsi Tipe Jmh

Feeder 20 kV

TM

1 AMF Ampere Fault 1 3 I Arus 1 4 P Daya Aktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

13 AR Circuit Breaker Auto Reclose A 1 14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1 31 UFR Under Frequency Relay Operate A 1

TSD

1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 10 RR Recloser Reset I 1

RCD

1 ARU Auto Recloser Use/Unuse 1 3 CB Circuit Breaker Closed/Opened 1 6 RR Recloser Reset 1

Page 120: SPLN S5.001:2008

SPLN S5.001: 2008

108

DB-07: Feeder 20 kV tipe 2

FEEDER 20 KVDB - 07

TYPE 2

PI

L/R

Teleinformasi Data Untuk Feeder 20 kV Tipe 2

Group Bay Data No Kode Fungsi Tipe Jmh

Feeder 20 kV

TM

1 AMF Ampere Fault 1 3 I Arus 1 4 P Daya Aktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

13 AR Circuit Breaker Auto Reclose A 1 14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1 31 UFR Under Frequency Relay Operate A 1

TSD

1 ARU Auto Reclose Use/Unuse I 1 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 9 RACK Circuit Breaker Rackin/Rackout I 1 10 RR Recloser Reset I 1

RCD

1 ARU Auto Recloser Use/Unuse 1 3 CB Circuit Breaker Closed/Opened 1 6 RR Recloser Reset 1

Page 121: SPLN S5.001:2008

SPLN S5.001: 2008

109

DB-08: Feeder 20 kV tipe 3

FEEDER 20 KVDB - 08

TYPE 3

IP

L/R

Teleinformasi Data Untuk Feeder 20 kV Tipe 3

Group Bay Data No Kode Fungsi Tipe Jmh

Feeder 20 kV

TM

1 AMF Ampere Fault 1 3 I Arus 1 4 P Daya Aktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

13 AR Circuit Breaker Auto Reclose A 1 14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1 31 UFR Under Frequency Relay Operate A 1

TSD

1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 1 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 10 RR Recloser Reset I 1

RCD

1 ARU Auto Recloser Use/Unuse 1 3 CB Circuit Breaker Closed/Opened 1 6 RR Recloser Reset 1

Page 122: SPLN S5.001:2008

SPLN S5.001: 2008

110

DB-09: Bus Section 20 kV tipe 1

BUS SECTION 20 KVTYPE 1

DB- 09

L/R

Teleinformasi Data Untuk Bus Section 20 kV Tipe 1

Group Bay Data No Kode Fungsi Tipe Jmh

Bus Section 20 kV

TSS

14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1

RCD 3 CB Circuit Breaker Closed/Opened 1

Page 123: SPLN S5.001:2008

SPLN S5.001: 2008

111

DB-10: Bus section 20 kV tipe 2

BUS SECTION 20 KVTYPE 2

DB -10

L/R

Teleinformasi Data Untuk Bus Section 20 kV Tipe 2 Group Bay Data No Kode Fungsi Tipe Jmh

Bus Section 20 kV

TSS

14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 9 RACK Circuit Breaker Rackin/Rackout I 1

RCD 3 CB Circuit Breaker Closed/Opened 1

Page 124: SPLN S5.001:2008

SPLN S5.001: 2008

112

DB-11: Kopel

KOPELDB -11

L/R

Teleinformasi Data Untuk Kopel

Group Bay Data No Kode Fungsi Tipe Jmh

Kopel

TSS

14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1 9 RACK Circuit Breaker Rackin/Rackout I 1

RCD 3 CB Circuit Breaker Closed/Opened 1

Page 125: SPLN S5.001:2008

SPLN S5.001: 2008

113

DB-12: Capacitor bay

CAPACITOR BAYDB -12

Q

L/R

Teleinformasi Data Untuk Capasitor Bay

Group Bay Data No Kode Fungsi Tipe Jmh

Capasitor

TM 6 Q Daya Reaktif 1 8 CCB Counter Of Circuit Breaker 1

TSS

14 BRF Breaker Fault A 1 15 CBTR CB Trip A 1 23 P1DEF Directional Earth Fault A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD

2 BI Bus Isolator Switch Closed/Opened I 2 3 CAM Capacitor Auto/Manual I 1 4 CB Circuit Breaker Closed/Opened I 1 8 LR Local Remote I 1

RCD 2 CAM Capacitor Auto/Manual I 1 3 CB Circuit Breaker Closed/Opened 1

Page 126: SPLN S5.001:2008

SPLN S5.001: 2008

114

DB-13: SUTM radial dengan keypoint dan PBO

SUTM RADIALDENGAN KEYPOINT DAN PBO

DB -13

PBO

KP

L/R

I

I I

IVV (R)

V (S)V (T)

Teleinformasi Data Untuk SUTM radial dengan keypoint dan PBO

Group Bay Data No Kode Fungsi Tipe Jmh

Keypoint

TM 3 I Arus 3 7 V Tegangan 3

TSS 22 EFI Earth Fault Indicator A 3

TSD 7 LBS Load Break Switch Closed/Opened I 1 8 LR Local Remote I 1

RCD 5 LBS Load Break Switch Closed/Opened 1

PBO

TM 3 I Arus 3 7 V Tegangan 3 8 CCB Counter Of Circuit Breaker 1

TSS

13 AR Circuit Breaker Auto Reclose A 1 15 CBTR CB Trip A 1 24 P2GFR Ground Fault Relay A 1 25 P2OCR Over Current Relay A 1 26 PTF Protection Faulty A 1

TSD 1 ARU Auto Recloser Use/Unuse I 1 4 CB Circuit Breaker Closed/Opened I 1 10 RR Recloser Reset I 1

RCD

1 ARU Auto Recloser Use/Unuse 1 3 CB Circuit Breaker Closed/Opened 1 6 RR Recloser Reset

Page 127: SPLN S5.001:2008

SPLN S5.001: 2008

115

DB-14: SUTM radial dengan keypoint tanpa PBO

SUTM RADIALDENGAN KEYPOINT TANPA PBO

DB -14

KP

I

I I

L/R

V (R)V (S)V (T)

Teleinformasi Data Untuk SUTM radial dengan keypoint tanpa PBO

Group Bay Data No Kode Fungsi Tipe Jmh

Keypoint

TM 3 I Arus 3 7 V Tegangan 3

TSS 22 EFI Earth Fault Indicator A 3

TSD 7 LBS Load Break Switch Closed/Opened I 1 8 LR Local Remote I 1

RCD 5 LBS Load Break Switch Closed/Opened 1

Page 128: SPLN S5.001:2008

SPLN S5.001: 2008

116

DB-15: SUTM loop dengan beberapa keypoint

SUTM LOOPDENGAN BEBERAPA KP

DB -15

I

VI

L/R

L/R

L/R

V

V

I

Teleinformasi Data Untuk SUTM loop dengan beberapa keypoint Group Bay Data No Kode Fungsi Tipe Jmh

Keypoint

TM 3 I Arus 3 7 V Tegangan 3

TSS 22 EFI Earth Fault Indicator A 3

TSD 7 LBS Load Break Switch Closed/Opened I 38 LR Local Remote I 3

RCD 5 LBS Load Break Switch Closed/Opened 3

Page 129: SPLN S5.001:2008

SPLN S5.001: 2008

117

DB-16: Spindle 20 kV

SPINDLE 20 kVDB -16

20 kVBusbar

GI

GT

GH

GD

GD

L/RL/R

L/R

L/R L/R L/R L/R

Teleinformasi Data Untuk Spindle 20 kV Group Bay Data No Kode Fungsi Tipe Jmh

Gardu Tengah (GT)

TSS 17 DOOR Door Activated A 1 22 EFI Earth Fault Indicator A 6

TSD 7 LBS Load Break Switch Closed/Opened I 68 LR Local Remote I 6

RCD 5 LBS Load Break Switch Closed/Opened 6 Gardu Hubung (GH)

TSS 17 DOOR Door Activated A 1 22 EFI Earth Fault Indicator A 7

TSD 7 LBS Load Break Switch Closed/Opened I 78 LR Local Remote I 1

RCD 5 LBS Load Break Switch Closed/Opened 7

Page 130: SPLN S5.001:2008

SPLN S5.001: 2008

118

Lampiran E – Struktur Informasi

Page 131: SPLN S5.001:2008

SPLN S5.001: 2008

119

STRUKTUR INFORMASI Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilan bagian, yaitu:

A B C D E F G H I Bagian A: Nomor ID, terdiri dari 6 digit (sebagai primary key) Bagian B: Time stamp, sebanyak karakter 23 karakter Bagian C: Nama GI/GH/GT/KP, sebanyak 20 karakter Bagian D: Level tegangan, sebanyak 5 karakter Bagian E: Nama bay / feeder, sebanyak 20 karakter Bagian F: Kode nama peralatan atau nama alarm atau nama elemen, sebanyak 5 karakter Bagian G: Status peralatan atau status alarm, sebanyak 15 karakter Bagian H: Nama user yang melakukan aksi (seperti remote control, dan sebagainya),

sebanyak 10 karakter Bagian I: Prioritas alarm, sebanyak 8 karakter Struktur di atas ditentukan dalam field yang berbeda. Contohnya dapat dilihat pada Tabel 1.

Tabel 1. Struktur informasi

A B C D E F G H I RCC Cawang 110007 02/03/2007 11:10:05.320 Cawang 150 Gandul-1 BI1 Close Class-3 110009 05/03/2007 07:00:55.115 Gandul 150 Cawang-1 ARO Appear Class-2 RCC Waru 140104 11/04/2007 17:44:21.220 Rungkut 150 Waru-1 LT Disappear Class-1 140085 12/04/2007 20:11:51.312 Waru 150 Bangil-1 CB Invalid Class-4 DCC Pasuruan 430011 25/04/2007 00:30:35.000 Gondang Wetan 20 Bromo CB Open Adi Class-1 430012 19/11/2007 10:00:05.520 Gondang Wetan 20 Semeru CBTR Appear Class-1

A. Nomor ID Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yang menyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTU bersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut

A1 A2 Bagian A1: Kode area Bagian A2: Nomor RTU

Page 132: SPLN S5.001:2008

SPLN S5.001: 2008

120

Kode area Kode area yang terdiri dari 3 karakter adalah sebagai berikut: NCC : 900 IRCC : x00 IRCC Jawa-Bali : 100 IRCC Sumatera : 200 IRCC Kalimantan : 300 IRCC Sulawesi : 400 IRCC di Indonesia Timur : 500 RCC di Jawa-Bali : 1xx RCC Cawang : 110 RCC Cigereleng : 120 RCC Ungaran : 130 RCC Waru : 140 RCC di Sumatera : 2xx RCC Medan : 210 RCC Padang : 220 RCC Palembang : 230 RCC di Kalimantan : 3xx RCC Banjarbaru : 310 RCC Balikpapan : 320 RCC di Sulawesi : 4xx RCC Makassar : 410 RCC Manado : 420 RCC di Indonesia Timur : 5xx IDCC : x00 IDCC Jawa-Bali : 100, 200, 300, 400 IDCC Sumatera : 500, 600 IDCC Kalimantan : 700 IDCC Sulawesi : 800 IDCC di Indonesia Timur : 900 DCC di Jakarta : 0xx – 1xx DCC daerah Jawa bagian Barat : 2xx DCC daerah Jawa bagian Tengah : 3xx DCC daerah Jawa bagian Timur dan Bali : 4xx DCC daerah Sumatera : 5xx – 6xx DCC daerah Kalimantan : 7xx DCC daerah Sulawesi : 8xx DCC daerah Indonesia Timur : 9xx

Nomor RTU Nomor RTU terdiri dari 3 digit (001 – 999)

Page 133: SPLN S5.001:2008

SPLN S5.001: 2008

121

B. Time stamp Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari 23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2 karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakter atau sampai dengan orde milidetik). Contohnya:

25/04/2007 00:30:35.000

19/11/2007 10:00:05.520

C. Nama GI/GH/GT Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter). Contohnya adalah sebagai berikut:

Cawang Gandul Gondang Wetan Rungkut Waru

Cawang : menyatakan GI Cawang (dikontrol oleh RCC Cawang). Gandul : menyatakan GI Gandul (dikontrol oleh RCC Cawang). Waru : menyatakan GI Waru (dikontrol oleh RCC Waru). Rungkut : menyatakan GI Rungkut (dikontrol oleh RCC Waru). Gondang Wetan : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC Pasuruan).

D. Level Tegangan Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada Tabel 2.

Tabel 2. Level tegangan

Tegangan Level Tegangan 500 kV 500 275 kV 275 150 kV 150 70 kV 70 66 kV 66 30 kV 30 25 kV 25

23.5 kV 23 20 kV 20

16.75 kV 16.75 16.5 kV 16.5 13 kV 13 11 kV 11 6 kV 6

Page 134: SPLN S5.001:2008

SPLN S5.001: 2008

122

E. Nama Bay / Feeder Nama Bay/Feeder terdiri dari 20 karakter. Contohnya dapat dilihat pada Tabel 3.

Tabel 3. Nama bay atau feeder

Nama Bay / Feeder Kode Pusat Listrik Pusat Listrik Tenaga Air PLTA Pusat Listrik Tenaga Diesel PLTD Pusat Listrik Tenaga Gas PLTG Pusat Listrik Tenaga Panas Bumi PLTP Pusat Listrik Tenaga Nuklir PLTN Pusat Listrik Tenaga Uap PLTU Pusat Listrik Gas/Uap (Combine Cycle) PLTGU Pusat Listrik Tenaga Mikrohidro PLTMH Pusat Listrik Tenaga Angin/Bayu PLTB Peralatan di Gardu Induk Line Bay (Feeder Bay) Format penulisan:

IRCC/RCC: Nama GI lawan + ”-” + nomor penghantar. Contohnya: o Gandul-1 o Cawang-1

DCC: Nama Feeder. Contohnya: o Bromo o Semeru

Bay ke Unit Generator UNIT Busbar BUSBAR Kopel (Bus Tie) KOPEL Bus Section BUSSECT Trafo TRAFOx (X adalah Kode Tegangan

dari primer dan sekunder trafo) Diameter DAMTR Shunt Reactor SHTXL Shunt Capacitor SHTXC Cadangan SPARE Nama Bay Bay 500 kV diameter 1 busbar A 7A1 Bay 500 kV diameter 3 antara busbar A dan B

7AB3

Bay 500 kV diameter 5 busbar B 7B5

Kode tegangan dari primer dan sekunder trafo dapat dilihat pada Tabel 4. Tabel 4. Kode tegangan dari primer dan sekunder trafo

Tegangan Range Kode Tegangan Rendah (TR) sampai 1000 V 0 Tegangan Menengah (TM) 1 sampai 10 kV 1 Tegangan Menengah (TM) 10 sampai 30 kV 2

Page 135: SPLN S5.001:2008

SPLN S5.001: 2008

123

Tegangan Range Kode Tegangan Menengah (TM) 30 sampai 60 kV 3 Tegangan Tinggi (TT) 60 sampai 90 kV 4 Tegangan Tinggi (TT) 90 sampai 200 kV 5 Tegangan Tinggi (TT) 200 sampai 400 kV 6 Tegangan Ekstra Tinggi (TET) 400 sampai 600 kV 7 Tegangan Ekstra Tinggi (TET) 600 sampai 1000 kV 8 Tegangan Ekstra Tinggi (TET) 1000 kV ke atas 9

F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen Kode nama peralatan atau nama alarm atau nama elemen terdiri dari 5 karakter. Contohnya dapat dilihat pada Tabel 5.

Tabel 5. Kode nama peralatan/alarm/elemen Nama Kode Circuit Breaker CB Bus Isolator #1 BI1 Bus Isolator #2 BI2 Line Isolator LI Ground Fault GF Over Current OC Line Trip LT Breaker Fault BRF Power Supply Faulty PSF Daya MW P Daya MVAr Q Arus I Load Break Switch LBS Recloser REC

Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal, telemeasurement atau remote kontrol seperti ditunjukan pada Lampiran A-D).

G. Status Peralatan atau Status Alarm Status peralatan atau status alarm terdiri dari 15 karakter, menunjukkan status dari peralatan atau alarm pada bagian E. Contohnya adalah sebagai berikut:

Close Open Invalid Appear Disappear On Off

H. Nama user yang melakukan aksi Nama user terdiri dari 10 karakter, menunjukkan nama user yang login pada saat melakukan aksi tertentu seperti Remote Control, Overall Check, start dan stop perangkat keras, out of service RTU dan Inter Center Link, dan sebagainya. Contohnya adalah sebagai berikut:

Page 136: SPLN S5.001:2008

SPLN S5.001: 2008

124

Adi Lukman Jufri Joko Syafnir Kuncoro

I. Prioritas Alarm Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1 merupakan kelas alarm yang menempati prioritas paling tinggi. Contohnya sebagai berikut:

Class-1 Class-2 Class-3 Class-4

Struktur Informasi Khusus Penamaan Pemutus Tenaga Pada Gardu Induk 1 ½ Breaker. Struktur informasi khusus untuk pemutus tenaga pada gardu induk 1 ½ breaker dipakai untuk tujuan komunikasi verbal diantara operator. Kode tersebut hanya ditampilkan di VDU (Video Display Unit), dan dipergunakan di dalam database. Struktur informasi dinyatakan dengan susunan sebagai berikut:

X Y Z

Bagian X: kode referensi tegangan Bagian Y: kode nama CB Bagian Z: nomor diameter

Contoh: A untuk breaker yang terhubung langsung ke busbar A B untuk breaker yang terhubung langsung ke busbar B AB untuk breaker yang terhubung ke breaker A dan breaker B

Contohnya dapat dilihat pada Gambar 4 dan Gambar 5. Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4

Gambar 4. Struktur informasi khusus (bay diameter)

Page 137: SPLN S5.001:2008

SPLN S5.001: 2008

125

Contoh :

GITET 500 kVSAGULING

UNIT 2 UNIT 3 UNIT 4UNIT 1

CIRATA 1 CIRATA 2

BANDUNG SELATAN 2

BUSBAR A

BUSBAR B

CIBINONG 1

7A1

7AB1

7B1

~ ~

7A3

7AB3

7B3

7AB4

7B4

7AB5

7B5

BANDUNG SELATAN 1

~ ~

CIBINONG 2

7A2

7AB2

7B2

Gambar 5. Struktur informasi khusus (gardu induk 1½ breaker)

Page 138: SPLN S5.001:2008

SPLN S5.001: 2008

126

Lampiran F – Simbol dan Warna

Page 139: SPLN S5.001:2008

SPLN S5.001: 2008

127

Simbol-simbol gambar yang digunakan mengacu pada Gambar 6.

SIMBOL GAMBAR

Generator

Circuit Breaker

Circuit Breaker Rack

Isolating Switch

Earthing Switch

Current Transformer

Voltage Transformer

Reaktor

Capacitor Voltage Transformer

Trafo Daya Dua Belitan

Trafo Daya Tiga Belitan

Arus

Tegangan

Frekuensi

Daya aktif

Daya reaktif

Tap Position Indication

Remote Control Digital

Telesignal Single

Local/ Remote

Load Frequency Control

I

V

F

P

Q

TPI

RCD

TSS

L/R

LFC (Po, Pr,N)

Kapasitor

Remote Control AnalogRCA

Telesignal DoubleTSS

Surge / Lightning Arester

( Disconecting Switch)

( 3 phases )

PBO Pemutus Balik Otomatis

Load Break Switch

Gardu Distribusi

Cut out fuse

Gambar 6. Simbol gambar

Page 140: SPLN S5.001:2008

SPLN S5.001: 2008

128

Tampilan-tampilan status yang digunakan mengacu pada Gambar 7. Tampilan Status

GENERATOR

ITEMS SYMBOL R E M A R K

CB CLOSED

CB OPENED

DS CLOSED

DS OPENED

ES CLOSED

ES OPENED

RACKED IN CB CLOSED

Busbar' s color, filled

Busbar' s color, blank

RACKED IN CB OPENED

TRANSF. 2 WINDINGS

TRANSF. 3 WINDINGS

REACTOR

CAPACITOR

LBS CLOSED

LBS OPENED

GARDU PORTALTIANG

GARDU TEMBOK BESI

CUT OUT FUSE

PBO CLOSED

PBO OPENED

Feeder’s color, filledPBO

PBO

RACKED OUT CB CLOSED

RACKED OUT CB OPENED

Feeder’s color, blank

Feeder’s color

Feeder’s color

Feeder’s color, filled

Feeder’s color, blank

Feeder’s color

Feeder’s color

Feeder’s color, filled

Feeder’s color, blank

Feeder’s color, filled

Feeder’s color, blank

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

VOLTAGE STATUS : LIVE

DEAD

/

Gambar 7. Tampilan status

Page 141: SPLN S5.001:2008

SPLN S5.001: 2008

129

WARNA TAMPILAN Tabel 6 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitor dan layar tayang.

Tabel 6. Warna tampilan URAIAN WARNA Single line diagram 500 kV Biru Single line diagram 275 kV Biru-muda Single line diagram 150 kV Merah Single line diagram 70 kV Kuning Single line diagram 30 kV Hijau Single line diagram 20 kV Coklat Single line diagram 12 kV Abu-abu Single line diagram 6 kV Merah muda Single line diagram 0.4 kV Hijau-muda All devices Warna Busbar Invalid device Ungu dan perubahan simbol Device saat loss connection (RTU out of poll) Oranye Background color Hitam Ground color Biru-tua Kondisi tidak bertegangan Putih Perubahan status karena gangguan Frame CB warna merah, blinking Perubahan status karena local dari gardu induk Warna Busbar, blinking + karakter ”L” Perubahan status karena remote dari dispatcher Warna Busbar, blinking Telemetering Putih Invalid telemetering Ungu Telesignal Alarm Warna kuning, blinking

Keterangan: • Untuk change of state gangguan, setelah acknowledge blinking hilang, warna merah pada

frame CB mengikuti warna busbar. • Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan warna pada

single line diagram level tegangan terdekat. • Warna jaringan sesuai dengan feeder colouring. • Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol dan warna.

Page 142: SPLN S5.001:2008

SPLN S5.001: 2008

130

Pengelola Standardisasi: